Honeywell

Honeywell 2000 Microelectronic Thermostat User Manual

Honeywell 2000 Microelectronic Thermostat

Product OVERVIEW

FEATURES

  • Program up to two Occupied and two Unoccupied time periods for each daily schedule.
  • Set different schedules for each day of the week.
  • Temporary temperature overrides.
  • Program copy key.

PROGRAMMING

The keyboard is located behind the thermostat cover. Sixteen keys are used to set, review and modify programmed times and temperature settings.
The thermostat display shows a day, time, program period, and temperature.
The thermostat can be set for two Occupied and two Unoccupied times for each day of the week (28 independent time settings). Temporary Occupied key provides quick temporary temperature changes for increased occupant comfort. The Continuous An unoccupied key provides energy-efficient operation for extended periods of time.
Before starting the program procedure, use the the following chart to organize the program schedule.

Day

Occupied Period 1 Unoccupied Period 1 Occupied Period 2 Unoccupied Period 2
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday

The program has four temperature settings, Occupied and Unoccupied heat, and cool. The thermostat will operate at the Unoccupied temperature setting unless the thermostat is programmed. The following chart shows the default temperature settings.

 

Control

Occupied Setpoint Unoccupied Setpoint
Default Desired Default Desired
Heating 70°F (21°C) 55°F (13°C)
Cooling 78°F (25.5°C) 90°F (32°C)

Setting Current Day and Time

  1. Press Set Current Day/Time.
    NOTE: On initial power-up or after an extended power loss, 1:00 pm flashes on the LCD until a key is pressed.
  2. Press Day until the current day is displayed.
    NOTE: Sun = Sunday, Mon = Monday, Tue = Tuesday, Wed = Wednesday, Thu = Thursday, Fri = Friday, Sat = Saturday.
  3. Press the increase ▲ or decrease ▼ key until the current time is displayed.
    NOTE: Tapping the Set Current Day/Time will change the time in one-hour increments.
  4. Press Run Program.

Setting Program Times

  1. Press Occupied Start Time.
    NOTE: Anytime a start time is not required, press the Clear Start Time.
  2. Press Day until the desired day is displayed.
  3. Press the increase ▲ or decrease ▼ key until the desired start time is displayed.
    NOTE: The program times are in fifteen-minute intervals. (Example: 8:00, 8:15, 8:30).
  4. Press Occupied Start Time a second time to set a second Occupied Start Time.
  5. Press the increase ▲ or decrease ▼ key until the desired start time is displayed.
  6. Press Unoccupied Start Time.
  7. Press the increase ▲ or decrease ▼ key until the desired start time is displayed.
  8. Press Unoccupied Start Time a second time to set a second Unoccupied Start Time.
  9. Press increase ▲ or decrease ▼ key until the desired start time is displayed.

Copying a Day

NOTE: The thermostat must be in program mode to use the copy feature. Go to step 2 if the thermostat is already in the program mode.

  • Press Occupied Start Time.
  • Press Day to select the day to be copied if different from the day displayed.
  • Press Copy.
  • Press Day until the day to be copied is displayed.
  • Press Copy.
    NOTE: donE will be displayed for two seconds and then the normal program display will be shown.
  • Repeat steps 2 through 5 for all the days desired.
  • Press Run Program.

Setting Program Temperature Setpoints

NOTE: The setpoint temperature range is 40 to 90°F (7 to 31°C) for heating and 45 to 99°F (9 to 37°C) for cooling.

  1. Press Occupied Temp.
  2. Press the increase ▲ or decrease ▼ key until the desired temperature is displayed.
  3. Press Heat/Cool Settings to change between heat and cool settings.
  4. Press the increase ▲ or decrease ▼ key until the desired temperature is displayed.
  5. Press Unoccupied Temp.
  6. Press increase ▲ or decrease ▼ key until the desired temperature is displayed.
  7. Press Heat/Cool Settings to change between heat and cool settings.
  8. Press the increase ▲ or decrease ▼ key until the desired temperature is displayed.
  9. Press Run Program.

Clearing Program Start Times

  • Press Occupied Start Time or Unoccupied Start Time until the start time to be cleared is displayed.
  • Press Day until the desired day is displayed
  • Press Clear Start Time.
  • Repeat steps 1 through 3 for all the start times to be cleared.
  • Press Run Program.

