The SunStat View model 500750 is designed to operate either a 120 VAC or 240 VAC resistance floor heating system. It comes with an easy setup wizard, a typical program ready to go, and a GFCI inside to meet safety needs.
Press anywhere on the display if the screen is blank. This wakes the display.
WARNING
Read this Manual BEFORE using this equipment.
Failure to read and follow all safety and use information can result in death, serious personal injury, property damage, or damage to the equipment.
Keep this Manual for future reference.
Installation must be performed by qualified personnel, in accordance with local codes and standards. A licensed electrician is recommended.
WARNING
As with any electrical product, care should be taken to guard against the potential risk of fire, electric shock, and injury to persons. The following must be observed:
Local building or electrical codes may require modifications to the information provided. You are required to consult the local building and electrical codes prior to installation. If this information is not consistent with local building or electrical codes, the local codes should be followed.
Unpack the thermostat control and make sure everything is in good condition.
Do not use a damaged control or part. The package comes with these items:
NOTICE
A single-gang extra-deep box allows sufficient space to connect 1 or 2 heating mats or cables. For 3 heating mats or cables, a 4-inch square extradeep electrical box with a single-gang “mud ring” is necessary. Alternately,a junction box may be installed to connect multiple heating mats or cables,then run power supply wire from the junction box to the control electrical box. See the Installation Instructions provided with the floor heating system for more details.
Locating the Control
Find a suitable location for the control. Consider the following:
Mounting the Electrical Box
WARNING
To prevent the risk of personal injury and/or death, make sure power is not applied to the product until it is fully installed and ready for final testing. All work must be done with power turned off to the circuit being worked on.
House Wiring
Pull power supply wiring to the control location. Consider the following:
Floor Sensor
TEMPERATURE | TYPICAL VALUES |
55°F (13°C) | 17 kΩ |
65°F (18°C) | 13 kΩ |
75°F (24°C) | 10 kΩ |
85°F (29°C) | 8 kΩ |
Power Leads from Heating Mat or Cable
Pull the power lead wires from the floor heating system into the control location.
Excess power lead wire may be cut off, but leave about 6 to 8 inches (15 to 20 cm) of wire for connections.
Removing the Thermostat Front Module
(see Figure 1 and 2)
Connect the wires as shown in the diagram. Consider the following:
Overview
On/Off and Reset
Pressing
Startup
When first powered on, the thermostat begins a “startup wizard” to help the user through basic setup.
GFCI Testing
The GFCI (Ground Fault Circuit Interrupter) in this control must be tested when installation is finished and once each month.
Adjusting the Temperature
Normally the thermostat will run automatically based on the settings in the Program Schedule. However, these settings may be overridden temporarily or for a specified period of time.
Temporary Adjustment
Hold a Setpoint Temperature
Vacation Hold
To quickly override the Program Schedule to a low setpoint while on vacation, press Settings
Customizing the Program Schedule
Table 2 – Settings
Setting | Options |
Vacation See the “Vacation Hold” section above. | Not adjustable |
Clean Screen Allows the screen to be cleaned without function for 30 seconds. IMPORTANT: Use a dry or damp soft cloth only to clean the screen. Do not spray the screen directly and do not use harsh solvents or abrasives as this may damage the screen and control. | Not adjustable |
Brightness Adjust the display brightness. | 1 to 10 |
Date/Time Set the time and date. This thermostat will automatically adjust the time for daylight savings. If you want this ability turned off, de-select the box “Adjust for Daylight Savings”. | |
Usage | 24 hours 7 days 30 days All time |
The thermostat stores in memory the number of hours that it is | |
heating. This information may be useful in calculating the energy | |
used by the floor heating system. To reset these counters to zero, | |
press Clear and confirm. | |
Language Change the language shown. | English, French, Spanish |
