CAUTION
Follow the Installation Instructions before proceeding. Set the thermostat mode to “OFF” prior to changing settings in setup or restoring Factory Defaults.
This Source 1 thermostat has the ability to receive updates to its firmware. Periodically firmware updates are released by the manufacturer to add features and/or performance enhancements. This manual was produced reflecting the most current firmware/feature set at the time of publication, firmware rev. 12. Firmware releases after rev. 12 may not be adequately depicted in this manual. Please refer to the appropriate website or contact your place of purchase to learn about changes to the thermostat after firmware release 12.
During Setup and Programming:
Setting the Clock and Day
Selecting the Heat or Cool Mode
AUTO-CHANGEOVER MODE— Pressing the WARMER or COOLER buttons in Auto mode will adjust both the heat and cool setpoints simultaneously. Toadjust heat and cool setpoints individually, choose HEAT mode to adjust the heat setpoint and COOL mode to adjust the cool setpoint, then return to AUTO mode.
HEAT OR COOL MODE—Pressing the WARMER or COOLER buttons in Heat or Cool mode will adjust only the heat or cool setpoints individually displayed.
Using the Fan Button FAN ON indicates constant fan operation. Pressing the FAN button toggles this feature. If you don’t see FAN ON, the fan is in auto mode and will only turn on during a heat or cool demand.
Viewing the Temperature Sensors
Press ACCESSRY STATUS to view the current values of optional outdoor and remote/supply temperature sensors. If connected to a Skyport® account, the temperature for the location you set up in the account will be shown if you don’t have a wired sensor connected. The high/low outdoor temperature will also be shown (resets at midnight). Press MODE to move between sensors and enter the actual Wi-Fi accessory status section. Setup step #44 selects the use of the wired temperature sensor. Press ACCESSRY STATUS again to return to the main screen.
Viewing the Indoor Humidity Sensor
Press the HUMIDITY button, then the mode button to display the current humidity measured at the thermostat. The room’s relative humidity is displayed in the top left corner. The humidification setpoint appears in the larger, center display and can be adjusted using the WARMER or COOLER buttons. Press the MODE button again to view and adjust the dehumidification setpoints. Press the HUMIDITY or MODE button again to confirm settings and return to normal operation.
Wire Connections
If the terminal designations on your old thermostat do not match those on the new thermostat, see the chart below or the wiring diagrams that follow.
Wire from the old thermostat terminal marked | Function | Install on the new thermostat connector marked |
G or F | Fan | G |
Y1, Y | Cooling | Y1 |
W1, W | Heating | W1/0/B |
Rh, R, M, Vr, A | Power | R |
C | Common | C |
O/B | Rev. Valve | W1/O/B* |
W2 | 2nd Stage Heat | W2 |
Y2 | 2nd Stage Cooling | Y2 |
W3 | 3rd Stage Heat | W3 |
H, Hum | Humidity | HUM |
D, Dehum | Dehumidity | DEHUM |
Ck1 | Dry Contact Switch | DRY CONTACT |
CKGND | Dry Contact Switch | DRY CONTACT |
To remove the thermostat backplate: Gently separate the display from the base by pulling first from one side, then the other until the two pieces unsnap.
Check Dip Switches
Ensure which switch is correct for your system. Dip switches are located on the back of the thermostat
When GAS/EL or HP is set for GAS/EL:
This switch (GAS or ELEC) controls how the thermostat will control the Fan (G) terminal in heating mode. When GAS is chosen, the thermostat will not energize the Fan (G) terminal in heating. When ELEC is chosen, the thermostat will energize the fan in heating.
When GAS/EL or HP is set for HP:
This switch (GAS or ELEC) defines the Aux Heat type. When GAS is chosen, the auxiliary heat will not be allowed to run during heat pump operation. When using a Dual Fuel system, set this switch for GAS. When ELEC is chosen, up to two stages of auxiliary strip heat will be allowed to run.
