WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performed by a qualified installer, service agency or the gas supplier
This iComfort® S30 Smart Thermostat is an electronic communication, color display touchscreen, and 7-day programmable interface which communicates directly with a Smart Hub. The Smart Hub stores system parameters and settings in non-volatile memory (i.e., retains data when electrical power fails or is turned off). After online registration is completed, the system may then be accessed by the homeowner from anywhere using a remote Internet connection via a computer or personal communicating device. The iComfort® S30 Smart Thermostat supports the following equipment and features:
Before beginning installation, note the type of equipment, number of stages, and any accessories being installed.
Do
Do Not
Mag-Mount Installation
Mag-Mount LED
LED: A blue LED is visible on the front of the Mag-Mount when it is connected, powered up, and the HD Display has not been installed (see figure 2, step F) or through the top vent of the mag-mount near the top-left corner. (see figure 2, step J) when the HD Display is installed. The LED has three conditions, steady, flashing and off. Those conditions are:
HD Display Installation
CAUTION
Magnets located in this product have far-reaching and strong magnetic fields. They could damage TVs and laptops, computer hard drives, credit and ATM cards, data storage media, mechanical watches, hearing aids and speakers. Keep HD Display and Mag-Mount away from devices and objects that could be damaged by strong magnetic fields.
NOTE: Make sure the Mag-Mount cover is reinstalled correctly to the Mag-Mount base. The cover must be flush with the base or could cause power or communication issues. Do not install HD Display/Mag-Mount on outside walls or in direct sunlight.
The figure below illustrates the basic Lennox communication control wiring to all system components.
DATS NOTE:
Installation of discharge air temperature sensor (DATS) (88K38) must comply with the following requirements:
OAS NOTE
The optional outdoor air (temperature) sensor (OAS) (X2658) wiring distance to either the comfort furnace control or comfort air handler control should not exceed 200 feet when wired with an 18-gauge thermostat wire. Installation of OAS must comply with the following requirements:
THERMOSTAT WIRING NOTE
Thermostat control wiring runs are as follows:
IMPORTANT: PRIOR TO RUNNING THE ICOMFORT S30 SMART THERMOSTAT INSTALLER SETUP, ELECTRIC HEAT MUST BE MANUALLY CONFIGURED!
IMPORTANT: After electric heat strips are installed, the air handler control must be manually configured to detect the number of electric heat sections. (See also 506181-01 for a complete configuration guide.)
This procedure is applicable only to the CBX32MV-XX-230-6-06 and higher and CBX40UHV (all models). To configure the heat strips so that they will be detected by the thermostat:
A Lennox-managed local network provides a means for a mobile device using the iComfort Mobile Setup application to communicate directly to a Smart Hub. The iComfort Mobile Setup application running on a mobile device cannot reach a Smart Hub through the Internet or through the home Wi-Fi network.
The mobile device must be:
NOTE – A router with Bonjour capabilities is required for this function. Check the router functions if the Smart Hubs does not connect. Apple Bonjour® is an implementation of Zero-configuration networking (Zeroconf), a group of technologies that includes service discovery, address assignment, and host name resolution.
Local Home Wi-Fi Network)
Up to five (5) Smart Hubs, each controlling a separate HVAC system in a home, can be connected together over a local home Wi-Fi network.
Lennox Center Push Button Switch
The Smart Hub center push button switch:
NOTE: The only way to add another Smart Hub to the Lennox Manage Network is via the Group ID assignment.
The identity of devices requesting connection to a Smart Hub is rigorously authenticated before connection is allowed to ensure that only iComfort® S30 Smart Thermostat devices connect to a Smart Hub.
Smart Hub Indicators and Connectors
These LEDs have a red LED chip and a green LED chip in the package and can show red, green, or amber colors, steady or flashing.
As a general rule:
Center Push Button Indicator
The center push button has an RGB (red-green-blue) LED backlight that
indicates the Lennox-managed local network communication status of the Smart Hub, and if the Smart Hub is transferring a software image from a flash drive plugged into the USB port. While this LED indicator can show any color, it is currently limited to amber, green, or blue.
When the Smart Hub is in a normal steady state, — when the Smart Hub is in normal day-to-day operation the center push button backlight shows
This application tool is used by dealers to commission a S30 Smart Thermostat a system using a Wi-Fi-enabled mobile device.
Operating System Requirements
The iComfort Mobile Setup application is available for both IOS 6.0 and higher (App Store) and Android 4.1 and higher (Google Play).
Commissioning
To commission a system using the iComfort Mobile Setup application:
Service
To use the iComfort Mobile Setup application as a service tool, the commissioning of the system must have already been completed.
Alternative Method
From the home screen, go to menu > settings > advanced settings > pair Smart Hub to iComfort dealer mobile app selection. It will auto-connect to the dealer app and start you at the dealer control center screen. The following screen will appear and show the status of the connection. Once connected the screen will automatically disappear.
Multiple Smart Hub(s)
When there are multiple Smart Hubs installed in the home, all that are in the same group and are connected to the same home Wi-Fi access point will automatically find and connect to each other through a special Lennox-managed local network running on the home Wi-Fi. Each thermostat can then see and control all the other thermostats in that group.
Restarting Smart Hub
RESETTING SMART HUB – Pressing the center Lennox button for more than five seconds will restart the SMART HUB.
IMPORTANT: PRIOR TO RUNNING THE ICOMFORT S30 SMART THERMOSTAT INSTALLER SETUP, AIR HANDLER ELECTRIC HEAT MUST BE MANUALLY CONFIGURED! SEE PAGE 12.
The following procedures are written for the installer setup using the HD Display.
When power is first applied to the system all communicating devices attached to the system (air handler or furnace, outdoor unit or zoning control) will automatically be configured using optimal factory default settings based on system type, capacity and other configuration considerations.
This menu provides access to the dealer for performing various functions as listed below:
Equipment
Selections listed in this section are dependent on system hardware configuration. Not all options will be available.
NOTE – When changing the default settings for any parameter, there is a possibility that it will affect the settings for another parameter. If this happens, a pop-up message will be displayed listing the other affected parameters and their new automatically set values.
The following is a complete list of all possible parameters under the System. Parameters actually available are dependent on the Lennox communicating equipment type detected and non-communicating equipment added.
About
This screen provides information concerning language supported, equipment type name, control software revision, model, control mode number, control serial number, control hardware revision, protocol revision number, device product level, 24VAC average power consumption, 24VAC peak power consumption, compatible devices list, application code memory size and micro-controller part number.
Equipment Name
A unique name can be assigned to this component. The name can be up to 29 characters. A name can consist of letters, numbers, special characters, and spaces. The default name is Subnet Controller.
Temp Reading Calibration
The range is -5.0 to 5.0°F. Default is 0.0°F
If it is determined that the actual temperature being detected at the thermostat is off based on independent readings using other ambient temperature reading devices, the display can be adjusted using this setting.
Humidity Reading Calibration
The range is -10.0 to 10.0%. The default is 0.0%
If it is determined that the actual humidity percentage being detected at the thermostat is off based on independent readings using other humidity reading devices, the display can be adjusted using this setting.
Smooth Setback Recovery (SSR)
When enabled, smooth setback begins recovery up to two hours before the programmed time so that the programmed temperature is reached at the corresponding programmed event time. Assume 12°F per hour for first-stage gas/electric heating and 6°F per hour for first-stage compressor-based heating or cooling. With Smooth Set Back disabled, the system will start recovery at the programmed time. Options are enabled or disabled. Default is enabled.
The SSR set point calculation is as follows:
Rules for SSR:
Gas Heating Activation Temp Difference
Range is 0.5 to 10°F. The default is 1.5°F. Adjustments are in increments of 0.5°F. When the system is a dual-fuel and steady-state while operating at full HP demand, this is the amount of °F below the set point that is allowed before allowing to switch to gas heat.
Gas Heat Control Mode (SLP98 only)
Options are Staged, Load Tracking Variable Capacity and Variable Capacity. The default is Staged.
Staged
Some furnaces can be configured to provide up to four stages of gas heat operation. When staged heating is chosen, the iComfort® S30 Smart Thermostat allows you to choose between 1, 2, 3 and 4 stages of heat. Single-stage heat: 1st stage provides 100% of full capacity.
Load Tracking Variable Capacity
Load tracking variable capacity will smoothly track the load (sensible temperature changes) up and down and adjust the furnace heating rate both ways.
Variable Capacity
Variable capacity only tracks the load upward (rising temperature). Variable capacity uses the iComfort® S30 Smart Thermostat stage differentials but not stage timers.
Number of Gas Heating Stages
This is applicable to the SLP98V only. Number of selectable stages when Gas Heat Control Mode is set in “Staged” mode. Options are 1 through 4. Default is 4. \
Understanding Modulating Step Change and Steady State PI Gains
Each of these terms has a multiplier (or gain) associated with it called the proportional gain and the integral gain respectively and affect responsiveness and stability
Modulating Gas Heating Steady State PI Gain (SLP98V only)
This is applicable to the SLP98V only. Steady-state gain controls the demand when the system is not responding to a sensed temperature change away from the iComfort® S30 Smart Thermostat setting. Options are Less Aggressive, Standard and More Aggressive. Default is Standard. Recommend not changing this setting.
Modulating Gas Heating Step Change PI Gain (SLP98V only)
This is applicable to the SLP98V only. Step change gains to deal with set point changes and affects how fast the system reaches the next set point (Example: Adjustment to the iComfort® S30 Smart Thermostat setting).
Options are Less Aggressive, Standard, and More Aggressive. The default is Standard. Recommend not changing this setting.
Modulating Gas Heating Cycles Per Hour (SLP98V only)
This feature is activated when the structure BTU load is less than the minimum Heat Pump heating capacity of the outdoor unit. The system will be cycled “ON” and “OFF” at the selected cycles per hour to maintain the settings of the iComfort® S30 Smart Thermostat. (This governs how many cycles per hour the system will try to run when it needs to run at less than minimum capacity). Range is 4 to 10 cycles. Default is 6 cycles. Adjustments are in increments of 0.5 cycles.
Modulating HP Heating Steady State PI Gain (Lennox modulating Heat Pumps)
Steady state gain controls the demand when the system is not responding to a sensed temperature change away from the iComfort® S30 Smart Thermostat setting.
Options are Less Aggressive, Standard and More Aggressive. Default is Standard. Recommend not changing this setting.
Modulating HP Heating Step Change PI Gain (Lennox Modulating Heat Pumps)
Step change gains deal with set point changes and affects how fast the system reaches the next set point (Example: Schedule change or adjustment to the iComfort® S30 Smart Thermostat setting). Options are Less Aggressive, Standard and More Aggressive. Default is Standard. Recommend not changing this setting.
Modulating HP Heating Cycles Per Hour(Lennox Modulating Heat Pumps)
This feature is activated when the structure BTU load is less than the minimum Heat Pump heating capacity of the outdoor unit. The system will be cycled “ON” and “OFF” at the selected cycles per hour to maintain the settings of the iComfort® S30 Smart Thermostat. (This governs how many cycles per hour the system will try to run when it needs to run at less than minimum capacity). Range is 3 to 6 cycles. Default is 4 cycles. Adjustments are in increments of 0.5 cycles.
Aux Heating Activation Threshold
This is an adjustment to hasten or delay the aux heat activation. This adjusts how far below the set point the temperature must fall with the HP at 100% before allowing electric heat to come on.
Range is 0 – 10°F with increments of 0.25°F. The default setting is 2.5°F.
Cooling Mode
Options are Normal and Comfort. The default is Normal. When changing to Comfort Mode, several parameters are automatically modified for optimal system operations. The changed parameters are listed on the screen when set to Comfort.
Modulating Cooling Steady State PI Gain (Lennox Modulating Outdoor Units Only)
Steady-state gain controls the demand when the system is not responding to a sensed temperature change away from the iComfort® S30 Smart Thermostatsetting. Options are less aggressive, standard and more aggressive. Default is standard.
Modulating Cooling Step Change PI Gain (Lennox Modulating Outdoor Units)
Step change gains deal with set point changes and affects how fast the system reaches the next set point. Options are less aggressive, standard and more aggressive. Default is standard.
Modulating Cooling Cycles Per Hour (Lennox Modulating Outdoor Units Only)
This feature is activated when the structure BTU load is less than the minimum outdoor unit cooling capacity of the outdoor unit. The system will be cycled “ON” and “OFF” at the selected cycles per hour to maintain the settings of the iComfort® S30 Smart Thermostat. (This governs how many cycles per hour the system will try to run when it needs to run at less than minimum capacity). Range is 3 to 6 cycles hours. Can be adjusted in increments of 0.5. Default is 4.
DAT Offset
(Lennox Modulating Outdoor Units Only and Discharge Air Temperature Sensor Installed)
The default is 0.0°F. The range is -5.0°F to 5.0°F in increments of 0.5°F.
DAT Proportional Gain
(Lennox Modulating Outdoor Units Only)
Default is 10.0. Range is 7.0 to 13.0 in increments of 0.5. This is how the system attempts to reach the discharge air temperature set point. Lennox advises not to make changes to this setting without first contacting Lennox technical support or Lennox field technical consultant.
DAT Integral Gain (Lennox Modulating Outdoor Units Only)
Default is 10.0. Range is 7.0 to 13.0 in increments of 0.5. The indicates how stable the system is attempting to reach the discharge air temperature set point. You may hear the compressor hunting (ramping up and down) adjusting to lower setting will correct.
Lennox advises not to make changes to this setting without first contacting Lennox technical support or Lennox field technical consultant.
Temperature Control Mode
Options are Normal and Comfort. Default is Normal. The Feels-Like feature factors in the outdoor temperature and indoor humidity for a more accurate control of the temperature in the home. Either an outdoor temperature sensor is used or Internet Weather is enabled for this feature to operate. Modifying this setting here will also change the feature status on the user settings screen.
