| Technical Data | TFC24F3XYZ3 |
| Inputs | 1 Analog input (external temperature sensor 10Kohms) |
| 1 Analog input (change over 10Kohms or dry contact) | |
|
Outputs | 1 Fan analog or 3 Fan speed dry contracts 24Vac, 1A max 3A in-rush |
| 2 Analog outputs (cooling and/or heating 0-10Vdc) | |
| 1 Analog output (local reheat 0-10Vdc ) | |
| 2 Triacs output (cooling and/or heating) 24Vac, 0.3A max fused / triac | |
| 1 Triacs output (local reheat) 24Vac, 0.3A max fused / triac | |
| Power supply | 22 to 26 Vac 50/60Hz |
| Power consumption | 1 VA max |
| Set point range | 10ºC to 40ºC [50ºF to 104ºF] |
| Control accuracy | Temperature: ±0.4ºC [0.8ºF] |
| Proportional band | 0.5ºC to 5ºC [1ºF to 10ºF] adjustable (heat/cool/reheat independent) |
| Dead band | 0.3ºC to 5ºC [0.6ºF to 10ºF] adjustable (heat/cool/reheat independent) |
| Electrical connection | 0.8 mm2 [18 AWG] minimum |
| Operating temperature | 0ºC to 50ºC [32ºF to 122ºF] |
| Storage temperature | -30ºC to 50ºC [-22ºF to 122ºF] |
| Relative Humidity | 5 to 95 % non condensing |
| Degree of protection of housing | IP 30 (EN 60529) |
| Weight | 160 g. [0.36 lb] |
Presentation
| Dimension | Inches | Metric (mm) |
| A | 2.85 | 73 |
| B | 4.85 | 123 |
| C | 1.00 | 24 |
| D | 2.36 | 60 |
| E | 3.27 | 83 |
Mounting Instructions
CAUTION: Risk of malfunction. Remove power prior to separating the thermostat cover from its base.
| 2 Pipe | Analog | On/Off | Floating | ||||||||||||
| Terminals | Fan option | analog | 1 spd | 2 spd | 3 spd | analog | 1 spd | 2 spd | 3 spd | analog | 1 spd | 2 spd | 3 spd | ||
|
TB1 | 1 | Common | Common | Common | Common | ||||||||||
| 2 | 24 Vac | 24 Vac | 24 Vac | 24 Vac | |||||||||||
| 3 | Common Triac | Common Triac | Common Triac | Common Triac | |||||||||||
| 4 | Triac output 1 (TO1) | Floating output 1 | – | 2 Pipe on/off | 2 Pipe floating (close) | ||||||||||
| 5 | Triac output 2 (TO2) | – | – | 2 Pipe floating (open) | |||||||||||
| 6 | Triac output 3 (TO3) Reheat | Local reheat (optional) (on/off or pulse) | Local reheat (optional) (on/off or pulse) | Local reheat (optional) (on/off or pulse) | |||||||||||
| 7 | Common Relay | – | Common Relay | – | Common Relay | – | Common Relay | ||||||||
| 8 | Digital output 1 (DO1) | – | – | – | High | – | – | – | High | – | – | – | High | ||
| 9 | Digital output 2 (DO2) | – | – | High | Med | – | – | High | Med | – | – | High | Med | ||
| 10 | Digital output 3 (DO3) / Analog Fan Speed (AO4) | Fan analog | 1 spd | Low | Low | Fan analog | 1 spd | Low | Low | Fan analog | 1 spd | Low | Low | ||
| 11 | Not used | – | – | – | |||||||||||
| 12 | External Temp. Sensor (AI1) | External Temp. Sensor (optional) | External Temp. Sensor (optional) | External Temp. Sensor (optional) | |||||||||||
| 13 | External Changeover (AI2) | External Changeover | External Changeover | External Changeover | |||||||||||
| 14 | Analog output 1 (AO1) | 2 Pipe analog | – | – | |||||||||||
| 15 | Analog output 2 (AO2) | – | – | – | |||||||||||
| 16 | Analog output 3 (AO3) Reheat | Local reheat analog (optional) | Local reheat analog (optional) | Local reheat analog (optional) | |||||||||||
