The VT7300 provides the advanced features and monitoring functions required by modern building automation systems without the use of software and commissioning tools. The VT7300 is a low-voltage fan coil terminal equipment controller suitable for commercial and hospitality markets. It can also be used as a zone controller or mixed voltage solution.
Parameter | Specification |
---|---|
Thermostat Power Requirements | |
VT7350 | 19 to 30 Vac; 50 or 60 Hz; 2 VA Class 2 |
VTR7350 | 7.0 Vdc +/- 10%, 2.4 W min. |
Operating Conditions | 0 to 50 °C (32 to 122 °F); 0 to 95% RH non-condensing |
Storage Conditions | -30 to 50 °C (-22 to 122 °F); 0 to 95% RH non-condensing |
Temperature Sensor | Local 10k NTC thermistor |
Resolution | ±0.1 °C (± 0.2 °F) |
Control Accuracy: Temperature | ±0.5 °C (±0.9 °F) @ 21 °C (70 °F) typical, calibrated |
Control Accuracy: Humidity | ±3% from 20 to 70% RH at 21 °C (70 °F) |
Setpoint Range Cooling | 12 to 38 °C (54 to 100 °F) |
Setpoint Range Heating | 4.5 to 32 °C (40 to 90 °F) |
Room and Outdoor Air Temperature Display | -40 to 50 °C (-40 to 122 °F) |
Proportional Band for Room Temperature Range Control | Cooling & Heating: 1.8 °C (3.2 °F) |
Binary Inputs | Dry contact across terminal BI1, BI2 & UI3 to Scom* |
Outputs Rating | Triac output: 30 Vac, 1 A max., 3 A in-rush; Analog: 0 to 10 Vdc into 2k Ω resistance min.* |
Economizer Analog Output Rating | 0 to 10 Vdc into 2k Ω resistance min. |
Economizer Analog Output Accuracy | ±3% typical |
Wire Gauge | 18 gauge maximum, 22 gauge recommended |
Dimensions | 4.94” x 3.38” x 1.13” |
Parameter | Specification |
---|---|
Approximate Shipping Weight | 0.75 lb (0.34 kg) |
Warranty | Limited Warranty: 2 years |
AGENCY APPROVALS
Part Number | Description | Communication Interface |
---|---|---|
VT7300F5031B-ECM | ECM FCU Room Controller: BACnet, 2 Analog 0-10V Outputs, Commercial Interface BACnet MS/TP | Commercial Interface BACnet MS/TP |
VT7305F5031B-ECM | ECM FCU Room Controller: BACnet, 2 Analog 0-10V Outputs, Hotel Interface BACnet MS/TP | Hotel Interface BACnet MS/TP |
VT7350C5031 | Fan Coil Controller: Net Ready, Floating Outputs, with Humidity, Commercial Interface Standalone | Commercial Interface Standalone |
VT7350C5031B | Fan Coil Controller: BACnet, Floating Outputs, with Humidity, Commercial Interface BACnet MS/TP | Commercial Interface BACnet MS/TP |
VT7350C5531B | PIR FCU Room Controller: 2 On/Off or Floating Outputs, with Humidity, Commercial Interface BACnet MS/TP | Commercial Interface BACnet MS/TP |
VT7350C5531E | PIR FCU Room Controller: 2 On/Off or Floating Outputs, with Humidity, Commercial Interface LonWorks | Commercial Interface LonWorks |
VT7350C5531P | PIR FCU Room Controller: 2 On/Off or Floating Outputs, with Humidity, Commercial Interface Zigbee Pro | Commercial Interface Zigbee Pro |
VT7350C5531W* | PIR FCU Room Controller: 2 On/Off or Floating Outputs, with Humidity, Commercial Interface Zigbee | Commercial Interface Zigbee |
VT7350F5031 | Fan Coil Controller: Net Ready, 2 Analog 0-10V Outputs, with Humidity Standalone | Standalone |
VT7350F5031B | Fan Coil Controller: BACnet, 2 Analog 0-10V Outputs, with Humidity BACnet MS/TP | Commercial Interface BACnet MS/TP |
VT7350F5531B | PIR FCU Room Controller: 2 Analog 0-10V Outputs, with Humidity, Commercial Interface BACnet MS/TP | Commercial Interface BACnet MS/TP |
