Vive

VIVE Comfort TP-Z-DPMW Thermostat INSTALLATION MANUAL

VIVE Comfort TP-Z-DPMW Thermostat

QUICK REFERENCE

Damper Module(s)

  • The Damper Module is designed to operate with 24VAC 2-wire and 3-wire zone dampers.
  • The Damper Module(s) must be hardwired with 24VAC connected to R and C.
  • The zone damper will be connected to the NC, C, and NO terminals on the left side of the subbase.
  • The Master Thermostat will transmit the required damper position to the Damper Modules.
  • When the damper position is open, the ZONE LED will be ashing. 24VAC will be supplied to NC and C terminals.
  • When the damper position is closed, the ZONE LED will be solid. 24VAC will be supplied to NO and C terminals.
  • Wire the terminals according to the damper type used.

Caution:
Electrical Hazard
Failure to disconnect the power before beginning to install this product can cause electrical shock or equipment damage.

Damper Type                       Terminals

Normally-Closed, Power-Open NC & C
Normally-Open, Power-Close NO & C
Power-Open/ Power-Close NC, C, & NO

NOTE: To link damper module(s) to a desired zone, see page 4 for establishing communication.
NOTE:
Static/Barometric Bypass damper is recommended on all systems for safe and efficient zoning.
This system does not control bypass dampers.

WIRING

24VAC Transformer

Caution:
Electrical Hazard
Failure to disconnect the power before beginning to install this product can cause electrical shock or equipment damage.

NOTE: Multiple Damper Modules and zone dampers can be powered by one 24VAC transformer. It may be necessary to use a transformer separate from the HVAC system transformer. Multiple 24VAC motorized dampers can be controlled by one Damper Module.

ESTABLISHING COMMUNICATION

Remember
This Wireless Zoning System contains selectable wireless communication. Each component has a jumper switch labeled FSK and ASK. Default setting: FSK. All components must be set to the same position for wireless communication. This selectable communication option is available to you in case you have a device you are pairing with that only has the ASK option.

Establishing Communication between Master Thermostat and Damper Module

Once the Damper Module(s) are hardwired/ powered, follow the steps below to link their communication with the Master Thermostat. Keeping in mind…

  1. If you only need one Damper Module to control the Master Zone1, it is already factory linked to the Master Thermostat, out of the box.
  2. If you need multiple Damper Modules to control a single zone, they all need to be linked to that particular zone with the same procedure.
  3. Each Damper Module will open and close the damper(s) for the zone that it is congured to control.
  4. Each Damper Module will indicate the Zone Number it is congured for by using the Zone 1-5 LED indicators.

Linking Procedure

  1. To put the Damper Module(s) in learn mode; Hold the Learn Button until it’s communication LED begins flashing steady. Note all parts must have power to perform linking procedure
  2. With the Master Thermostat enter Tech Setup Mode, then proceed to the Link Damper Module Step (See page 16 of the Master Thermostat Installation Manual). This step connects the Master Module to the Damper Module(s). Use the to select the Zone Number, Zone 1-5.
  3. With the desired Zone Number selected on the Master Thermostat and the Damper Module(s) in Learn Mode (LED flashing), press and hold the FAN key on the Master Thermostat to Link and Congure the Damper Module for the Zone Number shown the Master Thermostat.

SPECIFICATIONS & CONTACT INFORMATION

Damper Module

  • Load rating:3 amps per terminal/3 amps total
  • Power source:18 to 30 VAC, NEC Class II, 50/60 Hz
  • Operating ambient:32ºF to +105ºF (0º to +65ºC)
  • Operating humidity:90% non-condensing maximum

REFERENCE

Download Manual

VIVE Comfort TP-Z-DPMW Thermostat INSTALLATION MANUAL

VIVE Comfort TP-Z-DPMW Thermostat INSTALLATION MANUAL

wpx_thermostats

Recent Posts

Johnson Controls T7000e LCD Digital Thermostat Installation Guide

Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide

2 years ago

Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’S GUIDE

Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE

2 years ago

Hetta HS01RF WIRELESS THERMOSTAT KIT USER MANUAL

Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…

2 years ago

HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat USER MANUAL

HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…

2 years ago

Honeywell RLV450 PROGRAMMABLE THERMOSTAT USER GUIDE

Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…

2 years ago

Honeywell RLV431 Programmable Thermostat User Guide

Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…

2 years ago