PARAMETERS | DESCRIPTIONS |
SSP Heating Cancel Coast Counter Increment Slope | The range is 0 to 0.75°F. Default is 0.25°F. Adjustments are in increments of 0.125°F |
SSP Heating Cancel Coast Counter Decrement Slope | The range is 0.25 to 2°F. The default is 0.5°F. Adjustments are in increments of 0.125°F |
SSP Cooling Cancel Coast Counter Increment Slope | Range is -0.75 to 0.0°F. Default is -0.25°F. Adjustments are in incre ments of 0.125°F. |
SSP Cooling Cancel Coast Counter Decrement Slope | Range is -2.0 to -0.25°F. Default is -0.5°F. Adjustments are in incre ments of 0.125°F. |
SSP Heating Lockout Outdoor Temp | When the outdoor temperature is above this setting, heating is not al lowed if single set point is running. Range is 50 to 80°F. Default is 70°F. Adjustments are in increments of 1.0°F. |
SSP Cooling Lockout Outdoor Temp | When the outdoor temperature is below this setting, cooling is not al lowed if single set point is running. Range is 30 to 60°F. Default is 40°F. Adjustments are in increments of 1.0°F. |
Heat Cool (H/C) Stages Lock in default is disabled (heat/cool stages are turned off separately). If changed to Enabled, heat/cool stages are turned off together (see figures 13 through 20).
NOTE – For non-variable speed systems only.
Cooling Prognostics
This algorithm will determine whether the unit will run out of capacity during the hottest time of summer. It will look back every day a minimum of three days to see if there is a pattern and compare it to the hottest day on record for that zip code before triggering a notification. It must see a pattern before it will trigger the notification. There may be a component or components that will require attention. The sensitivity (threshold) selection options are OFF, LOW, MEDIUM, and HIGH. The default is HIGH. The alert code notification is 65545.
Group ID
Default is Group ID is 1. Range is 0 to 9. When there are multiple Smart Hubs installed in a home, each can be assigned to a group. Each group can contain up to eight Smart Hubs. All Smart Hubs within a particular group can communicate with all other Smart Hubs in that group over the home Wi-Fi network. Smart Hubs in one group cannot see or interact with Smart Hubs in another group, however.
For example, seven Smart Hubs in a home can be divided up as one in Group 1 and six in Group 2, four in Group 1 and three in Group 2, and so on. Smart Hubs in Group 1 will not be able to see or interact with the Smart Hubs in Group This allows the intentional isolation of the Smart Hub for the master bedroom from the Smart Hub for the children’s area, for example.
If a Smart Hub is set to Group 0, there will be no connectivity with another Smart Hub.
The following is information on all possible available parameters. Parameters listed are dependent on actual type of heat pump installed.
About
This screen provides information concerning language supported, equipment type name, unit model number, unit serial number, unit nominal capacity, number of heating states, number of cooling stages, heating capacity by stage, cooling capacity by stage, control software revision, control model number, control serial number, control hardware revision, outdoor air temp sensor, protocol revision number, device product level, 24VAC average power consumption, 24VAC peak power consumption, line voltage average power consumption, line voltage peak power consumption, outdoor inverter model number, outdoor inverter firmware version, outdoor fan RPM profile, unit code, compatible devices list, application code memory size and micro-controller part number.
Equipment Name
A unique name can be assigned to this component. Name can be up to 29 characters. Name can consist of letters, numbers, special characters and spaces.
Compressor Short Cycle Delay
(Single and Two-Stage iComfort Outdoor Units)
The range is 60 – 300 seconds. Default is 300 seconds and with an incremental adjustment of 60 seconds.
This feature prevents the compressor from being short cycled any time the compressor is turned “OFF”
Defrost Termination Temp
(Single and Two-Stage iComfort Heat Pumps)
The range is 50 – 100°F. Default is 50°F and with an incremental adjustment of 10°F.
This is the temperature that defrost mode will be terminated. In dual fuel applications (furnace and heat pump), defrost tempering is automatically enabled and operates as follows:
Compressor Shift Delay ON / OFF
(Single and Two-Stage iComfort Outdoor Units)
The options are ON or OFF. By default it is set to ON.
The following is information on all possible available parameters. Parameters listed are dependent on actual type of air conditioner installed.
About
This screen provides information concerning language supported, equipment type name, unit model number, unit serial number, unit nominal capacity, number of cooling stages, cooling capacity by stage, control software revision, control model number, control serial number, control hardware revision, outdoor air temp sensor, protocol revision number, device product level, 24VAC average power consumption, 24VAC peak power consumption, line voltage average power consumption, line voltage peak power consumption, outdoor inverter model number, outdoor inverter firmware version, outdoor fan RPM profile, unit code, compatible devices list, application code memory size and micro-controller part number.
The following is information on all possible available parameters for Lennox communicating air handlers.
About
Provides information concerning unit code, language support, equipment type name, unit model number, unit serial number, unit nominal capacity, number of heating states, heating capacity by stage, indoor blower CFM range, control software revision, control model number, control serial number, control hardware revision, discharge air temp sensor, outdoor air temp sensor, protocol revision number, device product level, factory installed transformer, 24VAC average power consumption, 24VAC peak power consumption, line voltage average power consumption, line voltage peak power consumption, compatible devices list, applicable code memory size, and micro-controller part number.
About
This screen provides information on unit code, language supported, equipment type name, unit model number, unit serial number, unit nominal capacity, number of heating stages, heating capacity by stage, indoor blower CFM range, control software revision, control model number, control serial number, control hardware revision, discharge air temp sensor, outdoor air temp sensor, protocol revision number, device product level, factory installed transformer, 24VAC average power consumption, 24VAC peak power consumption, line voltage average power consumption, line voltage peak power consumption, compatible devices list, application code memory size and micro-controller part number.
Parameter Name | Description |
Low Heating Discharge Temp | Range is 105 to 135°F. Adjustable in increments of 5F. Default is 120°F. |
High Heating Discharge Temp | Range is 115 to 145°F. Adjustable in increments of 5F. Default is 130°F. |
About
This provides information on unit code, language supported, equipment type name, control software revision, control model number, control serial number, control hardware revision, protocol revision number, device product level, 24VAC average power consumption, 24VAC peak power consumption, compatible devices list, application code memory size, micro-controller part number, max number of zones, supported damper types, number of damper positions, zone temp sensor 1, zone temp sensor 2, zone temp sensor 3 and zone temp sensor 4.
About
This screen provides information concerning model number, serial number, hardware revision, software revision, language support and equipment type name.
Screen Locked
Options are unlocked, partially locked and locked. Default is unlocked.
About
This provides information on equipment type name, control hardware revision, control software revision, control serial number and control model number.
Add / Remove Equipment
This selection allows the installer to add or remove non-communicating 24VAC
controlled equipment such as outdoor units, humidifiers and dehumidifiers.
Selections on this screen allow S30 iComfort and HVAC equipment to be restarted, reconfigured, or reset to factory defaults.
Notifications
See table on page 48 for a complete list of all alert codes.
Tests
Verify Airflow Per Zone is the first screen to appear under this selection. If no zoning is installed, zone airflow settings will be for zone 1 only. If zoning equipment is detected by the system then zones 1 through 4 will be listed. These screens allow for verification and modification of CFMs for blower, heating and cooling circulation. Touch continue to proceed to the next screen. Select Test to Run is the next screen to appear. Depending on hardware present, various tests are available. By default all items to be tested are enabled. Selecting a specific test will un-check the item. When a specific set of tests are completed the results will be displayed on the screen next to the tested item. Touch continue to proceed to the next set of test items. Once all tests are completed press done to return to the touch tests to run screen. Touch the left arrow at the top left side of screen to return to the Dealer Control Center.
This screen allows the installer to test all major communicating components of the system indoor unit (air handler or furnace), outdoor unit (air conditioner or heat pump) and zoning control (if applicable). Pressing the stop diagnostics button will pause the diagnostic function. Touch the left arrow at the top left side of screen to return to the Dealer Control Center.
The overview screen provides information on dealer and customer information. Also included under day of install section is information on conditions at the time of installation. Information includes date, time indoor and outdoor temperatures and indoor humidity. Under equipment, system, indoor/outdoor and zoning model number, serial number and firmware information is displayed.
Other menus items include system indoor and outdoor units and zoning control parameter settings.
NOTE – Installation Report is not available until after exiting the dealer control center following commissioning. Return to the dealer control center from the home screen to view the installation report.
Information
Home Address
On this screen general information needs to be verified or changed. Touch any line item to change its contents. Information to be added is address 1, address 2, state, city and zip/postal code.
Complete the requested information and press the continue button.
For firmware version 3.15 and later, all controls for dehumidification under menu > settings > humidity. Under Humidity Control, select dehumidify to enable dehumidification. By default it is disabled.
When dehumidify is enabled, the options are as follows and are dependent on equipment type and accessory installed.
Dehumidification Setting Options
Table 1. Dehumidification Control Modes of Operations
Normal | √ Both Staged and Modulating Outdoor Units: Dehumidifies while servicing a cooling demand and will not overcool. The overcool slider is hidden from the user. Modulating units use the “comfort” table to run the system, regardless of the presence of a discharge air temperature sensor (DATS). | |||
Max | √ Staged Outdoor Unit: If at the start or during a cooling call, the humidity is above the relative humidity set point then the unit dehumidifies during the cooling demand. If at the time the cooling call terminates, the humidity demand is not satisfied, overcooling will occur up to the overcooling slider setting in an attempt to satisfy the dehumidification demand. Once the room temperature reaches the overcooling set point. If the system still has a dehumidification demand, the system keeps using the overcooling set point as its operating cooling set point (will not wait for the tempera ture to rise to the normal cooling set point to run again) until the dehumidification demand is satisfied √ Modulating Outdoor Unit: | |||
˃ Modulating units work as described as staged outdoor units and if a discharge air temperature sensor (DATS) sensor is installed, the DAT PI is used to control the compressor speed to maintain a cold coil for optimized dehumidification. | ||||
˃ If a DATS is not installed, the system runs using the outdoor unit’s “comfort” tables during dehumidification. | ||||
√ Staged Outdoor Unit: At the end of a cooling call, if the humidity is above the set point by a certain amount (Basic to Precision Threshold parame ter), then overcooling to the overcooling slider setting occurs to satisfy the dehumidification demand. Once the room temperature reaches the overcooling set point, if the system still has a dehumidification demand, the system keeps using the overcool set point as its operating cooling set point (will not wait for the temperature to rise to the normal cooling set point to run again) until the dehumidification demand is satisfied. | ||||
√ Modulating Outdoor Unit: | ||||
˃ If at the start or during a cooling call, the humidity level is below the relative humidity set point by more than 10%, then the mode becomes “Dry” such that the blower CFM is increased to the “Dry” table setting. | ||||
Dehumidification Only | Climate IQ (Auto) | ˃ If a cooling call starts with the humidity level below the relative humidity setpoint, or if during a cooling call, the humidity level is between the dehumidify off relative humidity point and the relative humidity set point -10, then standard cooling runs to satisfy the cooling demand, without any added dehumidification. | ||
˃ If at the start or during a cooling call, the humidity is above the relative humidity set point then the unit dehumidifies during the cooling demand. If at the time the cooling call terminates, the humidity is above the Basic to Precision Threshold then then overcooling will occur up to the slider setting in an attempt to satisfy the dehumidification demand. Once the room temperature reaches the overcool set point, if the system still has a dehumidification demand, the system keeps using the overcool set point as its operating cooling set point (does not wait for the tempera ture to rise to the normal cooling set point to run again) until the dehumidification demand is satisfied. | ||||
˃ The Basic to Precision Threshold is a parameter with the following properties: Definition: Relative humidity amount above the relative humidity setpoint where overcooling will occur to dehumidify. Default: 4, Min: 0, Max: 10, Inc: 1 | ||||
˃ Modulating units use the “comfort” table to run the system, regardless of the presence of a DATS. | ||||
overcooling | ||||
Available only with Max and Climate IQ (Auto) | ||||
1 Modulating outdoor units are XC20, XP20, XC25 and XP25. NOTE – The above information is applicable only for non-zoning systems. For the iComfort S30 Smart Thermostat using firmware version 3.15 or later. There is no dehumidification capacity in zoning systems. |
Complete iComfort® Systems — Furnace and Air Conditioner
An iComfort® gas furnace (G71MPP, EL296V, SLP98, SL280) with an iComfort® air conditioner (SL18XC, XC17, XC20, XC21 or XC25 only) unit.
TIPS
An outdoor temperature sensor is provided in all iComfort® outdoor units. To display the outdoor temperature on the home screen of the HD Display, you can enable this feature under the dealer control center. Use the following procedure to enable the outdoor temperature sensor display.
To enable the Indoor Humidity Display on the Home screen use the following procedure:
Dual fuel system using an iComfort® gas furnace (G71MPP, EL296V, SLP98, SL280) with an iComfort® heat pump (SL18XP, XP17, XP17N, XP21, XP21N, XP20 and XP25 only).
TIPS
An outdoor temperature sensor is provided in all iComfort® outdoor. To display the outdoor temperature on the home screen of the HD Display, you can enable this feature under the dealer control center. Use the following procedure to enable the outdoor temperature sensor display.
To enable the Indoor Humidity Display on the Home screen use the following procedure:
Complete iComfort® Systems — Air Handler and Air Conditioner
An iComfort® air handler (CBX32MV or CBX40UHV) with an iComfort® air conditioner (SL18XC, XC17, XC20, XC21 or XC25).
IMPORTANT! Be sure to configure the air handler control so that heat strips (if used) information will be detected by the iComfort® S30 Smart Thermostat. This must be done prior to powering up the system and control system.
TIPS
If the HD Display “System Setting” does not offer a choice for “emerg. heat” or the electric heat will not function; the electric heat has not been configured. Configure the electric heat as described on page 12, or for complete detail, see the air handler installation instructions. Reconfigure the iComfort® system by entering the installer program and selecting the setup button and following the prompts. An outdoor temperature sensor is provided in all iComfort® outdoor. To display the outdoor temperature on the home screen of the HD Display, you can enable this feature under the dealer control center. Use the following procedure to enable the outdoor temperature sensor display.