For Heat Pump Only
Sample Wiring Diagrams
Conventional Heating and Cooling Systems
Heat Pump Systems
Humidification or Dehumidification
Dry Contact and Aux Output
Test Operation
How to Change Settings in the Setup Screens
To enter Advanced Setup, press the SETUP button, then press MODE. Use the WARMER or COOLER buttons to adjust the value of your selection. Press MODE to advance to the next setup step. Press SETUP again to leave the setup screens
Backlight
Backlight Intensity Level (setup step 4)
The backlight can be adjusted between Off and seven levels of brightness.
Night Dimmer (setup step 5) –
Selecting On allows for automatic dimming of the display at night.
Night Dimmer Brightness (setup step 6)
OFF through seven levels of brightness.
Night Dimmer Start Time (setup step 7) – 12:00 am to 12:00 am
Night Dimmer Stop Time (setup step 8) – 12:00 am to 12:00 am
Language (setup step 20)
Scrolling Display Method (setup step 21)
This option allows the user to choose how the scrolling text is displayed. Options are:
Press the SETUP button, then press MODE repeatedly until the Scrolling Method setup step appears. Use the WARMER or COOLER buttons to make selection. Press MODE to advance to the next step. Press SETUP to leave the setup screens
Example of “Whole Words Centered”:
Holiday
The Holiday feature allows the thermostat to use temporary, energy saving settings without having to change regular programming. Holiday setup/programming at the local thermostat is limited to the number of days employing Holiday settings. When the optional Wi-Fi module is detected in the thermostat, local Holiday programming at the thermostat of the Holiday setup is not allowed. In this case Holiday setup and programming is accomplished with the Skyport Web App. Skyport gives the user extensive control over Holiday settings. Press the HOLIDAY button to enter Holiday programming (no Wi-Fi Module detected). If there is not a Holiday period active: Use the WARMER and COOLER buttons to choose the number of days desired to run the Holiday feature. To confirm your setting press the HOLIDAY button again. When the thermostat is programmed for Holiday operation, and the thermostat is in the Program On mode (running an Occupied/Unoccupied time period schedule), Holiday settings will take effect at 12:00AM of the next day. The thermostat will use the unoccupied mode and setpoints (see page 25) during the holidays. If the Holiday button is pressed during an active Holiday period: The active Holiday period may be cancelled by pressing the Mode button
Emergency Heat
The Emergency Heat function is only available if your thermostat is set to control a Heat Pump. To initiate the Emergency Heat feature, Press the EMERGCY HEAT button. During Emergency Heat operation the thermostat will turn on the fan and auxiliary stages of heat when there is a demand for heat. The compressor used for heating and all stages of cooling will be unavailable. To exit Emergency Heat, press the EMERGCY HEAT button.
Wireless Module
The ACCESSORY STATUS button allows the user to view the status of wired and wireless accessories. For many of the wireless devices this status includes: Battery Level, Signal Strength, and Last Time Updated. If there is an optional wireless module installed, the ACCESSORY SETUP button allows the user to link or connect wireless devices to the thermostat, or the thermostat to the network
Wi-Fi Module
Please follow the instructions included with the Wi-Fi module to connect to an Access Point or view status. The general instructions are below.
Wi-Fi Module
If the is present on the display then the thermosat is connected to the Wi-Fi Access Point. If just the “dot” of this icon appears, then just the Wi-Fi module is recognized. Press the ACCESSORY STATUS button, until you see the scrolling message starting with, PRESS THE WARMER. After that, press WARMER to view the Wi-Fi status/settings or press COOLER to view connected Wi-Fi sensors. Press the MODE button to step through the connected sensors or the Wi-Fi status screens listed below.
These setup steps allow the user to monitor equipment runtimes and program service alerts. Service alerts are displayed in the scrolling marquee
Heating and Cooling System Runtime – Energy Watch
UV Lamp Runtime
Humidifier Runtime
Selecting Your Time Period Schedule (setup step 1)
This thermostat may be configured to be programmable or non programmable.
Selecting Your Available Modes (setup step 2)
Programming a Daily Time Period Schedule* *not available when Wi-Fi module is present
Program Button
This thermostat features four programmable time periods per 24 hour day: Morning, Day, Evening, and Night. The start time for each time period is adjustable. The stop time for each time period is the start time for the next period. Each time period, or day part may be individually disabled.
