This section provides general descriptive and procedural information intended for typical daily operators of the thermostat.
Figure 36 describes the icons visible on the front of the thermostat.
Note: Except when the thermostat is powering up, when all of the icons are shown for 2 sec, only some of the icons will be visible at once.
If configured properly, both programmable and non-programmable thermostats will control HVAC equipment to maintain room temperature automatically
Non-programmable thermostats do not have timekeeping or scheduling capabilities.They will continue to maintain heating and/or cooling setpoints until an operator makes changes to the setup.Therefore, only the following tasks may be required performed:
Note: The system mode, temperature setpoints, and fan mode can each be individually locked to prevent users from changing them. If you see a on the display, you may need to unlock the setting before you change it (see “Locking or Unlocking Modes,” p. 40).
Changing the System Mode
Note: If you are unable to change the system mode, check the system type setting and the manual/auto changeover setting (see “Configuration,” p. 26) to verify that the thermostat is configured with heat and cool modes, and that it permits manually changing them.
Depending upon the model and system type, the thermostat can be set to one of five modes: Cooling, Heating, Emergency Heat, Auto, or Off.
Note: The 1-Heat/1-Cool thermostat does not have Emergency Heat mode.
To change the system mode:
To change the heating or cooling setpoint:
Note: If you are unable to see the fan mode, check the system type setting in the installation configuration options to make sure that it is specified as a system with a fan.
There are two fan modes. Each are indicated by an icon on the display:
To change the fan mode:
Programmable thermostats contain all of the functionality of non-programmable thermostats, but they also keep track of the date, day of the week, and time of day for scheduling purposes.
Programming
This section describes how to program the thermostat after it has been installed and configured.
Setting theTime
The time must be set in the thermostat to ensure operation of the schedule.
Note: The date is set during configuration and the day of the week is calculated automatically according to the date.
To set the time:
The thermostat can be configured for two periods (day and night) or four periods (morning, day, evening, and night).The chosen number of periods are applied to each day of the week when you program the thermostat. Each period can have a unique start time, heat setpoint, cool setpoint, and fan setting.
The groups of days can be one of the following:
Weekly Operating ScheduleWorksheet
To set the schedule:
After a programmable thermostat is configured and the schedule is programmed, the thermostat automatically changes the setpoints and fan settings according to the schedule.However, there are some operator tasks that you may need or want to perform:
Note: It is possible for a programmable thermostat to be configured to be a non-programmable thermostat. If installation configuration option #140 is set to 0, schedule programming capabilities will be absent.
Showing the Setpoint temperature on Display
Depending upon the value of configuration option #210, the large numeric display could show any of the following:
Figure 37. Display Options
Value of configuration option #210 | Numeric display options (press |
0 | The current local temperature, or the current or most recent temperature setpoint |
1 or 2 | The current local or remote indoor temperature or the current or most recent temperature setpoint |
3 | The current indoor temperature, the current or most recent temperature setpoint, or the current remote outdoor temperature, which only appears for 8 sec before reverting to current indoor temperature or setpoint |
To switch between the current temperature, “o dr” temperature, and the setpoint temperature, press and hold the
Timed Override (TOV) Mode
During normal operation, the thermostat controls the HVAC equipment according to the schedule that is programmed into it.To permanently change the temperature setpoint or fan setting, make the change in the programmed schedule (see “Scheduling,” p. 36). However, a timed override can be used to temporarily change the current settings without making any change to the schedule.
To start a temperature setpoint override:
Locking or Unlocking Modes
You can independently lock and unlock the system, fan, and schedule change modes. When a lock is activated, users cannot change the current mode or schedule settings. If you attempt to make a change,
To lock a mode:
To unlock a mode:
This section provides additional information that may be useful for understanding thermostat operation or programming.
Deadband
The thermostat automatically maintains a temperature deadband between the heating setpoint and the cooling setpoint whenever automatic changeover (heat-to-cool or cool-to-heat mode) is enabled.The temperature range of the deadband is 2–9 °F (1.0–4.5°C) and is specified in the installation configuration options (see “Configuration,” p. 26). If you attempt to change a temperature setpoint to within the deadband of its opposing setpoint, the opposing setpoint will automatically be pushed to the next value that satisfies the deadband. (See Figure 38.)
Heat and Cool Cycling Rate
The heat and cool cycling rate, expressed in cycles per hour (CPH) indicates how often heating or cooling system is turned on when temperature is within the temperature differential from the setpoint, which is 1°F (0.5°C).There are ten options (1–10) for heat stages and five options (1–5) for cool stages.The number selected is the maximum number of times the stage is cycled in 1 hr. For example, when the system is set to 5 CPH, it runs at 12 min cycles with variable duty cycle. Depending on the heating or cooling load, which is measured by feedback from the sensor thermistor and/or temperature error, the system could run at 50% duty cycle (6 min ON and 6 min OFF), 80% duty cycle (9.6 min ON and 2.4 min OFF), or other variations of the duty cycle.
