Power Type
A trained, experienced technician must install this product.
Carefully read these instructions. You could damage this product or cause a hazardous condition if you fail to follow these instructions.
Wall Locations
The thermostat should be installed approximately 4 to 5 feet above the floor. Select an area with average temperature and good air circulation
Do not install thermostats in these locations:
Mount Thermostat and Base Module
Align the 4 tabs on the subbase with corresponding slots on the back of the thermostat/base module, then push gently until it snaps in place.
Battery installation is optional if there are no remotes connected to the Master Thermostat (C terminal connected). If you connect an outdoor remote and/or indoor remote sensors it is required the thermostat be hardwired.
Important: High quality alkaline batteries are recommended. Rechargeable batteries or low quality batteries do not guarantee a 1-year life span.
Installation Tips
When performing an attic installation, instead of placing the base module in the attic, locate the closet nearest to the air conditioning unit. Then mount the base module high on the wall inside the closet or on the ceiling of the closet. This location will insure the base module is below the 150°F maximum ambient temperature specification
Wireless Range
Range between the thermostat and the base module is up to 100 feet with no obstructions and approximately 50 feet in standard residential construction. To extend the range try replacing the base unit higher if in a basement or further away from large metal objects
About The Badge
All of our thermostats use the same universal magnetic badge. Visit the company website to learn more about our free private label program.
Follow these steps for a simple wireless communication setup.
Thermostat, indoor/outdoor sensors.
Terminal Designations on the Base Module
This thermostat is shipped from the factory to operate a conventional heating and cooling system. This thermostat may also be configured for a heat pump system. See the “heat pump” configuration step on page 23 of this manual to configure the thermostat for heat pump applications
Terminal | 2 Heat 2 Cool Conventional System | 2 Heat 2 Cool Heat Pump System | 3 Heat 2 Cool Heat Pump System |
RC | Transformer power (cooling) | Transformer power (cooling) | Transformer power (cooling) |
RH | Transformer power (heating) | Transformer power (heating) | Transformer power (heating) |
C | Transformer common | Transformer common | Transformer common |
B | Energized in heating | Heat pump changeover valve energized in heating | Heat pump changeover valve energized in heating |
O | Energized in cooling | Heat pump changeover valve energized in cooling | Heat pump changeover valve energized in cooling |
G | Fan relay | Fan relay | Fan relay |
W/E | First stage of heat | First stage of emergency heat | First stage of emergency heat |
Y | First stage of cool | First stage of heat & cool | First stage of heat & cool |
Y2 | Second stage of cool | Second stage of cool | Second stage of cool & second stage of heat |
W2 | Second stage of heat | Auxiliary heat relay, second stage of heat | Auxiliary heat relay, third stage of heat |
H | Humidify | Humidify | Humidify |
D | Dehumidify | Dehumidify | Dehumidify |
Tech Setup Steps | LCD Will Show | Adjustment Options | Default | |
Filter Change Reminder | This feature will flash a reminder after the elapsed run time to remind the user to change the filter. A setting of “OFF” will disable this feature. | OFF
| You can adjust the filter change reminder from “OFF” to 2000 hours of fan runtime in 50 hour increments. | OFF |
Room Temperature Calibration | This feature allows the installer to change the calibration of the room temperature display. For example, if the thermostat reads 70˚ and you would like it to read 72˚ then select +2. | 0
CALIbRATE | You can adjust the room temperature display to read up to 4˚above or below the factory calibrated reading. | 0˚F |
Minimum Compressor On Time | This feature allows the installer to select the minimum run time for the compressor. For example, a setting of 4 will force the compressor to run for at least 4 minutes every time the compressor turns on, regardless of the room temperature. | OFF | You can set the minimum compressor run time to “OFF”, “3”, “4”, or “5” minutes. If 3,4 or 5 is selected, the compressor will run for at least the selected time before turning off. | OFF |
Tech Setup Steps | LCD Will Show | Adjustment Options Default | ||
Compressor Short Cycle Delay | The compressor short cycle delay protects the compressor from “short cycling”. This feature will not allow the compressor to be turned on for 5 minutes after it was last turned off. | ON OF CO | Selecting “ON” will not allow the compressor to be turned on for 5 minutes after the last time the compressor was on. Select “OF” to remove this delay. | ON |
Cooling Swing | The swing setting often called “cycle rate”, “differential” or “anticipation” is adjustable. A smaller swing setting will cause more frequent cycles and a larger swing setting will cause fewer cycles. | 0.5 dF
CO | The cooling swing setting is adjustable from 0.2˚ to 2˚. For example: A swing setting of 0.5˚ will turn the cooling on at approximately 0.5˚ above the setpoint and turn the cooling off at approximately 0.5˚ below the setpoint. | 0.5˚ |
Heating Swing | The swing setting often called “cycle rate”, “differential”, or “anticipation” is adjustable. A smaller swing setting will cause more frequent cycles and a larger swing setting will cause fewer cycles. | 0.5 dF
HE | The heating swing setting is adjustable from 0.2˚ to 2˚. For example: A swing setting of 0.5˚ will turn the heating on at approximately 0.5˚ below the setpoint and turn the heating off at 0.5˚ above the setpoint. | 0.4˚ |
Keypad Lockout | Keypad lockout allows you to configure the thermostat so that some or all of the keys don’t function. | PA | PA= partial keypad lockout, which locks all the keys except the or keys. FU= full keypad lockout, which locks out all the keys.