The choices are: Off, Heat only, Cool only and AUTO changeover.
The following steps determine when the Occupied period(s) will be active.
Minutes of Fan Purge (setup step 38) When this feature is activated, the fan will turn on during an unoccupied period at a preset amount of time prior to Occupied 1. This preoccupancy fan purge timer may be set from zero to three hours, in 15 minute increments. Zero means this feature is turned off.
Fan Off Delay in Seconds (setup step 39) This feature allows the user to increase the cooling or electric strip heating efficiency of the system. The thermostat may be programmed to continue running the fan after a call for cooling or electric strip heating has been satisfied. This delay can be set for 0, 30, 60, 90, or 120 seconds. If set to 0, the fan will not run after a call for cooling or electric strip heating has been satisfied.
Comfort Recovery (setup step 41) With Comfort Recovery on, the thermostat will attempt to reach the Occupied 1 setpoint temperature at the exact time programmed into the thermostat. Comfort Recovery, only works when the thermostat enters the Occupied mode from the Unoccupied mode. For example, if the Occupied program is set for 6am at 72°F heating and 75°F cooling, the thermostat will turn the system on before 6am in an effort to bring the temperature to its correct setting at exactly 6am. The thermostat learns from experience, so please allow 4-8 days after a program change or after initial installation to give Comfort Recovery time to adjust. If used with a heat pump, electric strip heat will be disabled while Comfort Recovery is active.
CONDENSATE PAN – If CONDENSATE PAN is selected when the dry contact is active, the thermostat will lockout the compressor terminal(s) and “CONDENSATE PAN OVERFLOW” will appear on the display.
OCCUPIED – If OCCUPIED is selected, when the dry contact is active, the thermostat will be forced into the programmed occupied mode / setpoints and the ‘occupied’ icon will blink. This setting is useful for allowing a twist timer to force occupied settings. FDD – If FDD is selected when the dry contact is active, “EQUIPMENT FAULT” will appear on the display.
HOLIDAY – If HOLIDAY is selected, when the dry contact is active, the thermostat will be forced into the programmed unoccupied mode/setpoints and the ‘unoccupied’ icon will blink.
DOOR SWITCH – If DOORSWITCH is selected, when the dry contact is active for more than 3 minutes, the thermostat set points will switch to OF (off), the equipment will turn off, and DOOR OPEN will appear on the display.
Control To Temp Source (setup step 45)
This feature allows the user to specify which temperature sensor source(s) to be used to measure room temperature for control
The thermostat is equipped with a programmable auxiliary output. This output can be configured to be controlled from a variety of sources.
Aux Output Polarity (setup step 66)
Specifies if the Auxiliary output will be Open (Normally Open) or Closed (Normally Closed).
Aux Output (setup step 67)
Specifies which source will control the Aux output.
Choices are:
Auxiliary Output Programming By Time
If TIME is selected for the Aux Output, the following setup steps will appear:
Auxiliary Output Programming By Temp
If TEMP is selected for the Aux Output, the following setup steps will appear:
Aux Output Temp Source (Setup step 73) – Specifies what temperature source will be monitored for controlling the programmable output.
The options are:
Aux Output Trigger Point Temp
Specifies the temperature from the above selected source above which the Aux Output is triggered. A non-adjustable two degree deadband is applied to avoid frequent triggering. The ‘N.O.’ (Normally Open) or ‘N.C.’ (Normally Closed) function (Setup Step 66) can be altered to make the output trigger below the set temperature. Temps are adjustable from 0 – 120 degrees Fahrenheit.
Press Fan To Clear All Messages
This feature allows the user to clear all current error messages from the display.
Source 1 thermostats support the handling of specific signals from the utility provider. The utility generated signals carry pricing information and/or setback actions that alter the comfort settings of the thermostat in order to reduce energy usage on demand. This is known as Automated Demand Response or ADR for short. You must register to participate in a utility sponsored program, if offered by your local utility, to take advantage of this feature.