To enable the Indoor Humidity Display on the home screen use the following procedure:
An iComfort® air handler (CBX32MV or CBX40UHV) with an iComfort® heat pump (SL18XP, XP17, XP17N, XP20, XP21, XP21N or XP25) unit.
IMPORTANT! Be sure to set up the air handler control for heat strips (if used) prior to powering up the system and thermostat.
TIPS
If the HD Display “System Setting” does not offer a choice for emerg. heat or the electric heat will not function; the electric heat has not been configured. Configure the electric heat as described on page 12, or for complete detail, see the Air Handler installation instructions. Reconfigure the iComfort® system by entering the installer program and selecting the setup button and following the prompts. An outdoor temperature sensor is provided in all iComfort® outdoor units. To display the outdoor temperature on the home screen of the HD Display, you can enable this feature under the dealer control center. Use the following procedure to enable the outdoor temperature sensor display.
An iComfort® as furnace (G71MPP, EL296V, SLP98 and SL280) with a conventional non-communicating Lennox brand air conditioner.
TIPS
If the HD Display home screen mode touch only lists heat only or off choices and does not offer a choice for cooling or heat/cool you must add the non-communicating air conditioning unit. Use the following procedures from the Home screen to add a non-communicating air conditioner.
On two-stage air conditioners you must cut the “W915 2 Stage Compr” link on the furnace control.
Partial iComfort® System — iComfort® Furnace and Non-Communicating Lennox Brand (Conventional) Heat Pump Unit (Dual-Fuel)
If using a conventional non-communicating heat pump unit in an iComfort® dual-fuel system then a iComfort® Equipment Interface Module must be used and set up as a communicating heat pump.
An iComfort® air handler (CBX32MV or CBX40UHV) with a conventional non-communicating Lennox brand heat pump unit.
IMPORTANT! Be sure to set up the air handler control for heat strips (if used) prior to powering up the system and iComfort® S30 Smart Thermostat.
TIPS
If the HD Display “System Setting” does not offer a choice for emerg. heat or the electric heat will not function; the electric heat has not been configured. Configure the electric heat as described on page 12, or for complete detail, see the air handler installer program. To start the reconfiguration option: HOME screen menu icon
An outdoor temperature sensor is provided in all iComfort® outdoor units. To display the outdoor temperature on the home screen of the HD Display, you can enable this feature under the dealer control center. Use the following procedure to enable the outdoor temperature sensor display.
The iComfort® Equipment Interface Module (EIM) can be configured in the following setups:
TIPS
An outdoor temperature sensor is provided in all iComfort® outdoor units. To display the outdoor temperature on the home screen of the HD Display, you can enable this feature under the dealer control center. Use the following procedure to enable the outdoor temperature sensor display.
To enable the Indoor Humidity Display on the Home screen use the following procedure
G71MPP or SLP98 Furnace Setting Adjustment
If your iComfort® S30 Smart Thermostat is being used with either a G71MPP or SLP98 furnace and is set to variable-capacity mode of operation (the iComfort® default with these units), the system’s settings for stage timers are ignored (even if shown enabled in the S30 Smart Thermostat Control System). The stage timer will be used on the cooling side for other cooling units except the XC20, SL18XC1/XP1 and XC/XP25 where they are not used. The furnace software sets and controls the firing rates. The only other controlling factor is the stage temperature differentials. In Load-Tracking Variable Capacity (default for these furnaces), both stage timers and temperature differentials are ignored.
FCC Compliance Statement — Part 15.19
This device complies with Part 15 of the FCC Rules.
Operation is subject to the following two conditions:
FCC Interference Statement — Part 15.105 (b)
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one of the following measures:
RF Exposure Information
This equipment complies with FCC radiation exposure limits set forth for an uncontrolled environment. In order to avoid the possibility of exceeding the FCC radio frequency exposure limits, human proximity to the antenna shall not be less than 20cm during normal operation.
Replacement Parts
The following iComfort® S30 Smart Thermostat component parts can be ordered:
Table 2. S30 Replacement Components
Catalog # | Component | Remarks |
12X97 | HD Display | Thermostat interface |
12X98 | Smart Hub | Control base |
12X99 | Mag-Mount | Wall mount for HD Display |
13X01 | Wall plate | Wall plate for Mag-Mount (use is optional) |
X5393 | Temporary Wall plate | For electrical J box installation |
Replacement iComfort Component Controls
These kits have been set up for replacement of the iComfort® controls. Please note that control kits are unit-specific.
Table 3. Replacement Controls
iComfort® Unit | Replacement Kit Catalog # | Control Part # |
G71MPP (rev. 03 or later) | 65W69 | 605341-01 |
SLP98 (rev. 01 or later) | 10G43 | 102813-03 |
SL280 (rev. 02 or later) | 83W88 | 103130-04 |
EL296 (rev. 01 or later) | 83W88 | 103130-04 |
CBX40UHV (rev. 02 or later) and CBX32MV (rev. 06 or later) | 65W70 | 605341-02 |
XC17 | 11H36 | 103369-04 |
XP17 and XP17N | 11H36 | 103369-04 |
XP19 (rev. 06 or later) | 11H36 | 103369-04 |
XC21 (rev. 04 or later) and SL18XC | 11H36 | 103369-04 |
SL18XP, XP21 and XP21N | 11H36 | 103369-04 |
XP20 and XP25 | 13U31 | 103686-06 |
XC20 and XC25 | 13U31 | 103686-06 |
iComfort® Thermostat App (Homeowner)
The free iComfort® Thermostat app is available for use on iPhone® and iPad®, Android™ devices.
Control cooling/heating temperatures, fan operation, set programs and set Away mode for multiple locations.
Also controls individual zone settings if system is equipped with the optional iHarmony® Zoning System.
iComfort® Mobile Setup App (Installer)
Allows the installer to commission the system and remotely turn the system on and off during setup on any iPhone®,
iPad® and Android™ device.
App Store (iPhone, iPad)
Google play (Android)
Apple, the Apple logo, iPhone and iPad are trademarks of Apple Inc. registered in the US and other countries.
Android is a trademark of Google Inc. Use of this trademark is subject to Google permission
Notifications
These screens provide information on active notifications and previously cleared notifications. When selecting either a cleared or active notification a brief description and alert code will be displayed.
Notifications are categorized by system, indoor unit (air handler or furnace), outdoor unit (air conditioner or heat pump), zoning control (if installed) and iComfort® S30.
To expand a specification notification to access a more detail description of the alert code, press the down arrow to expand the description. See table 1 for details on alert codes and troubleshooting advice.
Communication System: When communication controls are operating in a communication system, all jumper and link setting on controls are ignored. Jumpers and link setting are treated as defaults and would only be active if the system was converted to a non-communicating system.
Alert Codes and Troubleshooting | Initial notification of critical alerts will pop up on the home screen and will be listed under notification menu. Minor and moderate alerts are found only under the notification menu. * Current Lennox modulating outdoor units are XC/XP20 and XC/XP25. | ||||
Alert Code | Priority Condition | Applicable System Component(s) | Actual Displayed Alert Text | Component or System Operational State and Troubleshooting Tip | How to clear alert code |
10 |
Critical |
Thermostat |
Unknown Device Detected – DEVICE2 | The iComfort® S30 when NOT in configuration mode has detected an unknown device. Typically the thermostat will send a command to the unknown device and place the device into a soft disable state. The soft disable control will indicate so as follows: √ On air handler, furnace and outdoor controls, the soft-disabled state is displayed by double horizontal lines on seven-segment display. √ On the damper control module, the green LED will blink 3 seconds on and 1 second off. √ On the equipment interface module, the green LED will blink 3 seconds on and 1 second off. √ A new communicating device has been added to the system since the original configuration setup was completed. √ Go to menu > advance settings > view dealer control center > equipment and press reset all equipment. This will allow the system to auto-detect any iComfort® components attached. |
Clear alert code by reconfiguring the system. |
11 |
Critical |
Thermostat |
Missing DEVICE2 | The thermostat cannot find a previously installed system component. √ Check all system components (devices) connections to make sure they are iComfort®-compatible. √ Cycle system power. √ If problem persists, then check all system components (devices) connections to make sure they are iComfort®-compatible. √ Go to menu > advance settings > view dealer control center > equipment and press reset all equipment. This will allow the system to auto-detect any iComfort® components attached. |
Cycle system power, and If prob lem persists then clear by recon figuring the system. |
Alert Codes and Troubleshooting | Initial notification of critical alerts will pop up on the home screen and will be listed under notification menu. Minor and moderate alerts are found only under the notification menu. * Current Lennox modulating outdoor units are XC/XP20 and XC/XP25. | ||||
Alert Code | Priority Condition | Applicable System Component(s) | Actual Displayed Alert Text | Component or System Operational State and Troubleshooting Tip | How to clear alert code |
12 |
Critical |
Thermostat |
Incomplete System | Thermostat did not find an indoor unit. Make sure there is an iComfort® indoor unit on the system. √ Check for voltage and missing component. √ Check R, i+, i- and C connections. √ Ohm wires for electrical continuity. √ Cycle power to both indoor unit first and then thermostat. √ Verify that equipment interface module (if applicable) is configured as either an air handler or furnace when used with a non-communicating indoor unit. √ Go to menu > advance settings > view dealer control center > equip ment and press reset all equipment. This will allow the system to auto-de tect any iComfort® components attached. √ Replace indoor unit control if there is no response. |
Automatically clears when the system detects that the issue no longer exists. |
13 |
Critical |
Thermostat |
Duplicate Comfort Sensor ID | S30 Control System found more than one outdoor unit, or more than one indoor unit, or more than one thermostat connected to the system. S30 Con trol System will display the message “Too Many Devices of the Same Type”. √ Check wiring and remove duplicate equipment. √ Go to menu > advance settings > view dealer control center > equip ment and press reset all equipment. This will allow the system to auto-de tect any iComfort® components attached. |
Automatically clears when the system detects that the issue no longer exists. |
14 |
Critical |
Thermostat |
Too Many Devices of the Same Type | The thermostat found more than one thermostat, indoor or outdoor unit on the system. √ Check wiring and remove duplicate equipment. √ Go to menu > advance settings > view dealer control center > equip ment and press reset all equipment. This will allow the system to auto-de tect any iComfort® components attached. | Automatically clears when the system detects that the issue no longer exists. |
18 |
Minor |
Thermostat | Low Ambient HP Heat Lockout | The outside temperature is below the level where the heat pump is pro grammed to heat the home. The system will not use the heat pump to warm your home. √ Outdoor temperature is below the low balance point. √ Heat pump will not be used to service a heating demand. | This is a notification only alert code. Will automatically clear once the outdoor temperature rises above the low balance point. |
19 |
Minor |
Thermostat |
High Ambient Auxiliary Heat Lockout | The outside temperature is higher than the level where the furnace or elec tric heat is programmed to work. The system will only use the heat pump to warm your home. √ This is a notification only alert code. √ Outdoor temperature is above the low balance point. √ Indoor unit (furnace or air handler) will not be used to service a heating de mand. |
Automatically clears when the system detects that the issue no longer exists. |
29 |
Critical |
Thermostat |
Over Temperature Protection | The thermostat is reading an indoor temperature that is higher than 90ºF (factory default). The thermostat will not allow any heating operation to begin until it senses an indoor temperature lower than 90ºF. Indoor temperature rose above 90ºF during a heating or cooling demand. √ Heating operation is not allowed. √ Check to ensure that heating equipment is not stuck ON (reversing valve, etc.) √ Check the accuracy of the thermostat temperature sensor. √ Select cooling system mode to cool the indoor space below 90ºF. |
Automatically clears when the system detects that the issue no longer exists. |
Alert Codes and Troubleshooting | Initial notification of critical alerts will pop up on the home screen and will be listed under notification menu. Minor and moderate alerts are found only under the notification menu. * Current Lennox modulating outdoor units are XC/XP20 and XC/XP25. | ||||
Alert Code | Priority Condition | Applicable System Component(s) | Actual Displayed Alert Text | Component or System Operational State and Troubleshooting Tip | How to clear alert code |
30 |
Moderate |
Thermostat |
Low Temperature Protection | The thermostat will not allow any cooling operation to begin until it senses a temperature higher than 40ºF. √ Cooling operation is not allowed. √ Check to ensure that cooling equipment is not stuck ON. √ Check accuracy of the thermostat temperature sensor. √ Select heating system mode to heat the indoor space to above 40ºF. |
Automatically clears when the system detects that the issue no longer exists. |
31 |
Critical |
S30 Smart Hub |
Lost Communication with DEVICE2 | The applicable system component (indoor, equipment interface or damper control module or outdoor unit) has not communicated with thermostat for more than three minutes. √ Check connections and voltages. √ Ohm wires for electrical continuity. √ If float switch is installed on air handler drain pain, check condensate line to ensure it is not clogged and tripping the float switch connected in series with R terminal. |
√ If fault persists, then cycle pow er. √ Fault clears after communica tion is restored. |
32 |
Moderate |
S30, furnace, air handler or outdoor unit |
Asynchronous Reset DEVICE2 | The applicable system component (device) is resetting itself. This issue may occur during a power outage or power fluctuation in the system. If persistent or if it coincides with the system operations then proceed with the following troubleshooting steps. √ Check the power connections. √ Check the amp draw at the transformer (the transformer maybe overload ed). √ Check 24VAC voltage at the system component (device). √ If the fault persists after checking the connections, replace the applicable control. |
To clear the alert code, go to menu > settings > advanced settings > view dealer control center > notifications and select the alert code and press the clear button. |
34 |
Critical |
Indoor or outdoor unit |
Must Program Unit Capacity for DEVICE2 | The thermostat does not know the capacity (tonnage) of the indoor or out door unit. The applicable system component is missing the programmed unit capacity. √ Remove power to thermostat before programming the unit control. √ Go to applicable unit control and program the unit capacity manually (see the unit installation instruction for configuration instructions). √ Once configuration is complete then reconnect thermostat wires. √ Go to menu > advance settings > view dealer control center > equip ment and press reset all equipment. This will allow the system to auto-de tect any iComfort® components attached and their capacities. |