Format Format of clock and temperature. | 12 or 24-hour ᵒF or ᵒC |
Floor Limit | |
Minimum and maximum allowable setpoint temperatures of the floor sensor. This is useful when the floor covering cannot exceed a certain temperature (84°F is common for many wood | 40-99ᵒF (4.5-37ᵒC) |
or laminate products. |
Floor Limit Consult your floor covering manufacturer for recommended limits). It is also useful to limit adjustment by users. And it is useful if the thermostat is being operated in Air Sensing mode (see Sensor Regulation below) but it is still desired to maintain a minimum floor temperature regardless of the air temperature. | Default maximum: 99ᵒF (37ᵒC) Default minimum: 40ᵒF (4.5ᵒC) |
Sensor Regulation The thermostat is designed to operate best in Floor Sensing mode. It is also possible to operate in Air Sensing mode with Floor Sensing limitation. However, make sure to set a proper maximum Floor Limit temperature (see Floor Limit above) to avoid overheating certain floor coverings. Also note that internal heating in the thermostat may affect the air sensor temperature reading. | Floor Sensor Air Sensor
Default:Floor Sensor |
Calibration Under special circumstances, it may be desired to slightly adjust the temperature that is displayed for the sensor. Normally this is not recommended. The display will show the current sensor temperature and the offset. | ±9ᵒF (±5ᵒC) |
SmartStart Allows the thermostat to learn and automatically determine the best time to begin heating, reaching the setpoint temperature at the scheduled time. For example, the schedule may have a “WAKE” start time of 6:00 AM to be 82ᵒF (27.8ᵒC) and SmartStart may begin pre-heating at 5:30 AM to reach 82ᵒF by 6:00 AM. It will take a few days to learn. | ON OFF
Default: ON |
Factory Settings Use with caution! This will clear all programming and settings to factory condition. This is useful if there are problems or errors which cannot be corrected. |
If problems arise with the thermostat, please consult this troubleshooting guide. If not qualified to perform electrical work, it is highly recommended a qualified, licensed electrician be hired. Any electrical troubleshooting work should be performed with the power removed from the circuit, unless otherwise noted. Although this troubleshooting guide is provided to assist with problems experienced with a system, results are never guaranteed. Watts Radiant does not assume any liability or responsibility for damage or injury that may occur from using this guide. If problems with the system persist, call the manufacturer.
Insert the ends of the floor sensor wire into the terminals marked “SENSOR” and snug the screws. It does not matter which wire goes into which terminal.
Problem | Display | Solution |
The following are common issues and solutions. A more complete list and more solutions are on the manufacturer website. | ||
No heat | GFCI TRIP | Reset by turning thermostat off/on. Reset by turning circuit breaker off/on. Electrician: Check for loose wire connections at breaker and junctions. Check for short-circuit to ground on heating system. |
No heat | HEATING | Allow sufficient time. Verify floor is insulated. Electrician: Check for correct resistance between heating system power lead wires. Check for correct voltage supplied to heating system. Check for correct amps drawn by heating system. |
No display | None | Reset circuit breaker. Check contacts between Power Module and Front Module and clean with alcohol wipe. Electrician: Check for loose wire connections at circuit breaker and junctions. Check for correct voltage between LINE1 and LINE2. |
Heating occurs at the wrong times | HEATING | Check that the current time and schedule times are properly set to AM or PM. On uninsulated concrete slab floors the SmartStart feature may start heating very early. You may turn this feature off if not desired. |
No heat | FLOOR LIMIT | Check Floor Limit values (see Table 3). |
No heat | 95°F or higher | Electrician: Check to make sure only one Floor Sensor is attached. |
