VIVE Comfort TP-Z-DPMW Thermostat
QUICK REFERENCE
Damper Module(s)
- The Damper Module is designed to operate with 24VAC 2-wire and 3-wire zone dampers.
- The Damper Module(s) must be hardwired with 24VAC connected to R and C.
- The zone damper will be connected to the NC, C, and NO terminals on the left side of the subbase.
- The Master Thermostat will transmit the required damper position to the Damper Modules.
- When the damper position is open, the ZONE LED will be ashing. 24VAC will be supplied to NC and C terminals.
- When the damper position is closed, the ZONE LED will be solid. 24VAC will be supplied to NO and C terminals.
- Wire the terminals according to the damper type used.
Caution:
Electrical Hazard
Failure to disconnect the power before beginning to install this product can cause electrical shock or equipment damage.
Damper Type Terminals
Normally-Closed, Power-Open | NC & C |
Normally-Open, Power-Close | NO & C |
Power-Open/ Power-Close | NC, C, & NO |
NOTE: To link damper module(s) to a desired zone, see page 4 for establishing communication.
NOTE:
Static/Barometric Bypass damper is recommended on all systems for safe and efficient zoning.
This system does not control bypass dampers.
WIRING
24VAC Transformer
Caution:
Electrical Hazard
Failure to disconnect the power before beginning to install this product can cause electrical shock or equipment damage.
NOTE: Multiple Damper Modules and zone dampers can be powered by one 24VAC transformer. It may be necessary to use a transformer separate from the HVAC system transformer. Multiple 24VAC motorized dampers can be controlled by one Damper Module.
ESTABLISHING COMMUNICATION
Remember
This Wireless Zoning System contains selectable wireless communication. Each component has a jumper switch labeled FSK and ASK. Default setting: FSK. All components must be set to the same position for wireless communication. This selectable communication option is available to you in case you have a device you are pairing with that only has the ASK option.
Establishing Communication between Master Thermostat and Damper Module
Once the Damper Module(s) are hardwired/ powered, follow the steps below to link their communication with the Master Thermostat. Keeping in mind…
- If you only need one Damper Module to control the Master Zone1, it is already factory linked to the Master Thermostat, out of the box.
- If you need multiple Damper Modules to control a single zone, they all need to be linked to that particular zone with the same procedure.
- Each Damper Module will open and close the damper(s) for the zone that it is congured to control.
- Each Damper Module will indicate the Zone Number it is congured for by using the Zone 1-5 LED indicators.
Linking Procedure
- To put the Damper Module(s) in learn mode; Hold the Learn Button until it’s communication LED begins flashing steady. Note all parts must have power to perform linking procedure
- With the Master Thermostat enter Tech Setup Mode, then proceed to the Link Damper Module Step (See page 16 of the Master Thermostat Installation Manual). This step connects the Master Module to the Damper Module(s). Use the to select the Zone Number, Zone 1-5.
- With the desired Zone Number selected on the Master Thermostat and the Damper Module(s) in Learn Mode (LED flashing), press and hold the FAN key on the Master Thermostat to Link and Congure the Damper Module for the Zone Number shown the Master Thermostat.
SPECIFICATIONS & CONTACT INFORMATION
Damper Module
- Load rating:3 amps per terminal/3 amps total
- Power source:18 to 30 VAC, NEC Class II, 50/60 Hz
- Operating ambient:32ºF to +105ºF (0º to +65ºC)
- Operating humidity:90% non-condensing maximum