Automatically clears when the system detects that the issue no longer exists. |
36 |
Critical |
Thermostat |
Heating when Not Requested DEVICE2 | The system has been heating for at least 15 minutes without a demand for heating. √ Run the system in diagnostic mode and verify that it matches actual equip ment operation. Go to menu > settings > advance settings > dealer con trol center > diagnostics and press the start diagnostics button. √ Check for other alert codes that may be preventing the system from operat ing as expected. √ Check all heating equipment to determine cause of heating demand. √ Recycle power. |
Automatically clears when the system detects that the issue no longer exists. |
Alert Codes and Troubleshooting | Initial notification of critical alerts will pop up on the home screen and will be listed under notification menu. Minor and moderate alerts are found only under the notification menu. * Current Lennox modulating outdoor units are XC/XP20 and XC/XP25. | ||||
Alert Code | Priority Condition | Applicable System Component(s) | Actual Displayed Alert Text | Component or System Operational State and Troubleshooting Tip | How to clear alert code |
37 |
Critical |
Thermostat |
Cooling when not Requested DEVICE2 | The system has been cooling for at least 15 minutes, without a demand for cooling. √ Run the system in diagnostic mode and verify that it matches actual equip ment operation. Go to menu > settings > advance settings > dealer con trol center > diagnostics and press the start diagnostics button. √ Check for other alert codes that may be preventing the system from operat ing as expected. √ Check all cooling equipment to determine cause of cooling demand. √ Recycle power. |
Automatically clears when the system detects that the issue no longer exists. |
38 |
Critical |
Thermostat |
Not Heating when Requested DEVICE2 | The system has not been able to turn on the heating for more than 45 min utes. √ The system will go offline for 60 minutes and will attempt to restart itself. √ Run the system in diagnostic mode and verify that it matches actual equip ment operation. Go to menu > settings > advance settings > dealer con trol center > diagnostics and press the start diagnostics button. √ Check for other alert codes that may be preventing the system from operat ing as expected. √ Check all heating equipment to determine cause. √ Recycle power. |
Automatically clears when the system detects that the issue no longer exists. |
39 |
Critical |
Thermostat |
No Cooling when Requested DEVICE2 | The system has not been able to turn on the cooling for more than 45 min utes. √ The system will go offline for 60 minutes and will attempt to restart itself. √ Run the system in diagnostic mode and verify that it matches actual equip ment operation. Go to menu > settings > advance settings > dealer con trol center > diagnostics and press the start diagnostics button. √ Check for other alert codes that may be preventing the system from operat ing as expected. √ Check all cooling equipment to determine cause. √ Recycle power. |
This alert code will automatically clear when the system detects the issue no longer exists. |
Alert Codes and Troubleshooting | Initial notification of critical alerts will pop up on the home screen and will be listed under notification menu. Minor and moderate alerts are found only under the notification menu. * Current Lennox modulating outdoor units are XC/XP20 and XC/XP25. | ||||
Alert Code | Priority Condition | Applicable System Component(s) | Actual Displayed Alert Text | Component or System Operational State and Troubleshooting Tip | How to clear alert code |
40 |
Minor |
Heat pump, furnace, and iHarmony |
HP Heating Lockout. | The heat pump could not increase the room temperature 0.5°F towards the set point in 30 minutes. In order to use the gas furnace as a primary heating source (not defrost tempering) when the outdoor temperature is between the high and low bal ance points, the heat pump: √ Must be used for a minimum of 30 minutes and the temperature in the zone not increase by more than 0.5°F √ Has not gone into defrost in the 30 minute period. The default for HP Heating Lockout Time default is 120 minutes and will lock the heat pump off when the outdoor temperature is above the high balance point. Selectable range is 60 to 240 minutes. √ Go to menu > settings > advance settings > dealer control center > equipment > Smart Hub and located HP Heating Lockout Time to verify the lockout time setting. NOTE – HP Heating Lockout Time is only available in a zoning system. If any single zone satisfies the aforementioned conditions, the heat pump is stopped and the gas furnace is used to satisfy all heat calls for the next duration of the parameter heat pump lockout time. After the heat pump lock out is expired, the heat pump is once again used as the primary heat source. √ Run system and verify that the heat pump cannot raise the room tempera ture 0.5F in 30 minutes on the zone or zones. √ Check air flow to the zones or zones. √ Check discharge air temperatures. √ Check calibration of room thermostat. √ Set the low balance point and high balance point as close together as possi ble. (This is 3°F difference – Example: Set high balance point at 40°F and low balance point would set at 37°F). Go to menu > settings > advance settings > dealer control center > equipment > Smart Hub and located Low and High Balance Points. √ When below the low balance point, the indoor unit will heat the home be tween the low and high balance point, the heat pump and furnace will heat the home. When the outdoor temperature is above the high balance point, the gas furnace is locked out and all the heat is provided by the heat pump. |
Clears when heat pump comes out of HP Heating Lockout Time. |
41 | Moderate | Furnace, air handler or outdoor control | Component control has been replaced. | This alert code will appear anytime a component control [Furnace, air han dler, air conditioner or heat pump] is replaced in the system. | Must be cleared manually. |
105 |
Critical | Thermostat, furnace, air handler, outdoor unit, equipment interface or IHarmony |
Communication Problem | A system component has lost communication with the system. System com ponent (device) is unable to communicate. √ This may indicate the existence of other active alert codes. √ In most cases errors are related to electrical noise. Verify that high voltage power is separated from the low voltage communication wires. √ Check for incorrectly wired or loose connections between system compo nents (devices). √ Check for a high voltage source of noise close to the system. |
Automatically clears when the system detects the issue no longer exists. |
110 | Critical | Furnace | Low AC Line Voltage | The component AC line voltage is too low. This alert code may appear dur ing a brownout. Or when line voltage is below its designed operating value. √ Check and correct the power line voltage. | Automatically clears when the system detects the issue no longer exists. |
Alert Codes and Troubleshooting | Initial notification of critical alerts will pop up on the home screen and will be listed under notification menu. Minor and moderate alerts are found only under the notification menu. * Current Lennox modulating outdoor units are XC/XP20 and XC/XP25. | ||||
Alert Code | Priority Condition | Applicable System Component(s) | Actual Displayed Alert Text | Component or System Operational State and Troubleshooting Tip | How to clear alert code |
111 | Critical | Furnace | Line Polarity Reversed | The unit is reporting that its power and neutral lines are reversed. √ Turn off the power to the system and correct the line power voltage wiring. √ System resumes normal operation five seconds after critical condition is re covered. | Automatically clears when the system detects the issue no longer exists. |
112 |
Critical |
Furnace |
No Ground Connection | The reporting component cannot find earth ground. The thermostat will shut down the system. √ Provide proper earth ground to the equipment. √ System resumes normal operation five seconds after critical condition is re covered. | Automatically clears when the system detects the issue no longer exists. |
113 | Critical | Furnace | High AC Line Voltage | Line voltage high (voltage higher than nameplate rating). √ Provide power voltage within proper range. √ System resumes normal operation five seconds after critical condition is re covered. | Automatically clears when the system detects the issue no longer exists. |
114 |
Moderate / Critical |
Furnace, air handler, equipment interface or IHarmony |
AC Line Frequency / Distortion Prob | There is a frequency / distortion problem with the power to a specific system component. There is a frequency / distortion problem with the power to a specific system component. √ This alert code may indicate transformer overloading. √ Check the voltage and line power frequency. √ Check the generator operating frequency, if the system is running on back- up power. √ Correct voltage and frequency problems. √ System will resume normal operation five seconds after fault recovered. √ All applicable system component outputs are disabled – moderate condi tion. √ After 10 minutes, the priority condition is escalated – critical condition. √ Damper control module will operate in central mode only until proper volt age is restored or frequency distortion is resolved – moderate condition. |
Automatically clears when the system detects the issue no longer exists. |
115 |
Critical |
Furnace, air han dler, equipment in terface module and IHarmony |
Low Secondary (24VAC) Voltage | 24VAC power to a system component control is lower than the required range of 18 to 30VAC. √ Check and correct voltage. √ Check for additional power-robbing system components (devices) con nected to system. √ This alert code may require the installation of an additional or larger VA transformer. √ Damper control module will operate in non-zone mode until proper voltage is restored. |
Automatically clears when the system detects the issue no longer exists. |
116 | Critical | Furnace or Air Handler | High Secondary (24VAC) voltage | √ IComfort® S30 Control system will display this code when 24VAC power is high (18 to 30 VAC). √ Will display Furnace or Air Handler High Secondary (24VAC) voltage. | Check and correct voltage. Check for proper line voltage (120V, 240V, etc.) to equipment. Clears when control senses proper volt age. |
117 | Minor | Furnace | Poor Ground | The reporting unit has poor earth grounding. √ Provide proper grounding for the system component (device). √ Check for proper earth ground to the system. | Automatically clears 30 seconds after the issue is corrected. |
Alert Codes and Troubleshooting | Initial notification of critical alerts will pop up on the home screen and will be listed under notification menu. Minor and moderate alerts are found only under the notification menu. * Current Lennox modulating outdoor units are XC/XP20 and XC/XP25. | ||||
Alert Code | Priority Condition | Applicable System Component(s) | Actual Displayed Alert Text | Component or System Operational State and Troubleshooting Tip | How to clear alert code |
120 |
Moderate | Thermostat, furnace, air handler, outdoor unit, equipment interface or IHarmony |
Unresponsive DEVICE2. | There is a delay in the system component responding to the system. Typi cally this alert code does not cause any operational issues and will clear on its own. √ This alert code is usually caused by a delay in the outdoor unit responding to the thermostat. √ Check all wiring connections. | Automatically clears after an unre sponsive system component (de vice) responds to any inquiry. |
124 |
Critical |
Thermostat, furnace, air handler, outdoor unit, equipment interface or IHarmony |
Active Subnet Controller Missing | The thermostat has lost communication with a system component for more than three minutes. System component has lost communication with the thermostat. √ Check the wiring connections. √ Ohm wires. √ Cycle power. √ Check voltage at component. This alert code stops all associated system operations and waits for a heart beat message from the system component that is not communicating. |
Automatically clears after commu nication is re-established with ap plicable system component (de vice). |
125 |
Critical | Thermostat, furnace, air handler, outdoor unit, equipment interface or IHarmony |
Control Hardware Problem | There is a hardware problem on a system component control. There is a control hardware problem. √ Replace the control if the problem prevents operation and is persistent. √ Damper control module will remain in non-zone mode (all dampers open) for five minutes after priority condition no longer exist. √ Remove jumper if present on indoor unit between R and W2 if equipment interface module is in use. |
Automatically clears 300 seconds after the issue no longer exists. |
126 | Critical | Furnace, air handler or outdoor unit | Control Internal Communication Prob | There is an internal hardware problem on the system component control. √ Typically the system component control will reset itself. √ Replace the system component (device) control if the problem prevents op eration and is persistent. | Automatically clears 300 seconds after the issue no longer exists. |
130 | Moderate | Equipment interface module | Configuration Jumper Missing | √ Configuration jumper missing on equipment interface module. √ Install the missing jumper. NOTE: This is applicable in non-communicating applications only). | Automatically clears after the missing or incorrectly installed jumper is installed or corrected. |
131 |
Critical | Thermostat, furnace, air handler, outdoor unit, equipment interface or IHarmony | Corrupted Control Param eters | System component control parameters are corrupted. √ Replace the system component control if heating or cooling is not available. √ Go to menu > advance settings > view dealer control center > equip ment and press reset all equipment. This will allow the system to auto-de tect any iComfort® components attached. | Will automatically clear when sys tem component (device) passes memory self-test or system com ponent control is replaced. |
132 | Critical | Air handler, equipment interface module or IHarmony | Failed Flash CRC Check | System component control software is corrupted. √ Recycle power. √ If failure re-occurs, replace the system component control. | Manual system power reset is re quired to recover from this alert code. |
Alert Codes and Troubleshooting | Initial notification of critical alerts will pop up on the home screen and will be listed under notification menu. Minor and moderate alerts are found only under the notification menu. * Current Lennox modulating outdoor units are XC/XP20 and XC/XP25. | ||||
Alert Code | Priority Condition | Applicable System Component(s) | Actual Displayed Alert Text | Component or System Operational State and Troubleshooting Tip | How to clear alert code |
180 |
Critical |
Furnace, air handler or equipment interface module |
Outdoor Temperature Sensor Problem | The thermostat has found a problem with a system component’s outdoor temperature sensor. In normal operation after system component control recognizes sensors, the alarm will be sent if valid temperature reading is lost. √ Compare outdoor sensor resistance to temperature / resistance charts in unit installation instructions. √ Replace sensors pack if necessary. √ At the beginning of (any) configuration, furnace, air-handler control or equipment interface module will detect the presence of the sensor(s). √ If detected (reading in range), appropriate feature will be set as ‘installed’ and shown in the ‘About’ screen. |