Error Codes: An error code may display due to a power glitch or other false issue. Always: 1. Try clearing the Error code once by turning the thermostat off, resetting the circuit breaker, and then turning the thermostat back on. 2. Check the contacts between Power Base and Front Module for dirt or damage. Turn the circuit breaker off and remove the Front Module. Are the contacts bent or dirty? Try gently cleaning them with a rubbing alcohol wipe. Dirt or oil may have contaminated them during installation. In most locations this step may be performed without an electrician since there is no power available. 3. Check that the Mounting Screws are not too tight causing distortion. Turn the circuit breaker off and remove the Front Module. Back the screws out until the Power Base is just snug to the wall. 4. Check that both clips at the top are engaged and that the screw at the bottom is snug. If these actions and the following do not resolve the issue, turn off the circuit breaker and contact the manufacturer for direction. Do not continue using the system to prevent further risk of damage, fire, or electrical shock. |
No heat | Err1 | Floor Sensor may be wrong type. Electrician: Check floor sensor resistance. See Table 1 in the Installation section above. |
No heat | Err2 | Floor Sensor wires may be crossed. Electrician: Check if the Floor Sensor wires crossed and short- circuited. Check Floor Sensor resistance (see Table 1 in the Installation section above). |
No heat |
Err3 | Floor Sensor wires may not be connected. Check Floor Sensor connections and mounting screws as stated above. Electrician: Check if Floor Sensor is attached. If not, attach and reset the circuit breaker. |
No heat | Err4 or Err5 and Air | Internal air sensor may be faulty. Change setting to Floor Sensing mode (see Table 3 above). |
No heat | Err6 | Internal temperature limit may be exceeded. Check if sunlight or other heat source is causing added heat to thermostat. Electrician: Check if load exceeds 15 amps. |
No heat | Err7 | Contacts or internal connections may be faulty. Check connections and mounting screws as stated above. Reset circuit breaker. |
No heat | Err8 | Internal device error. |
Power Supply | 120 / 240 VAC, 50/60 Hz |
Maximum Load | 15 A, resistive |
Maximum Power | 1800 W at 120 VAC / 3600 W at 240 VAC |
GFCI | Class A (5 mA trip nominal) |
Display Range | 32ᵒF to 99ᵒF (0ᵒC to 37ᵒC) |
Setting Range | 40ᵒF to 99ᵒF (4ᵒC to 37ᵒC) |
Accuracy | ± 0.9ᵒF (0.5ᵒC) |
Environment | Indoor dry location only |
Storage Temperature | 0ᵒF to 120ᵒF (-17ᵒC to 49ᵒC) |
Floor Sensor | Thermistor, 10k NTC type, double insulated, Class2 |
Memory | Programming retained indefinitely. Current time/day will need reset if power is lost more than 30 minutes. |
ETL Listing | Control No. 3037530. Conforms to UL 873, UL 943, CSA C22.2 No. 24, CSA/CAN C22.2 No. 144. |
Watts Radiant warrants this control (the product) to be free from defect in material and workmanship for a period of (3) years from the date of original purchase from authorized dealers. During this period, Watts Radiant will replace the product or refund the original cost of the product at Watts Radiant’s option,without charge, if the product is proven defective in normal use. Please return the control to your distributor to begin the warranty process.
This limited warranty does not cover shipping costs. Nor does it cover a product subjected to misuse or accidental damage. This warranty does not cover the cost of installation, diagnosis, removal or reinstallation, or any material costs or loss of use.
This limited warranty is in lieu of all other warranties, obligations, or liabilities expressed or implied by the company. In no event shall Watts Radiant be liable for consequential or incidental damages resulting from the installation of this product.
Some states or provinces do not allow limitations on how long an implied warranty lasts, or the exclusion or limitation of incidental or consequential damages, so the above exclusions or limitations may not apply to you. This warranty gives you specific legal rights and you may also have other rights that vary from state to state.
WARNING: This product contains chemicals known to the State of California to cause cancer and birth defects or other reproductive harm. For more information: www.watts.com/prop65
A Watts Water Technologies Company
USA: Springfi eld, MO • Tel. (800) 276-2419 •
Fax: (417) 864-8161 • www.wattsradiant.com
Download Manual
SunTouch SUNSTAT VIEW 500750 Installation and Operation Manual
OTHER MANUAL
SunTouch SUNSTAT VIEW 500750 Product Specification Guide
SunTouch SUNSTAT VIEW 500750 Thermostat Installation and Operation Manual
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…