Note: The cycling rate described above is only active when the temperature is within the temperature differential. If the temperature is outside of the temperature, the heating and cooling equipment will either be fully on or fully off accordingly. (See Figure 38.)
There is one cycling rate setting for each of the thermostat’s available heat and cool stages, including auxiliary and emergency heat stages.You can specify them during installation configuration. See “Configuration,” p. 26.
To protect the compressor from cycling too frequently, there is an automatic 5 min gap between cycles.You cannot reduce the gap, but you can add up to 5 min if needed. See “Configuration,” p. 26.
Configuration and Programming Retention
The thermostat retains the time and date for a minimum of 5 days with no electricity. If power is lost for more than 5 days, you will need to reset the time and date when power is restored. All configuration parameters, system settings, and scheduling are stored in non-volatile memory, which will retain the data indefinitely with or without power.
Note: You can manually revert to default settings by setting the appropriate installation parameter (#300 for programmable thermostats or #18 for non-programmable thermostats) to a value of 1, and exiting configuration mode.
Extended Fan-onTime (Heat or Cool)
Note: This feature applies only to the programmable thermostat.
When the thermostat fan is in Auto mode, the fan on time can be extended.
Compressor and Auxiliary Heat Lockout
Note: This feature applies only to the programmable thermostat.
Compressor and auxiliary heat is used for heat pump systems with more heat stages than cool stages. When the temperature from an outdoor sensor is:
Auxiliary Heat Control
Note: This feature applies only to the non-programmable 3-Heat/2-Cool thermostat.
You can set the auxiliary heat control using configuration option #17 to one of two settings:
Economizer/TOD
Note: This feature applies only to the programmable thermostat.
You can set the Economizer orTOD mode using configuration options #150 to one of two settings:
This section describes troubleshooting for the thermostat.
Error Codes
An error code indicates that technical assistance may be required.
Try cycling the power to the thermostat as a first method to clear the error. See Table 10 below and Table 12, p. 47 for additional information.
Note: On the display, error codes appear at the bottom of the display.
Note: On the programmable thermostat, the error code alternates with the time on the display.
Table 10. Error Codes
Code | Description |
E0 | Thermistor Error; occurs when the configured thermistor reading is out of range (less than 14°F (-9.9°C) or greater than 122°F (50°C). If this error occurs: • All Heat/Cool outputs turn off. • If the fan mode is Auto, the thermostat turns off the fan. • If the fan mode is On, the thermostat leaves the fan on. |
E3 | Permanent data error. Access error or checksum error is detected. |
E4 | Input voltage out of range – too low or too high. Input voltage is lower than 18Vac or higher than 34Vac. The error code display will remain on for 30 sec after the detection of out of range input voltage. |
E5 | RTC Error (this error can only appear on the programmable thermostat). |
E7 | Memory error (write and read 0x55 and 0xAA failed). Only checked during power up test. |
SystemTest Mode
You can run diagnostic tests on the thermostat to verify that the thermostat is functioning properly
and that the devices in the system are wired properly.
To enter system test mode:
WARNING
Live Electrical Components!
The circuit board is energized. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform this step. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
Table 11. SystemTest Descriptions
1H/1C Thermostat (p/n X13511535-01) | 3H/2C Thermostat (p/n X13511536-01) | Programmable Thermostat | Description | Values |
1(1) | 1 | 1 | Heating system | 0 = all heating stages off 1 = heat stage 1 on; heat stage 2 off 2 = heat stage 2 on; heat stage 1 off 3 = heat stage 1 and 2 on This setting remains active when you scroll to the next setting. |
2(1) | 2 | 2 | Cooling system | 0 = all cooling stages off 1 = cool stage 1 on; cool stage 2 off 2 = cool stage 2 on; cool stage 1 off 3 = cool stage 1 and 2 turn on This setting remains active when you scroll to the next setting. |
3 | 3 | 3 | Fan system | 0 = fan off 1 = fan on This setting remains active when you scroll to the next setting. |
NA | 4 | 4 | O/B changeover valve | 0 = changeover valve off 1 = changeover valve on This setting remains active when you scroll to the next setting. |
NA | NA | 5 | TOD/Economizer system | 0 = TOD/Economizer off 1 = TOD/Economizer on This setting remains active when you scroll to the next setting. |
NA | 5 | NA | Auxiliary Heat | 0 = Auxiliary heat and fan turns off 1 = Auxiliary heat and fan turns off This setting remains active when you scroll to the next setting. |
NA | 6 | NA | Emergency Heat | 0 = Emergency relay, fan, and terminal L output turn off 1 = Emergency relay, fan, and terminal L output turn on This setting remains active when you scroll to the next setting. |
5 | 8 | 6 | LCD segments | 0 = full segment on 1 = odd segments on; even segments off 2 = even segments on; odd segments offThis setting is deactivated when you scroll to the next setting. |
NA | NA | 7 | Remote thermistor (S1 & S2) temperature reading | 0 = show temperature reading in Fahrenheit 1 = show temperature reading in Celsius This setting is deactivated when you scroll to the next setting. |
4 | 7 | 8 | The internal thermistor temperature reading | 0 = show temperature reading in Fahrenheit 1 = show temperature reading in Celsius This setting is deactivated when you scroll to the next setting for the 3H/2C and programmable thermostats, but it remains active when you scroll to the next setting for the 1H/1C thermostat. |
6 | 9 | 9 | Major software version | Show major software revision number. This setting is deactivated when you scroll to the next setting. |
7 | 10 | 10 | Minor software version | Show minor software version. This setting is deactivated when you scroll to the next setting. |
8 | 11 | 11 | Power up test | 0 = do not run power up test on self-test exit 1 = run power up test on self-test exit This setting retained (and applied) upon exit from self-test mode. |
Use Table 12 to diagnose and solve problems you may encounter.