Automatically clears upon configu ration, or sensing normal values. |
200 | Critical | Furnace | Rollout Limit Switch Open | The furnace roll out limit switch is open. Correct the cause of roll out trip. √ Reset roll out switch. √ Test the furnace operation. | Automatically clears after the fur nace roll out switch is closed. |
201 |
Critical | Furnace or air handler | Indoor Blower Motor Problem | Lost communication with indoor blower motor. √ Possible causes include power outage, brown-out, motor not powered, loose wiring, condensation on system component control without cover on breaker. √ Problem may be on system component control or motor side. | Automatically clears after commu nication is restored. |
202 |
Critical |
Furnace or air handler |
ID Blower Motor & Unit Size Mismatch | The unit size code for the indoor unit and the size of blower motor do not match. Incorrect appliance unit size code selected. √ Remove the thermostat from the system while applying power and repro gramming. √ Check for proper configuring under unit size codes for furnace/air handler in configuration guide or in installation instructions. | Automatically clears after the cor rect match is detected following a reset. |
203 |
Critical |
Furnace or air handler |
Invalid Unit Code | The unit size code for the indoor unit has not been selected. √ Remove the thermostat from the system while applying power and repro gramming. √ Check for correct configuration. Unit size codes for furnace and air handler are listed in the system component configuration guide or installation in struction. | Automatically clears after the cor rect match is detected following a reset. |
204 | Critical | Furnace | Gas Valve Problem | There is an issue with the furnace gas valve. √ Check gas valve operation and wiring. | Automatically clears after the is sue is corrected. |
205 | Critical | Furnace | Gas Valve relay Contact Closed | The furnace gas valve relay contact is closed. √ Check wiring on control and gas valve. | Automatically clears after the is sue is corrected. |
206 | Critical | Furnace | Gas Valve 2nd Stage Relay Failure | The furnace gas valve second-stage relay is faulty. √ Furnace will operate on first-stage for the remainder of the heating demand √ If unable to operate second-stage, replace furnace control. | Automatically clears after the is sue is corrected. |
207 | Critical | Furnace | HIS Sensed Open | The furnace hot surface igniter is open. √ Measure the resistance of hot surface igniter. √ Replace the igniter if it is not within the specified range found in furnace in stallation instruction. | Automatically clears after the is sue is corrected. |
Alert Codes and Troubleshooting | Initial notification of critical alerts will pop up on the home screen and will be listed under notification menu. Minor and moderate alerts are found only under the notification menu. * Current Lennox modulating outdoor units are XC/XP20 and XC/XP25. | ||||
Alert Code | Priority Condition | Applicable System Component(s) | Actual Displayed Alert Text | Component or System Operational State and Troubleshooting Tip | How to clear alert code |
223 |
Critical |
Furnace |
Low Pressure Switch Open | The furnace low pressure switch is open. √ Check pressure (inches w. c.) of the low pressure switch closing during a heat call. √ Measure operating pressure (inches w. c.). √ Inspect vent and combustion air inducer for correct operation and restric tion. √ Check for blocked CEHB or condensate drain and cracked hoses. |
Automatically clears after the is sue is corrected. |
224 |
Critical |
Furnace |
Low Pressure Switch Stuck Closed | The furnace low pressure switch is stuck closed. √ Check operation of low pressure switch to see if it is stuck closed for longer than 150 seconds during a heat call. √ Measure operating pressure (inches w. c.). √ Inspect vent and combustion air inducer for correct operation and restric tion. |
Automatically clears after the is sue is corrected. |
225 |
Critical |
Furnace |
High Press. Switch Failed to Close | The furnace high pressure switch will not close. √ Check pressure (inches w. c.) of high pressure switch closing during a heat call. √ Measure operating pressure (inches w. c.). √ Inspect vent and combustion air inducer for correct operation and restric tion. √ Check for blocked CEHB or condensate drain and cracked hoses. |
Automatically clears after the is sue is corrected. |
226 |
Critical |
Furnace |
High Pressure Switch Stuck Closed | The furnace high pressure switch will not open. √ Check operation of high pressure switch closing during a heat call. √ Measure operating pressure (inches w. c.). √ Inspect vent and combustion air inducer for correct operation and restric tion. |
Automatically clears after the is sue is corrected. |
227 |
Moderate |
Furnace |
Lo Pressure Switch Open in Run Mode | The furnace low pressure switch is open while in run mode. √ Check pressure (inches w. c.) of low pressure switch closing during a heat call. √ Measure operating pressure (inches w.c.). √ Inspect vent and combustion air inducer for correct operation and restric tion. √ Check for blocked CEHB or condensate drain and cracked hoses. |
Automatically clears after the is sue is corrected. |
228 |
Moderate |
Furnace | Inducer / Press. Switch Calib. Failure | The furnace control is not able to calibrate the pressure switch. Unable to perform pressure switch calibration. √ Check vent system and pressure switch wiring connections. √ Check the drain trap for blockage. √ Check for blocked CEHB or condensate drain and cracked hoses. | Automatically clears after a suc cessful calibration. |
229 | Minor | Furnace | Ignition on High Fire | Furnace control switched to high fire ignition because low fire pressure switch did not close in allowed time. | No action is required. |
Alert Codes and Troubleshooting | Initial notification of critical alerts will pop up on the home screen and will be listed under notification menu. Minor and moderate alerts are found only under the notification menu. * Current Lennox modulating outdoor units are XC/XP20 and XC/XP25. | ||||
Alert Code | Priority Condition | Applicable System Component(s) | Actual Displayed Alert Text | Component or System Operational State and Troubleshooting Tip | How to clear alert code |
240 |
Moderate |
Furnace |
Low Flame Current – Run Mode | The furnace flame current is low. √ Check micro-amperes of the flame sensor using thermostat diagnostics. √ Clean or replace the flame sensor. √ Measure voltage of neutral to ground to ensure good unit ground. √ Clean face of burner assembly. √ Check for AC voltage from flame sensor electrode to ground. |
Automatically clears after a proper micro-amp reading has been sensed. |
241 |
Critical |
Furnace |
Flame Out of Sequence – Still Present | The furnace flame is going out while the furnace is heating. √ Shut off gas. √ Check for a gas valve leak. √ Replace the gas valve if needed. √ Check for low flame signal. |
Automatically clears when a heat call ends successfully. |
250 |
Moderate |
Furnace and iHarmony |
Primary Limit Switch Open | The furnace primary limit switch is open. √ If limit switch is not closed withing three minutes, the unit will go into a 60 minute soft lockout (WatchGuard mode). √ Check for high gas pressure. √ Low supply air due to being plugged or restriction in system (example: dirty air filter or blockage in duct work). √ Limit trips will place the iHarmony® zoning system into non-zone mode. √ Check for proper firing rate on furnace. √ Check for non-functioning zone dampers. NOTE: Refer to S&A Note ACC-14-01 – iHarmony® and SLP98 – Insufficient Zone Heating and Alarm Code 250 Issues for corrective actions. |
Automatically clears when a heat call ends successfully. NOTE: If this issue occurred on an iHarmony® zoning system, the field will need to manually activate the zoning. |
252 | Moderate | Furnace | Discharge Air Temperature High | The furnace discharge air-temperature is high. √ Check temperature rise, air flow and input rate. √ Check for dirty air filter(s). | Automatically clears when a heat call ends successfully. |
270 |
Critical |
Furnace |
WatchGuard – Flame Failure on Ignite | The furnace is in WatchGuard mode. The furnace igniter cannot turn on the flame. This is a five strike condition during a single demand. √ Check for proper gas flow. √ Ensure that igniter is lighting burner. √ Check flame sensor current. √ Check for dirty filters. √ Check for blocked CEHB or condensate drain and cracked hoses. |
Automatically clears on successful ignition. |
271 |
Critical |
Furnace |
WatchGuard – Low Press Switch Open | The furnace is in WatchGuard mode. The furnace low pressure switch is open. This is a five strike condition during a single demand. √ Check pressure (inches w. c.) of low pressure switch closing during a heat call. √ Measure operating pressure (inches w. c.). √ Inspect vent and combustion air inducer for correct operation and restric tion. |
Automatically clears on successful ignition. |
Alert Codes and Troubleshooting | Initial notification of critical alerts will pop up on the home screen and will be listed under notification menu. Minor and moderate alerts are found only under the notification menu. * Current Lennox modulating outdoor units are XC/XP20 and XC/XP25. | ||||
Alert Code | Priority Condition | Applicable System Component(s) | Actual Displayed Alert Text | Component or System Operational State and Troubleshooting Tip | How to clear alert code |
272 |
Critical |
Furnace |
WatchGuard – Lo Press Switch Open Run Mode | The furnace low pressure switch is open during run mode. The system will go into WatchGuard mode. √ Check operation of low pressure switch to see if it is stuck open during a heat call. √ Measure operating pressure (inches w. c.). √ Inspect vent and combustion air inducer for correct operation and restric tion. √ Check for blocked CEHB or condensate drain and cracked hoses. |
Automatically clears when a heat call ends successfully. |
273 |
Critical |
Furnace |
WatchGuard – Flame fail in Run Mode | The furnace flame is going off during a heating cycle. The system will go into WatchGuard mode. √ Check micro-amperes of flame sensor using thermostat diagnostics. √ Clean or replace sensor. √ Measure voltage of neutral to ground to ensure good unit ground. √ Clean face of burner assembly. |
Automatically clears when a heat call ends successfully. |
274 | Critical | Furnace | WatchGuard – Primary Limit Switch Open | The furnace limit switch has been open for more than three minutes. The system will go into WatchGuard mode. √ Check firing rate and air flow. √ Check for air blockage. | Automatically clears when a heat call ends successfully. |
275 | Critical | Furnace | WatchGuard – Flame Out of Seq. No Flame | The furnace flame is out of sequence. The system will go into WatchGuard mode. √ Shut off gas. √ Check for gas valve leak. | Automatically clears on successful ignition. |
276 | Critical | Furnace | WatchGuard – Calibration Failure | The furnace is not able to calibrate or the high pressure switch opened or failed to close in run mode. The system will go into WatchGuard mode. √ Check vent system √ Check pressure switch wiring connections. | Automatically clears when the fur nace calibrates itself successfully. |
290 |
Critical |
Furnace |
Ignition Circuit Problem | There is a problem with the furnace ignition circuit. The system will go into WatchGuard mode. √ Measure resistance of hot surface igniter. √ Replace the hot surface igniter; it is not within specifications. √ Measure voltage to igniter. | Automatically clears on successful ignition |
291 | Critical | Furnace | Heat Airflow Restricted Below Min | The heating airflow is below the minimum required level. The system will go into WatchGuard mode. √ Check for dirty air filter(s) and other air flow restrictions. √ Check blower performance. | Automatically clears when a heat call ends successfully. |
292 |
Critical |
Furnace or air handler |
Indoor Blower Motor Start Problem | The indoor unit blower motor will not start. The system will go into WatchGuard mode. √ Indoor blower motor unable to start. √ This could be due to seized bearing, stuck wheel, and obstructions. √ Replace motor, motor module or wheel if assembly does not operate or meet performance standards. |
Automatically clears after the in door blower motor starts success fully. |
Alert Codes and Troubleshooting | Initial notification of critical alerts will pop up on the home screen and will be listed under notification menu. Minor and moderate alerts are found only under the notification menu. * Current Lennox modulating outdoor units are XC/XP20 and XC/XP25. | ||||
Alert Code | Priority Condition | Applicable System Component(s) | Actual Displayed Alert Text | Component or System Operational State and Troubleshooting Tip | How to clear alert code |
294 |
Critical |
Furnace | Inducer Motor Overcurrent | There is over current in the furnace inducer motor. The system will go into WatchGuard mode. √ Check combustion blower bearings, wiring and amps. √ Replace furnace inducer motor if it does not operate or does not meet per formance standards. | Automatically clears after inducer motor current is sensed to be in- range after the ignition following either WatchGuard mode or unit reset. |
295 |
Minor |
Furnace | Indoor Blower Over Temperature | The indoor blower motor is overheating. Indoor blower motor over tempera ture (motor tripped on internal protector). √ Check motor bearings and amps. √ Replace indoor blower motor if necessary. √ Check for high duct static. | Automatically clears after blower demand is satisfied. |
310 |
Moderate | Furnace and air handler only NOTE: Issues with a DATS connected to a DCM or EIM will not generate an alert code. |
Discharge Air Temp Sensor Problem | There is a discharge air temperature sensor issue. √ Compare discharge temperature sensor resistance to temperature / resis tance charts in system component installation instruction. √ Replace discharge air sensor if necessary. NOTE: Confirm there is no short or open circuits in the iComfort thermostat connections to any of the other components in the communication system. |
Automatically clears 30 seconds after condition is detected as re covered or after system restart. |
311 |
Minor |
Furnace |
Heat Rate Reduced to Match Airflow | The heat firing rate has been reduced to match available airflow (cutback mode). This is a warning only alert code. √ Furnace blower in cutback mode due to restricted airflow. √ Reduce firing rate every 60 seconds to match available CFM. √ Check air filter and duct system. √ To clear, replace air filter if needed or repair or add additional ducting. √ Two-stage controls will reduce firing rate to first stage. |
Automatically clears when a heat ing call finishes successfully. |
312 |
Minor |
Furnace or air handler |
Reduced/Airflow-Indoor Blower Cutback | The indoor blower cannot provide the requested CFM due to high static pressure. This is a warning only alert code. √ Possible restricted airflow – Indoor blower is running at a reduced CFM (Cutback Mode). √ The variable speed motor has pre-set speed and torque limiters to protect the motor from damage caused by operating outside of design parameters (0 to 0.8” e.g. total external static pressure). √ Check air filter and duct system. √ To clear, replace air filter if needed or repair or add additional ducting. |
Automatically clears after the cur rent service demand is satisfied. |
313 |
Minor | Furnace, air handler and outdoor unit | Indoor/Outdoor Unit Capacity Mismatch | The indoor and outdoor unit capacities do not match. This is a warning only alert code. √ Check for proper system component configuring in installation instructions. √ The system will operate, but might not meet efficiency and capacity param eters. | Automatically clears after commis sioning is complete. |