| 4 Pipe | Cool & Heat Analog | Cool & Heat On/Off | Cool Analog-Heat On/Off or pulse | Cool On/Off – Heat Analog | |||||||||||||||
| Terminals | Fan option | analog | 1 spd | 2 spd | 3 spd | analog | 1 spd | 2 spd | 3 spd | analog | 1 spd | 2 spd | 3 spd | analog | 1 spd | 2 spd | 3 spd | ||
|
TB1 | 1 | Common | Common | Common | Common | Common | |||||||||||||
| 2 | 24 Vac | 24 Vac | 24 Vac | 24 Vac | 24 Vac | ||||||||||||||
| 3 | Common Triac | Common Triac | Common Triac | Common Triac | Common Triac | ||||||||||||||
| 4 | Triac output 1 (TO1) | Floating output 1 | – | 4 Pipe on/off cool | – | 4 Pipe on/off cool | |||||||||||||
| 5 | Triac output 2 (TO2) | – | 4 Pipe (on/off or pulse) heat | 4 Pipe (on/off or pulse) heat | – | ||||||||||||||
| 6 | Triac output 3 (TO3) Reheat | Local reheat (optional) (on/off or pulse) | Local reheat (optional) (on/off or pulse) | Local reheat (optional) (on/off or pulse) | Local reheat (optional) (on/off or pulse) | ||||||||||||||
| 7 | Common Relay | – | Common Relay | – | Common Relay | – | Common Relay | – | Common Relay | ||||||||||
| 8 | Digital output 1 (DO1) | – | – | – | High | – | – | – | High | – | – | – | High | – | – | – | High | ||
| 9 | Digital output 2 (DO2) | – | – | High | Med | – | – | High | Med | – | – | High | Med | – | – | High | Med | ||
| 10 | Digital output 3 (DO3) / Analog Fan Speed (AO4) | Fan analog | 1 spd | Low | Low | Fan analog | 1 spd | Low | Low | Fan analog | 1 spd | Low | Low | Fan analog | 1 spd | Low | Low | ||
| 11 | Not used | – | – | – | – | ||||||||||||||
| 12 | Ext. Temp Sensor (AI1) | External Temp. Sensor (optional) | External Temp. Sensor (optional) | External Temp. Sensor (optional) | External Temp. Sensor (optional) | ||||||||||||||
| 13 | External Changeover (AI2) | – | – | – | – | ||||||||||||||
| 14 | Analog output 1 (AO1) | 4 Pipe analog cool | – | 4 Pipe analog cool | – | ||||||||||||||
| 15 | Analog output 2 (AO2) | 4 Pipe analog heat | – | – | 4 Pipe analog heat | ||||||||||||||
| 16 | Analog output 3 (AO3) Reheat | Local reheat analog (optional) | Local reheat analog (optional) | Local reheat analog (optional) | Local reheat analog (optional) | ||||||||||||||
When in this mode this symbol
Push the button
Recycling at end of life
At end of its life, please return the thermostat to your Neptronic® local distributor for recycling. If you need to find the nearest Neptronic® authorized distributor, please consult www.neptronic.com.
DOWNLOAD MANUALS:
Neptronic TROB24 Programmable Thermostat Product Specifications Guide
Neptronic TROB24 Programmable Thermostat Product Specifications Guide
Free Money Online Casino No Deposit Canada However, and players have no control over it.…
Eureka Casino No Deposit Bonus Codes For Free Spins 2026 Furthermore, and beginner-friendly as well.…
Top 10 Online Canada Casinos Top 10 online canada casinos you can contact Easy Slots'…
2026 Canada Changes In Blackjack 2026 canada changes in blackjack an online casino reload bonus…
Mannheim Casino No Deposit Bonus Codes For Free Spins 2026 Don't miss out on this…
Slot Games For Real Money I should start with a variety of gambling options, you…