T4039 Thermostats Control Line Voltage Valves of a fan coil unit in cooling, manual changeover heating-cooling, or automatic changeover heating-cooling systems. One or two valves may be controlled directly by the thermostat. The fan switch (where applicable) controls air circulation.
MODELS:
| System | Manual Switchinga | Model |
| Cooling Only | Off-Onb | T4039A |
| Cooling Only | Hi-Med-Lo Off-Onb | T4039B |
| Heating-Coolingc | — Off-Ond | T4039D |
| Heating Coolingc | Off-Hi-Lob — | T4039E |
| Heating-Coolingc | Hi-Med-Lo Off-Onb | T4039F |
| Automatic Heating-Cooling | None | T4039G |
| Automatic Heating-Cooling | — Off-Ond | T4039H |
| Automatic Heating-Cooling | Off-Hi-Lob | T4039J |
| Automatic Heating-Cooling | Off-Hi-Lod — | T4039K |
| Automatic Heating-Cooling | Hi-Med-Lob Off-On | T4039L |
| Autoamtic Heating-Cooling | Hi-Med-Lo Off-Ond | T4039M |
| Automatic Heating-Cooling | Hi-Med-Lo Heat-Off-Coold | T4039S |
| Automatic Heating-Cooling | Hi-Lo Off-Ond | T4039V |
ELECTRICAL RATINGS:
| Normal (A) | Inrush (B) | |
| 120 Vac | 0.32 | 1.00 |
| 240 Vac | 0.16 | 0.50 |
| 277 Vac | 0.14 | 0.43 |
| Full Load (A) | Locked Rotor (A) | |
| 120 Vac | 5.5 | 33.0 |
| 240 Vac | 2.75 | 16.5 |
| 277 Vac | 2.4 | 14.4 |
| 10A | Resistive at 125 Vac | |
| 5A | Resistive at 240 Vac | |
| 4.2A | Resistive at 277 Vac |
TEMPERATURE SETTING RANGE: Approximately 55° F to 95° F [13° C to 35° C]; marked COOLWARM in 10° F [6° C] increments from 75° F [24° C] midpoint.
DIFFERENTIAL: Approximately 2° F [1° C] at midscale. On automatic heating-cooling models, the differential from make of one contact to make of the opposite contact is 7° F [4° C] maximum with a positive deadspot.
DIMENSIONS: See Figs. 1 and 2.
When purchasing replacement and modernization products from your TRADELINE® wholesaler or your distributor, refer to the TRADELINE Catalog or price sheets for the complete ordering number, or specify—
FINISH: Silver bronze. T4039M is available in white.
MOUNTING: Models without manual switching mount on standard vertical outlet boxes. Models with manual switching mount on 4-in. square junction boxes or 2-ganged outlet boxes. Manual switching models may also mount on a standard vertical outlet box if local codes permit. See Fig. 3.
UNDERWRITERS LABORATORIES, INC. LISTED: File No. E4436, Vol. 2, dated 3-19-73; Guide No. XAPX.
WHEN INSTALLING THIS PRODUCT…
CAUTION
Disconnect the power supply to prevent electrical shock or equipment damage.
Before mounting, be sure to remove the cardboard shipping inserts that protect the contacts.
MOUNTING
Models without manual switching mount on standard vertical outlet boxes. Models with manual switching mount on 4-in. square junction boxes or 2-ganged outlet boxes. Manual switching models can also mount on standard vertical outlet boxes if local electrical codes permit. Mount thermostat on side wall about 5 ft. [1.5 m] above the floor. Do not mount where the thermostat can be affected by drafts, radiant heat from the sun or other sources of heat. Use Allen wrench to open cover and mount according to Fig. 3. Two mounting screws are provided.
WIRING
Disconnect power supply before beginning installation to avoid electrical shock or equipment damage. All wiring must comply with local codes and ordinances. Internal schematic and external connections for the T4039 are shown in Fig. 4. Use solderless connectors or other approved methods to wire the thermostat into the system. Six-inch color-coded lead wires are provided.
SETTING
The T4039 temperature scale is marked COOL-WARM with approximate scale divisions of 10° F from 75° F [24° C] midpoint. The range is approximately 55° F to 95° F [13° C to 35° C]. Set lever at desired temperature. To adjust the temperature setpoint range stops, Fig. 3, locate stops at the desired temperature range setpoint and insert them.
Fig. 4—Internal schmeatics and external connections for T4039 Thermostats.
| TYPICAL T4039K | YELLOW | BLUE | RED | BROWN | ORANGE |
| T4039K1024 | BROWN | RED | BLUE | YELLOW | BLACK |
In heating applications, as the temperature drops, the thermostat heating contacts make to open a valve that allows hot water to flow through the coil. On select models, the speed at which the heat is circulated is controlled manually by the fan switch.
In cooling applications, as the temperature rises, the thermostat cooling contacts close to open a valve that allows cold water to flow through the coil. The cooling mechanism will not operate if the manual switch is in the OFF position. Models T4039D,H, K,M,S,V will also turn off the heating valve when the manual switch is in OFF. In manual changeover heating-cooling models, the thermostat must be used with a remote changeover switch or control to select the proper heating or cooling cycle for the thermostat.
CALIBRATION
The T4039 is accurately calibrated at the factory under controlled conditions. Do not attempt to field calibrate this device.
Check the T4039 before leaving the installation. Raise the temperature setting to start the heating cycle or lower the setting to start the cooling cycle. Check both cycles on heating-cooling models.
Home and Building Control
Honeywell International, Inc. 1985 Douglas Drive North
Home and Building Control
Honeywell Limited—Honeywell Limitée 35 Dynamic Drive Golden Valley, MN 55422 Scarborough, Ontario
M1V 4Z9
Download Manual
Honeywell T4039A Line Voltage Thermostat User Manual
Free Money Online Casino No Deposit Canada However, and players have no control over it.…
Eureka Casino No Deposit Bonus Codes For Free Spins 2026 Furthermore, and beginner-friendly as well.…
Top 10 Online Canada Casinos Top 10 online canada casinos you can contact Easy Slots'…
2026 Canada Changes In Blackjack 2026 canada changes in blackjack an online casino reload bonus…
Mannheim Casino No Deposit Bonus Codes For Free Spins 2026 Don't miss out on this…
Slot Games For Real Money I should start with a variety of gambling options, you…