344 | Critical | Furnace | Relay Y1 Stuck | Link Relay Problem. Relay Y1 Failure √ Possible Y1 relay failure. √ All system operations will stop. | Automatically clears 300 seconds after Y1 input sensed OFF. |
Alert Codes and Troubleshooting | Initial notification of critical alerts will pop up on the home screen and will be listed under notification menu. Minor and moderate alerts are found only under the notification menu. * Current Lennox modulating outdoor units are XC/XP20 and XC/XP25. | ||||
Alert Code | Priority Condition | Applicable System Component(s) | Actual Displayed Alert Text | Component or System Operational State and Troubleshooting Tip | How to clear alert code |
345 |
Critical |
Air handler, equipment interface module or heat pump |
Relay O Failure | The O relay on the system component has failed. Either the pilot relay con tacts did not close or the relay coil did not energize. √ Possible O relay / stage 1 failure. √ Pilot relay contacts did not close or the relay coil did not energize. √ Replace system component (device) control. √ If error is applicable to the XC/XP 25, the outdoor control will need to be re placed. |
Automatically clears after the fault recovered following reset. |
346 |
Critical |
Air handler |
HP Jumper Not Removed | The heat pump configuration link is not cut on the air handler control. √ Configuration link not cut on air handler control. √ Cut O to R. √ This is only applicable with non-communicating heat pump with communi cating indoor unit. | Automatically clears when the system detects that the issue no longer exists. |
347 |
Critical | Furnace, air handler or equipment interface module |
Relay Y1 Failure | The Y1 relay on the applicable system component has failed. Either the pilot relay contacts did not close or the relay coil did not energize. √ System operation will stop. √ Possible Y1 relay / stage 1 failure. √ Pilot relay contacts did not close or the relay coil did not energize; √ There is no input back to the applicable system component control. |
Automatically clears after reset and Y1 input sensed. |
348 |
Critical | Furnace or air handler |
Relay Y2 Failure | The Y2 relay on the applicable system component has failed. Either the pilot relay contacts did not close or the relay coil did not energize. √ Possible Y2 relay / stage 2 failure. √ Furnace pilot relay contacts did not close or the relay coil did not energize √ No input back to furnace or air handler control. | Automatically clears when the system detects that the issue no longer exists. |
349 | Critical | Furnace | IFC Error Check Jumper O to R | The O to R link on the furnace needs to be restored. √ Configuration link R to O needs to be restored. √ Repair cut link by hard-wiring the R to O terminals on the terminal strip. √ Only applicable in non-communicating mode. | Automatically clears when the system detects that the issue no longer exists. |
350 |
Critical |
Air handler | Electric Heat Not Configured | The air handler’s electric heat is not configured or incorrectly configured. √ Heat call with no configured or incorrectly configured electric heat. √ Check for proper configuring under Configuring Electric Heat Stages in the air handler installation instructions. Smart Hub MUST be removed from the system before configuring electric heat. | Automatically clears after electri cal heat detection is successful. |
351 |
Critical |
Air handler |
Electric Heat Stage 1 Problem | There is an issue with the air handler’s first stage electric heat. √ Either the pilot relay contacts did not close or the relay coil in the electric heat section did not energize. √ Possible heat section / stage 1 failure. √ Air handler will operate on HP first stage for reminder of the heat call. |
Automatically clears after fault re covered. |
352 |
Critical |
Air handler | Electric Heat Stage 2 Problem | There is a issue with the air handler’s second stage electric heat. √ Either the pilot relay contacts did not close or the relay coil in the electric heat section did not energize. √ The air-handler will operate on first stage electric heat until the issue is re solved. | Automatically clears after fault re covered. |
Alert Codes and Troubleshooting | Initial notification of critical alerts will pop up on the home screen and will be listed under notification menu. Minor and moderate alerts are found only under the notification menu. * Current Lennox modulating outdoor units are XC/XP20 and XC/XP25. | ||||
Alert Code | Priority Condition | Applicable System Component(s) | Actual Displayed Alert Text | Component or System Operational State and Troubleshooting Tip | How to clear alert code |
353 |
Critical |
Air handler | Electric Heat Stage 3 Problem | There is a issue with the air handler’s third stage electric heat. √ Either the pilot relay contacts did not close or the relay coil in the electric heat section did not energize. √ The air-handler will operate on first stage electric heat until the issue is re solved. | Automatically clears after fault re covered. |
354 |
Critical |
Air handler | Electric Heat Stage 4 Problem | There is a issue with the air handler’s fourth stage electric heat. √ Either the pilot relay contacts did not close or the relay coil in the electric heat section did not energize. √ The air-handler will operate on first stage electric heat until the issue is re solved. | Automatically clears after fault re covered. |
355 |
Critical |
Air handler | Electric Heat Stage 5 Problem | There is an issue with the air handler’s fifth stage electric heat. √ Either the pilot relay contacts did not close or the relay coil in the electric heat section did not energize. √ The air-handler will operate on first stage electric heat until the issue is re solved. | Automatically clears after fault re covered. |
370 |
Critical |
Furnace |
Interlock Switch Open | The furnace control has not received 24VAC power for two minutes or more on the DS terminal √ The system will not operate. √ Dealer has cut the W914 jumper (Dehum, Harmony III) √ The thermostat monitors the DS terminal in the furnace for power and if the link has been cut then power will be lost to DS. | This alert code will clear when 24VAC is continuously sensed on DS terminal for a minimum of 10 seconds or on a power reset. |
380 |
Moderate / Critical |
Equipment interface module |
Interlock Relay Failure | Interlock relay failure (furnace or air handler modes only). √ Interlock relay is energized, but input is not sensed after three seconds. √ There will be no heating or cooling due to this alert code – moderate condi tion. √ De-energize interlock relay and energize after five minutes if demand is still present – critical condition. |
Automatically clears after fault re covered. |
381 | Moderate / Critical | Equipment interface module | Interlock Relay Stuck | Interlock relay stuck (furnace or air handler modes only). √ Interlock relay continuously sensed (with relay off). √ There is no heating and cooling operation – moderation condition. √ After 10 minutes if event still exist it will be escalated – critical condition. | Automatically clears 30 seconds after fault clears. |
382 | Moderate | Equipment interface module | Relay W1 Failure | Relay W1 failure (furnace or air handler modes only). √ W1 relay is energized but input is not sensed after three seconds. | Automatically clears when W1 re lay input is sensed. |
400 |
Critical |
Outdoor unit |
LSOM Comp. Internal Overload Tripped | The compressor internal overload has tripped. √ Thermostat demand Y1 is present; however compressor is not running. √ Check power to unit. √ This alert code is automatically cleared after current is sensed in both RUN and START sensors for at least two seconds or after service is removed, or after power reset. |
Automatically clears when the system detects that the issue no longer exists. |
Alert Codes and Troubleshooting | Initial notification of critical alerts will pop up on the home screen and will be listed under notification menu. Minor and moderate alerts are found only under the notification menu. * Current Lennox modulating outdoor units are XC/XP20 and XC/XP25. | ||||
Alert Code | Priority Condition | Applicable System Component(s) | Actual Displayed Alert Text | Component or System Operational State and Troubleshooting Tip | How to clear alert code |
401 |
Moderate |
Outdoor unit |
Compressor Long Run Cycle | Either the compressor ran for more than 18 hours continuously while at tempting to cool the home during a single demand or the system refrigerant pressure is low. √ Alert code will not lockout system. √ If the two-stage outdoor unit has: √ An outdoor control with blinking LED lights then the unit will run in low speed; √ An outdoor control with a 7-segment display, the outdoor control will display alert code 401, but continue to run in high speed. √ If the outdoor unit is a heat pump, and the outdoor temperature is less than 65°F, alert code 401 is ignored. √ Also monitors low pressure switch trips. |
Automatically clears after 30 con secutive normal run cycles or power reset. |
402 | Critical | Outdoor unit | Outdoor Unit System Pressure Trip | √ Either the discharge or suction pressure level is out-of-limits, or the com pressor has overloaded. √ Check discharge or suction pressure. | Automatically clears after four consecutive normal compressor run cycles. |
403 | Moderate | Outdoor unit | Compressor Short-Cycling | The compressor ran for less than three minutes to satisfy a thermostat de mand. | Automatically clears after four consecutive normal compressor run cycles. |
404 | Critical | Outdoor unit | Compressor Rotor Locked | The compressor rotor is locked up. √ Compressor rotor locked up due to run capacitor short. √ Bearings are seized. √ Excessive liquid refrigerant, etc. (NOTE: May need to install hard start kit). | Automatically clears after four consecutive normal run cycles or after power reset. |
405 | Critical | Outdoor Unit | Compressor Open Circuit | The compressor circuit is open. √ Compressor circuit open (due to power disconnection – open fuse, etc.) | Automatically clears after one nor mal compressor run cycle. |
406 | Critical | Outdoor unit | Compressor Open Start Circuit | The required amount of current is not passing through the START current transformer. | Automatically clears after current is sensed in START sensor, or af ter power reset. |
407 | Critical | Outdoor unit | Compressor Open Run Circuit | The required amount of current is not passing through RUN current trans former. | Automatically clears after current is sensed in RUN sensor, one nor mal compressor run cycle, or after power reset |
408 | Critical | Outdoor unit | Compressor Contactor Welded | The compressor is running continuously. | Automatically clears one normal compressor run cycle or after power reset. |
409 |
Moderate | Furnace, air handler or outdoor unit |
Compressor Voltage Low | The secondary voltage for the applicable system component has fallen be low 18VAC. √ Secondary voltage is below 18VAC. √ If this continues for 10 minutes, the thermostat will turn off the applicable system component. | Automatically clears after voltage is detected as higher than 20VAC for two seconds or after power re set. |
410 | Moderate | Outdoor unit | Open Low Pressure Switch | Unit low pressure is below the required limit. √ Check operating pressures. √ Low pressure switch opens at a specific pressure (system shuts down) and closes at a specific pressure (system restarts). | Automatically clears when the system detects that the issue no longer exists. |
Alert Codes and Troubleshooting | Initial notification of critical alerts will pop up on the home screen and will be listed under notification menu. Minor and moderate alerts are found only under the notification menu. * Current Lennox modulating outdoor units are XC/XP20 and XC/XP25. | ||||
Alert Code | Priority Condition | Applicable System Component(s) | Actual Displayed Alert Text | Component or System Operational State and Troubleshooting Tip | How to clear alert code |
411 |
Critical |
Outdoor unit |
Low Pressure Switch Strikes Lockout | The low pressure switch has opened five times during one cooling or heat ing demand. √ Thermostat will shut down the outdoor unit. √ Open low pressure switch error count reached five strikes. √ Check system charge using both approach and sub-cooling methods. √ Reset by putting outdoor unit control in test mode or resetting low voltage power. |
Automatically clears when the system detects that the issue no longer exists. |
412 |
Moderate |
Outdoor unit |
Open High Pressure Switch | The unit high pressure is above the upper limit. √ System will shut down. √ Confirm that the system is properly charged with refrigerant. √ Check condenser fan motor, expansion valve (if installed), indoor unit blow er motor, stuck reversing valve or clogged refrigerant filter. √ Confirm that the outdoor unit is clean. |
Automatically clears after the high pressure switch closes or a power reset |
413 |
Critical |
Outdoor unit |
Hi Pressure Switch Strikes Lockout | The high pressure switch has opened five times during one cooling demand. √ Thermostat will shut down the outdoor unit. √ Open high pressure switch error count reached five strikes. √ Check system charge using superheat and sub-cooling temperatures. √ Check outdoor fan operation. √ Check for dirt or debris blocking air flow to outdoor unit. √ Reset by putting outdoor unit control in test mode or resetting low voltage power. |
Automatically clears when the system detects that the issue no longer exists. |
414 |
Moderate |
Outdoor unit |
High Discharge Line Temperature | The discharge line temperature is higher than the recommended upper limit of 279ºF. √ Discharge line temperature is greater than 279ºF. √ Make sure coil is clean and airflow unobstructed in and out of condenser. √ Check system operating pressures and compare to unit charging charts in installation manual. |
Automatically clears after dis charge temperature is less than 225ºF. |
415 |
Critical |
Outdoor unit |
Hi Disch. Line Temp Strikes Lockout | The discharge line temperature has been consistently higher than the rec ommended upper limit of 279ºF. √ Discharge line high temperature error count reached five strikes during a single demand. √ Make sure coil is clean and airflow unobstructed in and out of condenser. √ Check system charge using superheat and sub cooling temperatures. √ Reset by putting outdoor control in test mode or resetting low voltage pow er. |
Correct issue and cycle power to the system. |
Alert Codes and Troubleshooting | Initial notification of critical alerts will pop up on the home screen and will be listed under notification menu. Minor and moderate alerts are found only under the notification menu. * Current Lennox modulating outdoor units are XC/XP20 and XC/XP25. | ||||
Alert Code | Priority Condition | Applicable System Component(s) | Actual Displayed Alert Text | Component or System Operational State and Troubleshooting Tip | How to clear alert code |
416 |
Moderate / Critical |
Outdoor unit |
Outdoor Coil Sensor Faulty | The outdoor coil sensor is either open, short-circuited or the temperature is out of sensor range. √ Outdoor unit control will not perform demand or time / temperature defrost operation. (System will still heat or cool.) √ This fault is detected by allowing the unit to run for 90 seconds before checking sensor resistance. If the sensor resistance is not within range af ter 90 seconds, the control will display a moderate code. √ Advances from moderate to critical after ten (10) minutes. √ Plug-in sensor harness correctly. (Refer to Service and Application Note C-18-08) √ Check resistance of sensor to determine if it is open, shorted, out of temper ature calibration or out of ambient temperature range. Replace if out-of- specifications. |
Automatically clears when outdoor unit control detects proper sensor readings. If sensor is faulty and the system is reporting the condition as criti cal, replaced sensor. Reset power to clear alert code. |
417 |
Moderate / Critical |
Outdoor unit |