Skyport Cloud Services
From the web application the user will select Thermostat Settings from the left column. Then the Demand Response button is selected
Automated Demand Response
The Demand Response configuration page, shown below, is where the thermostat is configured to respond to the energy provider’s signals. It also sets operational parameters for the thermostat. The left column of the ADR configuration page allows or prevents access by the utility. Here communication with the utility and your thermostat may be turned On or Off.
Selecting the Overview tab of the ADR page will cause a summary of ADR events to be displayed
ADR (Setup step 85)
Controls whether you want the thermostat to possibly respond to signals from the utility provider. Select ON to allow this and to have steps 86-92 appear.
ADR Action (Setup step 86)
Allows the user to determine what action is taken when an ADR event is received.
Observe Setpoint Offsets – will offset the heat and cool setpoints by the amounts specified in setup steps 91 and 92
Observe Static Setpoints – will set the heat and cool setpoints to the values specified in setup steps 89 and 90
Event Min Heat Setpoint (Setup step 88)
Specifies the range of allowable setpoint adjustments to be enforced when any ADR signal has been received from the utility. Since you might be paying more for energy while an event is active, you can impose tighter limits on setpoint ranges that are only enforced during the event.
Static Cool Setpoint (Setup step 89)
Specifies the setpoints that will come into use during an event when the ADR ACTION is set to OBSERVE STATIC SETPOINTS
Heat Setpoint Offset (setup step 92)
Specifies how much the current setpoints in effect prior to an event will be altered during an event when the ADR ACTION is set to OBSERVE SETPOINT OFFSETS. The heat setpoint can be automatically lowered by -1 to -10 degrees while the cool setpoint can be automatically raised by 1 to 10 degrees.
DISPLAY INDICATIONS WHEN AN ADR EVENT IS HAPPENING
After setting your desired values for use during an ADR event, the scrolling display will give a little information when an event is pending or active. For instance, when an ADR event has been sent to your thermostat, you might see ADR STARTS at 4:15 to notify you of a pending event. Once active, you might see ADR STOPS at 5:30. When an event is active, you can press any of COOLER, WARMER or MODE buttons, followed by the WARMER to opt out of the event.
To prevent unauthorized use of the thermostat, the front panel buttons may be disabled. To disable, or ‘lock’ the keypad, press and hold the MODE button. While holding the MODE button, press the WARMER and COOLER buttons together. The
Resetting the Thermostat to the Factory Default Settings (for default values see page 43-45)
If, for any reason, you desire to return all the stored settings back to the factory default settings, follow the instructions below.
To enter Technician Setup, press and hold the SETUP button for 10 seconds. After all the icons appear, press MODE. The version number of the thermostat will appear in the scrolling text. Press MODE to advance to the next step. Use the WARMER or COOLER buttons to adjust the value of your selection. To leave Technician Setup, press SETUP
Technician Setup contains the following options:
Advanced Setup Table
Step# Description | Pg# | Range | Df | |
1 | Prog Mode | 25 | Non, 1 Day, 5/2 Day, 7 Day | 7 |
2 | Available Modes | 25 | Heat/Cool/Auto/Off, Heat/Cool /Off, Heat/Off, Cool/Off | Heat/Cool/ Auto/Off |