VT7350F5531E | PIR FCU Room Controller: 2 Analog 0-10V Outputs, with Humidity, Commercial Interface LonWorks | Commercial Interface LonWorks |
VT7350F5531P | PIR FCU Room Controller: 2 Analog 0-10V Outputs, with Humidity, Commercial Interface Zigbee Pro | Commercial Interface Zigbee Pro |
VT7350F5531W* | PIR FCU Room Controller: 2 Analog 0-10V Outputs, with Humidity, Commercial Interface Zigbee | Commercial Interface Zigbee |
VT7355C5031 | Fan Coil Controller: Net Ready, Floating Outputs, with Humidity, Lodging/Hotel Interface Standalone | Lodging/Hotel Interface Standalone |
VT7355C5031B | Fan Coil Controller: BACnet, Floating Outputs, with Humidity, Lodging/Hotel Interface BACnet MS/TP | Lodging/Hotel Interface BACnet MS/TP |
VT7355C5531B | PIR FCU Room Controller: 2 On/Off or Floating Outputs, with Humidity, Lodging/Hotel Interface BACnet MS/TP | Lodging/Hotel Interface BACnet MS/TP |
VT7355C5531E | PIR FCU Room Controller: 2 On/Off or Floating Outputs, with Humidity, Lodging/Hotel Interface LonWorks | Lodging/Hotel Interface LonWorks |
VT7355C5531P | PIR FCU Room Controller: 2 On/Off or Floating Outputs, with Humidity, Lodging/Hotel Interface Zigbee Pro | Lodging/Hotel Interface Zigbee Pro |
VT7355C5531W* | PIR FCU Room Controller: 2 On/Off or Floating Outputs, with Humidity, Lodging/Hotel Interface Zigbee | Lodging/Hotel Interface Zigbee |
VTR7350A5031 | Fan Coil Controller: Net Ready, with Humidity, Commercial Interface Standalone | Commercial Interface Standalone |
VTR7350A5031B | Fan Coil Controller: BACnet, with Humidity, Commercial Interface BACnet MS/TP | Commercial Interface BACnet MS/TP |
VTR7350A5531B | PIR FCU Room Controller: with Humidity, Commercial Interface BACnet MS/TP | Commercial Interface BACnet MS/TP |
VTR7350A5531P | PIR FCU Room Controller: with Humidity, Commercial Interface Zigbee Pro | Commercial Interface Zigbee Pro |
VTR7350A5531W* | PIR FCU Room Controller: with Humidity, Commercial Interface Zigbee | Commercial Interface Zigbee |
VTR7355A5031 | Fan Coil Controller: Net Ready, with Humidity, Lodging/Hotel Interface Standalone | Lodging/Hotel Interface Standalone |
VTR7355A5031B | Fan Coil Controller: with Humidity, Lodging/Hotel Interface BACnet MS/TP | Lodging/Hotel Interface BACnet MS/TP |
VTR7355A5531B | PIR FCU Room Controller: with Humidity, Lodging/Hotel Interface BACnet MS/TP | Lodging/Hotel Interface BACnet MS/TP |
VTR7355A5531P | PIR FCU Room Controller: with Humidity, Lodging/Hotel Interface Zigbee Pro | Lodging/Hotel Interface Zigbee Pro |
VTR7355A5531W* | PIR FCU Room Controller: with Humidity, Lodging/Hotel Interface Zigbee | Lodging/Hotel Interface Zigbee |
*Wireless ‘W’ Zigbee models for replacement or existing projects only. See PN: VCM7000V5000W.
** I/O relay pack required for VTR7350.
Note: All models with PIR motion sensors and most models with communication modules must be purchased in two or three different parts. For example, VT7200F5531E should be ordered as: VT7200F5031 + COV-PIR-ZN-5031 + VCM7300V5000E.
© 2021 Viconics Technologies, Inc. All rights reserved.
sales.support@viconics.com
viconics.com
Download manuals:
Viconics VT7300 Room Temperature Control Thermostat Data Sheet
Other Manual:
Viconics VT7300 Room Temperature Control Thermostat Installation Guide
Viconics VT7300 Room Temperature Control Thermostat Data Sheet
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…