Discharge Sensor Faulty | SYSTEM DETECTION AND OPERATION: The outdoor unit discharge line temperature sensor is either open, short- circuited or the temperature is out of sensor range. √ This fault is detected by allowing the unit to run for 90 seconds before checking discharge line sensor resistance. √ If the discharge sensor resistance is not within range after 90 second peri od, the control will display the priority condition as moderate. √ If the moderate condition continues for 10 minutes, the system changes the priority condition to critical. POSSIBLE CAUSES: √ The applicable system component detects either an open, shorted or tem perature out of range condition. √ Discharge sensor leads located in wrong pin positions in harness plug-in connector. Refer to the applicable unit installation and service procedure and locate the terminal descriptions table to verify cable harness assembly wiring pin positions are correct. POSSIBLE SOLUTIONS: √ Check the resistance of the discharge sensor and compare to temperature resistance chart located in the applicable unit installation and service pro cedure. If sensor resistance is out of range then replace the discharge line temperature sensor. √ If discharge sensor wring leads are located in the wrong connector pin-out then order a replacement cable assembly. |
Moderate – Automatically clears after fault signal condition is no longer present. Critical – Power down the system component and either replace faulty sensor or cable assembly (whichever is applicable). Power up system component after re placing the applicable part which will clear the alert code / priority condition. |
418 |
Moderate |
Equipment interface module and outdoor unit |
W Output Hardware Fault | There is a faulty W output circuit. √ W terminal is energized while in cooling mode. √ Possible cause may be a stuck closed relay on the control, or something external to the control that is energizing W terminal when it should not be energized. √ Disconnect any wiring from the W terminal. √ If 24VAC is still present on the terminal, then it is a stuck relay. √ If 24VAC disappears, then there is a need to check any of the wires hooked up to the W terminal. |
Automatically clears after fault sig nal is removed. |
Alert Codes and Troubleshooting | Initial notification of critical alerts will pop up on the home screen and will be listed under notification menu. Minor and moderate alerts are found only under the notification menu. * Current Lennox modulating outdoor units are XC/XP20 and XC/XP25. | ||||
Alert Code | Priority Condition | Applicable System Component(s) | Actual Displayed Alert Text | Component or System Operational State and Troubleshooting Tip | How to clear alert code |
419 |
Critical |
Equipment interface module and outdoor unit |
W Output hardware Fault Lockout | The W output has reported more than five errors. √ The system will shut down the outdoor unit. √ The W output (code E418) on the outdoor unit has reported more than five strikes. √ Disconnect thermostat wire from W and verify there is no 24VAC on the W. √ If 24VAC is present, replace the outdoor control. |
Automatically clears after power recycled. |
420 |
Critical | Air handler or equipment interface module |
Defrost Out of Control | The heat pump defrost cycle has taken more than 20 minutes to complete. √ Defrost cycle lasts longer than 20 minutes. √ Check heat pump operation. √ This is applicable only in communicating indoor unit with non-communicat ing heat pump. |
Automatically clears when W1 sig nal is removed. |
421 | Critical | Equipment interface module and outdoor unit | W External Miswire Fault | The W output terminal on the outdoor unit is not wired correctly. √ Voltage sensed on W output terminal when Y1 out is deactivated. | Automatically clears once voltage is not sensed on output or power is cycled. |
422 |
Moderate |
Outdoor unit |
Compressor Top Cap Switch Open | Compressor top cap switch exceeding thermal limit. √ Check condenser fan motor, TXV and indoor unit blower motor. √ Check for stuck reversing valve or clogged refrigerant filter. √ XC/XP25: Check to ensure that one of the wires from the top cap switch has not been disconnected from one of the TP terminals on the outdoor control. Reconnect wire if disconnected. √ Check superheat and sub-cooling. |
Automatically clears when error is corrected. |
423 |
Moderate / Critical |
Inverter based outdoor unit* |
OD Inverter CT Circuit Problem | The inverter has detected a circuit issue. √ When this condition is detected the outdoor control will stop outdoor unit op erations and start the anti-short cycle timer – moderate condition. √ Outdoor control will lockout unit after 10 strikes within an hour – critical condition. √ Inverter LEDs will blink code 40 √ Refer to the unit service documentation for troubleshooting procedures. | A moderate alarm will clear auto matically when the inverter detects the condition no longer exist and will send a clear alarm message. To clear critical alarm disconnect power to outdoor unit and restart. |
424 |
Moderate |
Outdoor unit |
OD Liquid Line Sensor Faulty | The liquid line temperature sensor has malfunctioned. √ In normal operation after outdoor control recognizes sensors, the alert code will be sent if a valid temperature reading is lost. √ Compare liquid line sensor resistance to temperature / resistance charts in unit installation instructions. √ Replace sensor pack if necessary. √ At the beginning of (any) configuration, furnace or air handler control will detect the presence of the sensor(s). √ If detected (reading in range), appropriate feature will be set as ‘installed’ and shown in the iComfort Wi-Fi® thermostat ‘About’ screen. |
Automatically clears upon configu ration, or sensing normal values. |
Alert Codes and Troubleshooting | Initial notification of critical alerts will pop up on the home screen and will be listed under notification menu. Minor and moderate alerts are found only under the notification menu. * Current Lennox modulating outdoor units are XC/XP20 and XC/XP25. | ||||
Alert Code | Priority Condition | Applicable System Component(s) | Actual Displayed Alert Text | Component or System Operational State and Troubleshooting Tip | How to clear alert code |
425 |
Minor |
Inverter based outdoor unit* |
Compressor Speed Limited by OD Temperature | Outdoor control has increased minimum compressor speed to allow for proper oil return due to low ambient temperature. √ Outdoor ambient temperature is below system limit. √ Control will attempt to run at lowest allowed compressor speed to allow for proper oil return. NOTE: Minimum speed adjustments start at 45°F and go up to 100% mini mum at 17°F |
Automatically clears when outdoor ambient temperature rises above limit for more than five minutes. |
426 | Critical | Inverter based outdoor unit* | Excessive Inverter Alarms | After 10 faults within 60 minutes rolling time period, the control will lockout. In verter will blink codes 12 to 14 and 53. These inverter codes do not count to wards this lockout condition. | To clear disconnect power to out door control and restart |
427 |
Moderate / Critical |
Inverter based outdoor unit* |
OD Inverter DC Peak Fault | The inverter has detected a DC peak fault condition. √ If condition (55A or higher) is detected, outdoor unit will stop (compressor and fan) – moderate condition. √ Anti-short cycle is initiated. √ If peak current (55A or higher) occurs 10 times within an hour, system will lockout – critical condition. √ Inverter LEDs will blink code 21. √ Refer to the unit service documentation for detailed troubleshooting proce dures. |
To clear, disconnect and recon nect power to outdoor control. |
428 |
Moderate / Critical |
Inverter based outdoor unit* |
OD Inverter High Main Input Current | The inverter has detected a high main input current condition. √ If condition is detected, outdoor unit will stop (compressor and fan) – mod erate condition. √ Anti-short cycle is initiated. √ If condition occurs 10 times within an hour, system will lockout – critical condition. √ Inverter LEDs will blink code 22. √ Refer to the unit service documentation for detailed troubleshooting proce dures. |
To clear, disconnect power to out door unit and restart. |
429 |
Moderate / Critical |
Inverter based outdoor unit* |
OD Inverter DC Link Low Voltage | The inverter has detected a DC link low voltage condition. √ On a call for compressor operation, if DC link power in inverter does not rise above 180 VDC for 2- and 3 -ton models, 250 VDC for 4- and 5-ton models within 30 seconds, the control will display a moderate code. √ If condition is detected, outdoor unit will stop (compressor and fan) – mod erate condition. √ An anti-short cycle timer is initiated. If condition occurs 10 times within a 60 minute rolling time period, system will lock out and display alert code 429 – critical condition. √ The outdoor control anti-short cycle timer will time out and the unit will recy cle the demand. √ Replace outdoor inverter. √ Inverter LEDs will blink code 23. √ Refer to the unit service documentation for detailed troubleshooting proce dures. |
Automatically clears when the system detects that the issue no longer exists. |
Alert Codes and Troubleshooting | Initial notification of critical alerts will pop up on the home screen and will be listed under notification menu. Minor and moderate alerts are found only under the notification menu. * Current Lennox modulating outdoor units are XC/XP20 and XC/XP25. | ||||
Alert Code | Priority Condition | Applicable System Component(s) | Actual Displayed Alert Text | Component or System Operational State and Troubleshooting Tip | How to clear alert code |
430 |
Moderate / Critical |
Inverter based outdoor unit* |
OD Inverter Compressor Startup Fail | Compressor start-up failure. √ If condition is detected, outdoor unit will stop (compressor and fan) – mod erate condition. √ Anti-short cycle is initiated. √ If condition occurs 10 times within an hour, system will lockout – critical condition. √ Inverter LEDs will blink code 26. √ Refer to the unit service documentation for detailed troubleshooting proce dures. |
To clear, disconnect power to out door unit and restart. |
431 |
Moderate / Critical |
Inverter based outdoor unit* |
OD Inverter PFC Fault | The inverter has detected a PFC circuit over-current condition. √ Error occurs when PFC detects an over current condition of 100A peak. √ If condition is detected, outdoor unit will stop (compressor and fan) – mod erate condition. √ Anti-short cycle timer is initiated. √ If condition occurs 10 times within an hour, system will lockout – critical condition. √ Inverter LEDs will blink code 27. √ Refer to the unit service documentation for detailed troubleshooting proce dures. |
To clear, disconnect power to out door unit and restart. |
432 |
Moderate / Critical |
Inverter based outdoor unit* |
OD Inverter DC Link High Voltage | The inverter has detected a DC link high voltage condition. √ Error occurs when the DC link capacitor voltage is greater than 480VDC. √ If condition is detected, outdoor unit will stop (compressor and fan) – mod erate condition. √ Anti-short cycle timer is initiated. √ If condition occurs 10 times within an hour, system will lockout – critical condition. √ Inverter LEDs will blink code 28. √ Refer to the unit service documentation for detailed troubleshooting proce dures. |
To clear, disconnect power to out door unit and restart. |
433 |
Moderate / Critical |
Inverter based outdoor unit* |
OD Inverter Compressor Overcurrent | Compressor phase current is too high. √ Error occurs when compressor peak phase current is greater than 28A. √ Inverter will issue code 14 first and slow down to try to reduce the current. √ If the current remains high, outdoor unit will stop (compressor and fan) – moderate condition. √ Antishort cycle timer is initiated. √ If condition occurs five times within an hour, system will lockout – critical condition. √ Inverter LEDs will blink code 29. √ Refer to the unit service documentation for detailed troubleshooting proce dures. |
To clear alert code disconnect power to outdoor unit and restart. |
Alert Codes and Troubleshooting | Initial notification of critical alerts will pop up on the home screen and will be listed under notification menu. Minor and moderate alerts are found only under the notification menu. * Current Lennox modulating outdoor units are XC/XP20 and XC/XP25. | ||||
Alert Code | Priority Condition | Applicable System Component(s) | Actual Displayed Alert Text | Component or System Operational State and Troubleshooting Tip | How to clear alert code |
434 |
Moderate / Critical |
Inverter based outdoor unit* |
OD Inverter Comm Error to Main Control | Outdoor control has lost communications with the inverter for greater than three minutes. √ Outdoor control has lost communications with the inverter for greater than three minutes. √ Outdoor control will stop all compressor demands – moderate condition. √ Recycle power to the inverter by de-energizing the contactor for two min utes. √ If this occurs three times in one thermostat call, the outdoor unit will lock out and display alert code 434 – critical condition. √ Check for loose or disconnected electrical connections. √ Interruption of main power to inverter. √ Inverter LEDs will blink code 53. √ Refer to the unit service documentation for detailed troubleshooting proce dures. |
Automatically clears when the system detects that the issue no longer exists. |
435 |
Moderate / Critical |
Inverter based outdoor unit* |
OD Inverter EEPROM Checksum fault | Inverter internal error. √ When this error occurs, the outdoor control will cycle power to the inverter by opening the contactor for two minutes – moderate condition. √ Outdoor control will cycle power to the inverter three times and then outdoor unit is locked out – critical condition. √ Inverter LEDs will blink code 60. √ Refer to the unit service documentation for detailed troubleshooting proce dures. |
To clear alert code disconnect power to outdoor unit and restart. |
436 |
Moderate / Critical |
Inverter based outdoor unit* |
OD Inverter High Heat-Sink Temperature | Inverter heat sink temperature exceeded limit. √ This occurs when the heat sink temperature exceeds the inverter limit. In verter will issue inverter alert code 13 first and slow down to try to cool the heat sink. √ If temperature remains high, outdoor unit will stop both compressor and fan – moderate condition. √ Antishort cycle is initiated. √ If condition occurs five times within an hour, system will lockout – critical condition. √ The screws that hold the inverter to the inverter board were loose causing poor contact between these two components. √ Tighten screws that hold the heat sink to the inverter control board. NOTE: Wait five minutes for all capacitors to discharge before checking screws. √ Inverter LEDs will blink code 62. √ Refer to the unit service documentation for detailed troubleshooting proce dures. |
Moderate condition will automati cally clear when the inverter sends an alarm clear message. Critical condition is cleared by dis connecting power to the outdoor unit and restart. |
Alert Codes and Troubleshooting | Initial notification of critical alerts will pop up on the home screen and will be listed under notification menu. Minor and moderate alerts are found only under the notification menu. * Current Lennox modulating outdoor units are XC/XP20 and XC/XP25. | ||||
Alert Code | Priority Condition | Applicable System Component(s) | Actual Displayed Alert Text | Component or System Operational State and Troubleshooting Tip | How to clear alert code |
437 |
Moderate / Critical |
Inverter based outdoor unit* |
OD Inverter Heat-Sink temp Sensor Fault | Heat sink temperature sensor fault has occurred (temperature less than 4ºF or greater than 264ºF after 10 minutes of operation). √ When the temperature sensor detects a temperature less than 4ºF or greater than 264ºF after 10 minutes of operation. √ Outdoor unit will stop both compressor and fan – moderate condition. √ Antishort cycle is initiated. √ If condition occurs five times within an hour, system will lockout – critical condition. √ Inverter LEDs will blink code 65. √ Refer to the unit service documentation for detailed troubleshooting proce dures. |
