Pull the thermostat directly away from the wall to access the batteries. A firm tug will be required to remove the thermostat from the subbase mounted on the wall.
Caution:
When the battery icon appears replace your AA batteries immediately. Failure to do so may result in your heating & cooling system becoming inoperable. Freezing or overheating can occur.
Important:
The low battery indicator is displayed when the AA battery power is low. If the user fails to replace the battery within 21 days, the screen will only show the low battery indicator but maintain all functionality. If the user fails to replace the batteries after an additional 21 days (days 22-42 since first “low battery” display) the setpoints will change to 55˚F (Heating) and 85˚F (Cooling). If the user adjusts the setpoint away from either of these, it will hold for 4 hours and then return to either 55˚F or 85˚F. After day 63 the batteries must be replaced immediately to avoid freezing or overheating because the thermostat will shut the unit off until the batteries are changed.
Follow the steps below to change your target humidity setpoint.
Press the humidity button.
Use the
Note:
The target humidity setpoint is not programmable. Unlike temperature, humidity does not change quickly and should not be programmed.
Note:
Humidity is only energized during heat. Dehumidity is only energized during cool. Heat and cool each have their own target setpoints.
Ambient Humidity Display
Ambient humidity will flash opposite the day and time. If the optional outdoor temperature sensor is installed the ambient outdoor temperature will also cycle in the display.
Increasing Humidity
The table on the right shows recommended indoor humidity levels in relation to outdoor temperatures during heating (adding humidity).
Set Time
Follow the steps below to set the day of the week and current time:
Important:
You will see a TECHNICIAN SETUP option after the MENU key is pressed. This TECHNICIAN SETUP key is for installer configuration and should NOT be changed unless you consult your professional heating and air conditioning technician.
Set 5+1+1 Program Schedule
To customize your 5+1+1 Program schedule, follow these steps:
Weekday:
Repeat steps 4 through 7 for the remaining days of the week.
A Note About Programmable Fan
The programmable fan feature will run the fan continuously during any time period it is programmed to be on. This is the best way to keep the air circulated and to eliminate hot & cold spots in your building.
Next Zone (Only if indoor remote is connected)
The NEXT ZONE key cycles through all sensors connected to your wireless system.
SYSTEM AVERAGE shows the average ambient temperature of all connected sensors.
LOCAL shows the ambient temperature of the thermostat only.
The name of the remote sensor will show and the ambient temperature for that sensor will be displayed.
For more information please refer to the Indoor Remote Sensor User Guide.
Keypad Lockout Note:
If appears in the display, then the keypad is locked. All or some of the keys will not work. Hold the
Temporary Hold: The thermostat will display HOLD and Run Schedule on the bottom of your screen when you press the
Permanent Hold: With a temporary hold set, if you press the HOLD key at the bottom of your screen, you will see HOLD appear next to the setpoint temperature in the display. The thermostat will now permanently stay at this setpoint and can be adjusted using the
To Return To the Program: Press the Run Schedule key at the bottom of your screen to exit temporary and permanent holds.
Filter Change & Other Reminders
If your HVAC contractor has configured the thermostat to remind you when the air filter needs changed, you will see a reminder in the display when your air filter needs to be changed.
Resetting The Filter Change Reminder: When the reminder is displayed, you should change your air filter and reset the reminder by pressing the CLEAN key for 3 seconds.
Warranty Registration
Your new thermostat has a 5 year limited warranty. You must register your thermostat within 60 days of installation. Without this registration, the warranty period will begin on the date of manufacture. For warranty issues please contact the HVAC professional that installed this product. You can register your new thermostat in 2 ways:
Warranty Registration
Name:
Address:
City:
State:
Zip:
Thermostat Model:
Date Installed:
Complete form and mail to: Thermostat Warranty Registration Vive Comfort P.O. Box 3377
Springfield, MO 65808-3377
www.vivecomfort.com
Download Manual:
Vive Comfort TP-S-955WH Non-Programmable Thermostat Operational Manual
OTHER MANUALS
Vive Comfort TP-S-955WH Non-Programmable Thermostat Installation Manual
Vive Comfort TP-S-955WH Non-Programmable Thermostat Operational Manual
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…