Table 12. Troubleshooting
Problem | Solution |
Error code E0 – Thermistor error. | • For non-programmable thermostats and programmable thermostats set to use internal temperature sensor (configuration option #210 set to 0, 1, or 2): Thermistor is defective or local temperature is out of range. Replace or repair thermostat through a qualified Trane supplier. • For programmable thermostats with configuration option #210 set to 3: Check the sensor terminals S1 and S2 for secure connection. If wires are securely connected, try replacing the sensor. |
Error code E4 – Input voltage out of range | • Check the input voltage to the thermostat. It must be within the range of 18Vac to 32 Vac rms. |
Error codes E3, E5, or E7 | • Cycle the power to the thermostat. • If it does not recover to normal operation, have it serviced or replaced by a qualified Trane supplier. |
Blank display | • Check the power supply. • If the power supply is ok, have the thermostat serviced or replaced by a qualified Trane supplier. |
Erratic display appearance or contrast | • Check the power supply. • Check the frequency configuration (Configuration option #210 for the programmable thermostat or #11 for non-programmable thermostats) to make sure that you are using the correct frequency setting for your power supply. • If the power supply and frequency setting are ok, have the thermostat serviced or replaced by a qualified Trane supplier. |
Buttons do not respond | • Make sure the thermostat modes are not locked. See “Locking or Unlocking Modes,” p. 40. • Cycle the power to the thermostat. • If the modes are not locked and cycling the power do not solve the problem, have the thermostat serviced or replaced by a qualified Trane supplier. |
“–F” or “–C” flashes | • Temperature is outside of the measurable range. The temperature reading should be correct when the temperature is within the measurable range. |
Fan settings are not visible | • Check the system status. If the status is Off, the fan settings will not appear. • Check the configuration options to verify that the fan is enabled: For programmable thermostats, check options 0130 and 0151; For non-programmable thermostats, check options 01 and 03. |
Programmable Thermostat | Non-Programmable Thermostats | |
Input power | 24Vac, 50Hz or 60Hz (18Vac to 32Vac) (Power supply frequency selected using installation configuration option #190) | 24Vac, 50Hz or 60Hz (18Vac to 32Vac) (Power supply frequency selected using installation configuration option #11) |
Wire size | 18 to 22 AWG | 18 to 22 AWG |
Output terminal ratings | 1A @ 30Vac | 1A@ 30Vac |
Indoor temperature display range | +15 to +122°F (–9.5 to +50°C) | +32 to +99°F (0 to +37°C) |
Outdoor (remote) temperature display range | –31 to +122°F (–35 to +50°C) | NA |
Storage temperature | –40 to +158°F (–40 to +70°C) | –40 to +158°F (–40 to +70°C) |
Accuracy | ±1.4°F (±0.8°C) over a range of 50 to 90 °F (10 to 32.2°C) | ±1.4°F (±0.8°C) over a range of 50 to 90 °F (10 to 32.2°C) |
Resolution | Configurable: 1.0°F, 0.5°F, 1°C, 0.5°C, 0.1°C | Configurable: 1.0°F, 0.5°F, 1°C, 0.5°C, 0.1°C |
Power consumption | < 1VA | < 1VA |
Housing materials and rating information | Polycarbonate/ABS blend, UV protected, UL 94-5VA flammability rating, suitable for application in a plenum. | Polycarbonate/ABS blend, UV protected, UL 94- 5VA flammability rating, suitable for application in a plenum. |
Mounting | 3.24 in (8.26 cm) for two mounting screws (supplied) | 3.24 in (8.26 cm) for two mounting screws (supplied) |
Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader in creating and sustaining safe, comfortable, and energy-efficient environments, Trane offers a broad portfolio of advanced controls and HVAC systems, comprehensive building services, and parts. For more information, visit www.Trane.com.
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.
© 2012 Trane. All rights reserved.
BAS-SVX36C-EN 13 Mar 2012
Supersedes BAS-SVX36B-EN 30 Sep 2010
DOWNLOAD MANUALS:
TRANE 1H1C(pn X13511535-01) Programmable Thermostats Operation MANUAL
OTHER MANUALS:
TRANE 1H/1C(p/n X13511535-01) Programmable Thermostats Installation MANUALS
TRANE 1H/1C(p/n X13511535-01) Programmable Thermostats Operation MANUAL
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…