This installation sheet applies to AppStat controllers for heat pump units. The model numbers for these models end with “0003”. Additional information for the controllers can be found in the document Installation, Operation and Application Guide for the AppStat which is available on the KMC partners web site.
Planning for motion sensing
For models with a motion sensor mount the AppStat on a wall that will have an unobstructed view of the typical traffic in the coverage area. When choosing a location, do not install the sensor in the following areas.
The effective detection range is approximately 10 meters or 33 feet. Factors that may reduce the range include:
False detections may be triggered by:
For the most accurate performance, install the AppStat on an inside wall where it can sense the average room temperature. Avoid locations with direct sunlight, heat sources, windows, air vents, and air circulation or obstructions such as curtains, furniture, etc.
The AppStat must not be:
For models with motion sensing, see the topic, Planning for motion sensing.
Complete rough-in wiring at each location before mounting an AppStat. This includes the following steps.
To install the controller on a mounting base, do the following:
Caution: To prevent mounting screw heads from touching the circuit board in the controller, use only the mounting screws supplied by KMC Controls. Using screws other than the type supplied may damage the AppStat.
The inputs for the AppStat are configured for specific functions and do not require setup in the field. Not all inputs are required for every model or application.
Remote space temperature sensor (optional)
Connect a 10kΩ, Type II thermistor temperature sensor to the remote space temperature (RS) input and ground (GND) terminals. The input includes the internal pull-up resistor. An STE-6011W10 sensor is suitable for this application. Follow the instructions supplied with the sensor for installation.
When a remote space temperature input is connected to the AppStat, the remote temperature is used instead of the internal temperature sensor.
Fan status switch (optional)
Connect a Normally Closed Fan Status switch to the Discharge Air Temperature (DAT) input and ground (GND) terminals. The input includes the internal pull-up resistor. A CSE-1102 differential pressure switch is suitable for this application. Follow the instructions supplied with the switch for installation.
Outdoor air temperature sensor
Connect a 10kΩ, Type III thermistor temperature probe to the outdoor air temperature (OAT) input. The input includes the internal pull-up resistor. An STE-1451 sensor is suitable for this application. Follow the instructions supplied with the sensor for installation.
Discharge air temperature
Connect a 10kΩ, Type III thermistor temperature probe to the discharge air temperature (DAT) input. The input includes the internal pull-up resistor. An STE-1405 sensor is suitable for this application. Follow the instructions supplied with the sensor for installation.
Connecting outputs
The AppStat outputs are model dependent and are configured for specific applications.
Caution: Improperly connecting loads or equipment to output terminals may damage the equipment. Connect only as shown in the following diagrams or application drawings.
Connecting power
The AppStat requires an external, 24-volt, AC power source. Use the following guidelines when choosing and wiring transformers.
See Installation Accessories on page 4 for a list of transformers available from KMC Controls, Inc.
Remove dust as necessary from the holes in the top and bottom. Clean the display with soft, damp cloth and mild soap.
AppStat specifications are subject to change without notice.
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions:(1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
The following accessories are available from KMC Controls, Inc.
Additional resources
The latest support files are always available on the KMC Controls website.
For detailed specifications, installation, operating, application, and system integration information, see The Installation, Operation, and Application Guide for AppStat.
For additional specifications information, see the BAC-4000 AppStat Data Sheet.
The material in this document is for information purposes only. The contents and the product it describes are subject to change without notice. KMC Controls, Inc. makes no representations or warranties with respect to this document. In no event shall KMC Controls, Inc. be liable for any damages, direct or incidental, arising out of or related to the use of this document.
KMC Controls, Inc.
P.O. Box 497
19476 Industrial Drive
New Paris, IN 46553
U.S.A.
TEL: 1.574.831.5250
FAX: 1.574.831.5252
E-mail: info@kmccontrols.com
DOWNLOAD MANUALS:
KMC Controls BAC-4201CW0003 BACnet or Stand Alone Thermostat Installational Guide
KMC Controls BAC-4201CW0003 BACnet or Stand Alone Thermostat Installational Guide
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…