See Keypad Lockout Note | PA |
Tech Setup Steps | LCD Will Show | Adjustment Options | Default | |
Stages of Heat | You can configure the thermostat to operate a 3 stage heat pump system. 2H 2C = 2 heat, 2 cool 3H 2C = 3 heat, 2 cool This feature is shown only if the HEAT PUMP technician setup step is ON. | 2H2C
STAGE | Use the or key to change between 2 or 3 stages of heat. 2 heat will use Y1 as first stage and W2 as auxiliary. 3 heat will use Y1 as the first stage, Y2 as the second stage and W2 as the auxiliary. | 2 STAGES |
Note:
Up to four indoor temperature sensors can be connected to one thermostat. This allows for 5 sensing points (zones). For example: the local (thermostat) plus four indoor sensors enables 5 sensing points. To connect an indoor sensor to a thermostat, select 1 on the FINDING SENSOR technician setup step. Then hold down the light button on the indoor sensor until it beeps, while in ZONE technician setup step on the indoor sensor. To connect a second indoor sensor change the thermostat to read 2 and change the indoor sensor to zone 2. The zone setting must match between the thermostat and the indoor sensor to connect. When the connection is established the thermostat will show FOUND + NAME of the indoor sensor in the system information area of display.
Balance Point: The system operates differently when a balance point is used. On a dual fuel system, the balance point outdoor temperature setting will be the outdoor temperature at which the thermostat chooses either the heat pump or gas furnace. For example: A balance point setting of 30°F will turn on only the heat pump above 30°F and only the gas furnace below 30°F. Y1 will be stage one above 30°F and W2 will be stage one below 30°F. A heat pump with electric auciliary will energize the heat pump above and below balance point. The electric auxiliary will only energize below balance point. For Example: A balance point setting of 40°F, will turn on the heat pump above 40°F and turn on the heat pump and electric auxiliary below 40°F.
Follow the steps below to change your target humidity setpoint. Press the humidity button. Use the or button to select the target humidity setpoint. Press DONE when completed
Ambient Humidity Display
Ambient humidity will flash opposite the day and time, if the optional outdoor temperature sensor is installed the ambient outdoor temperature will also cycle in the display
The table on the right shows recommended indoor humidity levels in relation to outdoor temperatures during heating (adding humidity).
Set Time
All our programmable thermostats are shipped with an energy saving default program. You can customize this default program by following the instructions in the set program schedule section starting on page 34.
Programming
Your thermostat can be programmed to have each day of the week programmed uniquely (7 days), all the weekdays the same with a separate program for Saturday and a separate program for Sunday (5+1+1), or non-programmable. For the 7-day and 5+1+1 programming modes, there are three time period options.
Day of the Week | Events | Time | Setpoint Temperature (HEAT) | Setpoint Temperature (COOL) |
Weekday | Wake/OCC1 | |||
Leave/UNOCC1 | ||||
Return/OCC2 | ||||
Sleep/UNOCC2 | ||||
Occupied | ||||
Unoccupied | ||||
Saturday | Wake/OCC1 | |||
Leave/UNOCC1 | ||||
Return/OCC2 | ||||
Sleep/UNOCC2 | ||||
Occupied | ||||
Unoccupied | ||||
Sunday | Wake/OCC1 | |||
LeaveUNOCC1 | ||||
Return/OCC2 | ||||
Sleep/UNOCC2 | ||||
Occupied | ||||
Unoccupied |
Day of the Week | Events | Time | Setpoint Temperature (HEAT) | Setpoint Temperature (COOL) |
Weekday | Wake/OCC1 | 6 AM | 70˚F (21˚C) 75˚F (24˚C) | |
Leave/UNOCC1 | 8 AM | 62˚F (17˚C) 83˚F (28˚C) | ||
Return/OCC2 | 6 PM | 70˚F (21˚C) 75˚F (24˚C) | ||
Sleep/UNOCC2 | 10 PM | 62˚F (17˚C) 78˚F (26˚C) | ||
Saturday | Wake/OCC1 | 6 AM | 70˚F (21˚C) 75˚F (24˚C) | |
Leave/UNOCC1 | 8 AM | 62˚F (17˚C) 83˚F (28˚C) | ||
Return/OCC2 | 6 PM | 70˚F (21˚C) 75˚F (24˚C) | ||
Sleep/UNOCC2 | 10 PM | 62˚F (17˚C) 78˚F (26˚C) | ||
Sunday | Wake/OCC1 | 6 AM | 70˚F (21˚C) 75˚F (24˚C) | |
LeaveUNOCC1 | 8 AM | 62˚F (17˚C) 83˚F (28˚C) | ||
Return/OCC2 | 6 PM | 70˚F (21˚C) 75˚F (24˚C) | ||
Sleep/UNOCC2 | 10 PM | 62˚F (17˚C) 78˚F (26˚C) |
Day of the Week | Events | Time | Setpoint Temperature (HEAT) | Setpoint Temperature (COOL) |
Weekday | OCCUPIED | 8 AM | 70˚F (21˚C) 72˚F (22˚C) | |
UNOCCUPIED | 6 PM | 64˚F (18˚C) 80˚F (27˚C) | ||
Saturday | OCCUPIED | 8 AM | 70˚F (21˚C) 72˚F (22˚C) | |
UNOCCUPIED | 6 PM | 64˚F (18˚C) 80˚F (27˚C) | ||
Sunday | OCCUPIED | 8 AM | 70˚F (21˚C) 72˚F (22˚C) | |
UNOCCUPIED | 6 PM | 64˚F (18˚C) 80˚F (27˚C) |
Monday
Weekday::
vive
Download Manual:
Vive Comfort TP-S-955WH Non-Programmable Thermostat Installation Manual
OTHER MANUALS
Vive Comfort TP-S-955WH Non-Programmable Thermostat Operational Manual
Vive Comfort TP-S-955WH Non-Programmable Thermostat Installation Manual
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…