Temporary Occupied Override

Setting Temperature Offset for Temporary Override

  1. Press Occupied Temp.
  2. Press Temporary Occupied.
  3. Press the increase ▲ or decrease ▼ key until the desired temperature offset is displayed (range is 0° to 5°F).
  4. Press Run Program.

Using Temporary Override

  1. Press Temporary Occupied.
    NOTE: The default temperature setting is the Occupied setpoint.
  2. Press the increase ▲ or decrease ▼ key to change the default setting by the offset (range is 0° to 5°F), if desired.
    NOTE: If the offset is zero, the default setting changes in one-degree increments. If the offset is 1 through 5, the default setting changes by plus or minus the offset.
  3. Press Run Program to cancel the override.

Using Continuous Unoccupied

  1. Press Continuous Unoccupied.
    NOTE: The default temperature setting is the Unoccupied setpoint. The default appears for five seconds and then the display shows the room temperature.
  2. Press the increase ▲ or decrease ▼ key to change the default setting if desired.
  3. Press Heat/Cool Setpoint to change between heat and cool settings. Use the increase ▲ or decrease ▼ key to adjust temperature settings.
  4. Press Run Program again to cancel the Hold and to return to the program.

Changing Temperature Setpoint Until Next Program Period

  1. Press the increase ▲ or decrease ▼ key until the desired temperature is displayed.
    NOTE: If ▼ or ▲ appear under the temperature display, it means that both the heating and cooling setpoints are being adjusted. Tapping the key will change both the heat and cool setpoints by one degree. Press Heat/Cool Settings after the desired setpoint is reached to review the settings.
  2. Press Run Program to cancel the temporary setpoint and to return to the program.

TROUBLESHOOTING GUIDE

Symptom Action
Display will not come on. •      Check if the circuit breaker is tripped—reset the circuit breaker.

•      Check if the fuse is blown—replace the fuse.

•      Check if the system switch at the equipment is in the Off position— set to the On position.

•      Check wiring between thermostat and HVAC equipment—replace any broken wires.

•      If 24 Vac is present, proceed with troubleshooting.

Temperature settings will not change (Example: cannot set the heating higher or the cooling lower). •      Check that the temperature setpoints are:

–      heating: 40 to 90°F (7 to 31°C)

–      cooling: 45 to 99°F (9 to 37°C).

•      Keyboard is locked. Contact the installer.

Heating will not come on. •      Check if the circuit breaker is tripped—reset the circuit breaker.

•      Check if the fuse is blown—replace the fuse.

•      Check if the system switch at the equipment is in the Off position— set to On position.

•      If 24 Vac is present, proceed with troubleshooting.

•      Wait five minutes for the system to respond.

•      Set system selection to Heat.

Symptom Action
Cooling will not come on. •      Check if the circuit breaker is tripped—reset the circuit breaker.

•      Check if the fuse is blown—replace the fuse.

•      Check if the system switch at the equipment is in the Off position— set to On position.

•      If 24 Vac is present, proceed with troubleshooting.

•      Wait five minutes for the system to respond.

•      Set system selection to Cool.

System on indicator (flame=heat, snowflake=cool) is displayed, but no warm or cool air is coming from the registers. Wait a minute after seeing the flame or snowflake and then check the registers.

Automation and Control Solutions
Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422-4386
Honeywell Limited-Honeywell Limitée
35 Dynamic Drive
Scarborough, Ontario M1V 4Z9
www.honeywell.com/buliding/components

Reference

Download Manual

Honeywell 2000 Microelectronic Thermostat User Manual

Honeywell 2000 Microelectronic Thermostat User Manual

wpx_thermostats

Recent Posts

Johnson Controls T7000e LCD Digital Thermostat Installation Guide

Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide

1 year ago

Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’S GUIDE

Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE

1 year ago

Hetta HS01RF WIRELESS THERMOSTAT KIT USER MANUAL

Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…

1 year ago

HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat USER MANUAL

HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…

1 year ago

Honeywell RLV450 PROGRAMMABLE THERMOSTAT USER GUIDE

Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…

1 year ago

Honeywell RLV431 Programmable Thermostat User Guide

Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…

1 year ago