Moderate priority condition will au tomatically clear when the inverter sends an alarm clear message. Critical priority condition can be cleared by disconnecting and re connecting power to outdoor unit to restart. |
438 |
Moderate / Critical |
Inverter based outdoor unit* |
OD Inverter PFC Input Overcurrent | The inverter has detected a PFC circuit over-current condition. √ The inverter has detected a power factor correction (PFC) over current condition. This may be caused by a high load condition, high pressure, or outdoor fan failure. √ Outdoor control will display the code when the inverter has detected the er ror – moderate condition. √ After three minutes, the inverter will reset and the compressor will resume operation. √ If the error condition occurs 10 times within a 60 minute rolling time period, the outdoor unit control will lock out operation of the outdoor unit – critical condition. √ Possible issue is system running at high pressures. √ Check for high pressure trips or other alert codes in iComfort® S30 and out door control. √ Inverter LEDs will blink code 73. √ Refer to the unit service documentation for detailed troubleshooting proce dures. |
Moderate priority condition is auto matically cleared when the inverter sends a clear message. Critical priority condition will auto matically clear when inverter is power cycled. |
439 |
Moderate |
Inverter based outdoor unit* |
OD Inverter Compressor Slowdown – High Input Current | Compressor slowdown due to high input current. √ Input current is approaching a high limit. √ Compressor speed will automatically slow down. The outdoor control will continue sending the inverter speed demanded by the thermostat. √ The outdoor control will set indoor CFM and outdoor RPM to values accord ing to demand percentage rather than the actual Hz. √ Inverter LEDs will blink code 12. √ Refer to the unit service documentation for detailed troubleshooting proce dures. |
Automatically clears when the condition no longer exists. |
Alert Codes and Troubleshooting | Initial notification of critical alerts will pop up on the home screen and will be listed under notification menu. Minor and moderate alerts are found only under the notification menu. * Current Lennox modulating outdoor units are XC/XP20 and XC/XP25. | ||||
Alert Code | Priority Condition | Applicable System Component(s) | Actual Displayed Alert Text | Component or System Operational State and Troubleshooting Tip | How to clear alert code |
440 |
Moderate |
Inverter based outdoor unit* |
OD Inverter Compressor Slowdown – High Heat-Sink temperature | Compressor slowdown due to high heat sink temperature. √ Heat sink temperature is approaching limit. √ The compressor speed automatically slows to reduce heat sink tempera ture. √ The control sets indoor CFM and outdoor RPM to values according to de mand percentage rather than the actual Hz. √ Feedback from supplier tear down of inverter indicates that the screws that hold the inverter to the inverter board were loose causing poor contact be tween these two components. √ Tighten screws that hold the heat sink to the inverter control board. NOTE: Wait five minutes for all capacitors to discharge before checking screws. √ Inverter LEDs will blink code 13. √ Refer to the unit service documentation for detailed troubleshooting proce dures. |
Automatically clears when the condition no longer exists. |
441 |
Moderate |
Inverter based outdoor unit* |
OD Inverter Compressor Slowdown – High Compressor Current | Compressor slowdown due to high compressor current. √ Compressor slowdown due to high compressor current. √ Compressor current is approaching limit. √ The compressor speed automatically slows. √ The control sets indoor CFM and outdoor RPM to values according to de mand percentage rather than the actual Hz. √ Possible issue is system running at high pressures. √ Check for high pressure trips or other alert codes in iComfort® S30 and out door control. √ Inverter LEDs will blink code 14. √ Refer to the unit service documentation for detailed troubleshooting proce dures. |
Automatically clears when the condition no longer exists. |
442 |
Critical |
Outdoor unit | Compressor Top Cap Switch Strike Lockout | The top cap switch has opened five times within one hour. As a result, the outdoor unit is locked out. √ This condition occurs when compressor thermal protection sensor opens five times within one hour. √ Outdoor unit will stop. | To clear, disconnect power to out door unit and restart. |
443 |
Critical |
Outdoor unit |
MUC Unit Code to Inverter Model Mismatch | Incorrect appliance unit size code selected. √ Check for proper configuring under unit size code used for outdoor unit (see unit configuration guide or in installation instructions). √ If replacing inverter, verify inverter model matches unit size. √ Remove the thermostat from the system while applying power and repro gramming. |
Automatically clears after the cor rect match is detected following a power reset. |
530 | Moderate / Critical | IHarmony | Low Damper 24VAC Volt age | Low Damper 24VAC Voltage √ Damper supply voltage is less than 18VAC. √ Maintain non-zone mode for five minutes after alarm clears. | Automatically clears when the condition no longer exists. |
Alert Codes and Troubleshooting | Initial notification of critical alerts will pop up on the home screen and will be listed under notification menu. Minor and moderate alerts are found only under the notification menu. * Current Lennox modulating outdoor units are XC/XP20 and XC/XP25. | ||||
Alert Code | Priority Condition | Applicable System Component(s) | Actual Displayed Alert Text | Component or System Operational State and Troubleshooting Tip | How to clear alert code |
532 | Moderate | IHarmony | Zoning Pressure Switch Opened (High Pressure) | Zoning Pressure Switch Opened (high pressure) √ Compressor pressure is above the specified limit. √ Compressor is turned off. √ Zoning will be restored once the high pressure switch closes. | Automatically clears after com pressor pressure is within limits. |
542 | Moderate/ Critical | IHarmony | Zone 1 Temperature Sensor Problem | √ Zone temperature sensor reading out of range. √ Open or short zone temperature sensor detected for more than five sec ond. √ Damper control module will operate in non-zone mode (all dampers open) – moderate condition. √ If after 10 minutes the condition does not change, the priority code is change to critical. System will continue to operate in non-zone mode. |
Automatically clears 30 seconds after condition no longer exist. |
543 | Moderate/ Critical | IHarmony | Zone 2 Temperature Sensor Problem | ||
544 | Moderate/ Critical | IHarmony | Zone 3 Temperature Sensor Problem | ||
545 | Moderate/ Critical | IHarmony | Zone 4 Temperature Sensor Problem | ||
594 |
Moderate / Critical |
Equipment interface module |
Pre-Coil Air temp Sensor Problem | Pre-coil discharge air temperature sensor problem (DFM mode only). Ad vances from moderate to critical after ten (10) minutes. √ Interlock relay energized, but input not sensed after three seconds. √ No heating and cooling operations. √ De-energize interlock relay and re-energized five minutes later if demand is still present. |
Alarm clears five minutes after fault clears. |
600 |
Minor |
Outdoor unit |
Load Shed Event | Compressor has been cycled OFF on utility load shedding. √ Load shedding function provides a method for a local utility company to limit the maximum power level usage of the outdoor unit. √ The feature is activated by applying 24VAC power across the L and C ter minals on the outdoor control. | Automatically clears when L termi nal is inactive. |
Alert Codes and Troubleshooting | Initial notification of critical alerts will pop up on the home screen and will be listed under notification menu. Minor and moderate alerts are found only under the notification menu. * Current Lennox modulating outdoor units are XC/XP20 and XC/XP25. | ||||
Alert Code | Priority Condition | Applicable System Component(s) | Actual Displayed Alert Text | Component or System Operational State and Troubleshooting Tip | How to clear alert code |
601 |
Minor |
Heat Pump |
OD Unit Low Ambient Operational Lockout | √ This is a low ambient protection feature. √ Outdoor unit has been lock out (will not run) due to low ambient conditions. √ Outdoor unit will not operate when the outdoor ambient is at or below 4°F (20°C). √ If the unit is satisfying a demand (running) and the outdoor ambient drops below 4°F (20°C), the unit will continue to operate until the demand has been satisfied or the outdoor ambient drops to 15°F (26°C) which will re sult in the unit being locked out (shut down). |
Automatically clears when low temperature condition no longer exists. |
610 |
Critical |
Thermostat |
Low Room Temperature Detected | √ This alert will automatically notified the user that a low room temperature condition exist. A notification is displayed on the HD Display and email noti fication sent to homeowner and dealer. √ The freeze alert protection parameter range is 30°F to 50°F. Default is 40°F. NOTE: Notification is dependent on the thermostat having a active Wi-Fi connection and the user account has been setup and includes a valid email address. |
Automatically clears when condi tion is resolved. |
611 |
Critical |
Thermostat |
High Room Temperature Detected | √ This alert will automatically notified the user that a high room temperature condition exist. A notification is displayed on the HD Display and email noti fication sent to homeowner and dealer.. √ The heat alert protection parameter range is 80°F to 100°F. Default is 90°F. NOTE: Notification is dependent on the thermostat having a active Wi-Fi connection and the user account has been setup and includes a valid email address. |
Automatically clears when condi tion is resolved. |
700 | Critical | S30 HD Display Unit or Mag-Mount | Comfort Sensor Temp Sensor Problem | The temperature sensor in the HD Display is not working properly. √ Run reset all under Dealer Control Center. √ Try removing display from mag-mount and reattaching. √ If issue persist, then replace either the S30 HD Display or Mag-Mount. | Automatically clears when the system detects that the issue no longer exists. |
701 | Moderate | Thermostat | The thermostat is reading indoor temperatures above the pre-programmed limit. |
√ Run reset all under Dealer Control Center. √ Cool thermostat √ Adjust set point. √ Replace HD-Display or mag-mount, if needed. |
Automatically clears when the system detects that the issue no longer exists. |
702 | Moderate | Thermostat | The thermostat is reading indoor temperatures be low the pre-programmed limit. | ||
703 | Moderate | S30 Mag-Mount | The humidity sensor in the thermostat is not working properly. | Automatically clears when the system detects that the issue no longer exists. | |
704 | Moderate | S30 Mag-Mount | The thermostat is reading indoor humidity levels above the pre-pro grammed limit. | √ Run reset all under Dealer Control Center. √ Replace mag-mount, if needed. | Automatically clears when the system detects that the issue no longer exists. |
705 | Moderate | S30 Mag-Mount | The thermostat is reading indoor humidity levels be low the pre-programmed limit. | √ Run reset all under Dealer Control Center. √ Replace mag-mount, if needed. | Automatically clears when the system detects that the issue no longer exists. |
900 | Moderate | S30 System | Temperature Control Problem | Something is causing the system not to be able to reach set point. Check for dirty coil, low refrigerant or verify the system is not under size for the appli cation. | Automatically clears when the system detects that the issue no longer exists. |
Alert Codes and Troubleshooting | Initial notification of critical alerts will pop up on the home screen and will be listed under notification menu. Minor and moderate alerts are found only under the notification menu. * Current Lennox modulating outdoor units are XC/XP20 and XC/XP25. | ||||
Alert Code | Priority Condition | Applicable System Component(s) | Actual Displayed Alert Text | Component or System Operational State and Troubleshooting Tip | How to clear alert code |
901 | Critical | S30 System | Smart Alert | This indicates the system is not running in optimized efficiency. There may be a component or component that will require attention. NOTE: Currently this critical alert will not generate an email notification to the dealer or home owner. | Automatically clears when the system detects that the issue no longer exists. |
65537 | Critical | Thermostat | Missing Mag-Mount Base | √ Base not detected for more than 30 seconds. √ Amber LED is displayed on Smart Hub. √ Mount and wire Mag-Mount before powering up Smart Hub. | Automatically clears once is de tected for two seconds. |
65538 | Minor | Thermostat | Missing Mag-Mount Base | √ Base not detected for less than 30 seconds. √ Amber LED is displayed on Smart Hub. √ Mount and wire Mag-Mount before powering up Smart Hub. | Automatically clears once is de tected for two seconds. |
65539 | Critical | Thermostat | Missing HD Wall Display | √ HD Wall Display not detected for more than 30 seconds. √ Solid blue LED will appear on Mag-Mount if powered. √ Blinking blue LED will appear if not communicating with Smart Hub. | Automatically clears once is de tected for two seconds. |
65540 | Minor | Thermostat | Missing HD Wall Display | √ HD Wall Display not detected for less than 30 seconds. √ Solid blue LED will appear on Mag-Mount if powered. √ Blinking blue LED will appear if not communicating with Smart Hub. | Automatically clears once is de tected for two seconds. |
65541 | Minor | Thermostat | Download-failed | Download for firmware failed. | Not applicable. |
65542 | Minor | Thermostat | Hash verification failed | Has verification failed. Update failed. | Not applicable. |
65543 | Info | Thermostat | Firmware updated | When new firmware has been successfully updated to iComfort® S30. | Clears automatically after suc cessfully update. |
65544 | Critical | Thermostat | Too many siblings | The system is limited to no more than five (5) Smart Hubs in a local Wi-Fi network. | Once the system detects that only five or less Smart Hubs are de tected on the network will the alert code automatically clears. |
65545 |
Minor |
S30 System |
Cooling Prognostics Alert (capacity alert) | This indicates the system is not running cooling mode in optimized efficien cy. There may be a component or components that will require attention. NOTE: Currently this is a minor alert and will not generate an email notifica tion to the dealer or homeowner. Parameter settings for this feature are hidden for the software version 3.2 release. The information will be used for data collection only and sent to the Lennox server. This algorithm will determine whether the unit will run out of capacity during the hottest time of summer. It will look back everyday a minimum of three days to see if there is a pattern and compare it to the hottest day on record for that zip code before triggering an alert. It must see a pattern before it will trigger the alert. |
The system will continue to count the number occurrences within a 24 hours period where system de mand is not achieved. Will clear once cooling demand is achieved. |
Number | Value | Number | Value | Number | Value | Number | Value | Number | Value |
3000 | Filter 1 | 3002 | Humidifier Pad | 3004 | Maintenance | 4000 | User Wi-Fi state change, disable | 4002 | Image file download failed |
3001 | Filter 2 | 3003 | UV Light | 3005 | PureAir Maintenance | 4001 | Firmware download failed |
Download Manual
Lennox S30 Smart Thermostat Installation and setup Guide
OTHER MANUAL
Lennox S30 Smart Thermostat User Guide
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…