3 | Backlight | 17 | On, Off | Off |
4 | Backlight Level | 17 | Off thru 7 levels of brightness | Level 5 |
5 | Night Dimmer | 17 | On/Off | Off |
6 | Night Dimmer Brightness | 17 | Off thru 7 levels of brightness | 2 (20%) |
7 | Night Dimmer Start Time | 17 | 12A-12A | 8:00P |
8 | Night Dimmer Stop Time | 17 | 12A-12A | 6:00A |
9 | Current Service Filter Runtime Hours | 21 | 0-1999 Hours | 0 |
10 | Current Service Filter Calendar Days | 21 | 0-720 Days | 0 |
11 | Current Heat Runtime Hours | 22 | 0-1999 Hours | 0 |
12 | Current Aux Heat Runtime Hours | 22 | 0-1999 Hours | 0 |
13 | Current Cool Runtime Hours | 22 | 0-1999 Hours | 0 |
14 | Current UV Lamp Calendar Days | 22 | 0-720 Days | 0 |
15 | Current Humidifier Calendar Days | 22 | 0-720 Days | 0 |
16 | Set Service Filter Runtime Hours | 21 | 0-1950 hours | 0 |
17 | Set Service Filter Calendar Days | 21 | 0-720 Days | 0 |
18 | Set UV Lamp Calendar Days | 22 | 0-720 Days | 0 |
19 | Set Humidifier Calendar Days | 22 | 0-720 Days | 0 |
20 | Language | 17 | English, Espanol, Francais | English |
21 | Scrolling Method | 18 | “L-R Slow, L-R Fast, Word L-R Slow, Word L-R Fast, Whole Word L Slow, Whole Word R Slow, Whole Word Ctr. Fast, Whole Word Ctr. Slow” | “Whole Words Center Fast” |
22 | Setpoint Limits | 26 | No, Use | No |
23 | Max Heat Setpoint | 26 | 35 – 99 Degrees | 74 |
24 | Min Cool Setpoint | 26 | 35 – 99 Degrees | 70 |
25 | Cycles Per Hour | 26 | No Limit, 2, 3, 4, 5, 6 | 6 |
26 | Compressor Minimum Off Minutes | 26 | 0, 3, 5 Minutes | 5 |
27 | Min. Heat/Cool Setpoint Difference | 26 | 0 – 6 Degrees | 2 |
28 | Number of Heat Stages | 26 | 0 – 3 | 2 |
29 | Number of Cool Stages | 26 | 0 – 2 | 1 |
30 | Number Of Compressor Stages | 26 | 1, 2 | 1 |
31 | Number of Aux Stages | 26 | 0, 1, 2 | 0 |
32 | 1st Stage Deadband | 27 | 1 – 6 Degrees | 2 |
33 | 2nd Stage Deadband | 27 | 0 – 10 Degrees | 2 |
34 | 3rd Stage Deadband | 27 | 0 – 10 Degrees | 2 |
35 | 4th Stage Deadband | 27 | 0 – 10 Degrees | 2 |
Step# Description | Pg# | Range | Df | |
36 | Minutes Between 1st and 2nd Stage | 27 | 0 – 60 Minutes | 2 |
37 | Minutes Between 2nd and 3rd Stage | 27 | 0 – 60 Minutes | 2 |
38 | Minutes Between 3rd and 4th Stage | 27 | 0 – 60 Minutes | 2 |
39 | 2nd StageTurnoff Point | 27 | Deadband, Setpoint | Deadband |
40 | 3rd StageTurnoff Point | 27 | Deadband, Setpoint | Deadband |
41 | 4th Stage Turnoff Point | 27 | Deadband, Setpoint | Deadband |
42 | Fan Program | 28 | On, Off | Off |
43 | Minutes of Fan Runtime | 28 | 0-60 | 0 |
44 | Fan Program Start Time | 28 | 12:00A – 12:00A | 7:00A |
45 | Fan Program Stop Time | 28 | 12:00A – 12:00A | 9:00A |
46 | Wired Sensor Type | 28 | Remote, Supply | Remote |
47 | Control to Temp Source | 31 | Thermostat, Wired Remote*, Wireless Remote, Average of Wireless Remotes, Average Thermostat and Wired Remote*, Average All Sensors. *Option only if prior step = “Remote” | Thermostat |
48 | Wireless Remote to Use | 31 | list of wifi sensors currently linked to thermostat. * This step only appears if prior step = “Wireless Remote” | first linked sensor in list |
49 | Humidity Only With Heat | 29 | On, Off | Off |
50 | Fan With Humidity Demand | 29 | Fan On, Fan Off | Fan Off |
51 | Fan With Dehumidify Demand | 29 | Fan On, Fan Off | Fan Off |
52 | Humidity Setpoints | 29 | Auto, Manual | Manual |
53 | Cool To Dehumidify | 29 | On, Off | Off |
54 | Maximum Dehum Overcool | 29 | 0 – 20 Degrees | 2 |
55 | Reheat Operation W/Cool To Dehum. | 29 | On, Off | Off |
56 | Lockout Heatpump with Outdoor Temp | 30 | On, Off | Off |
57 | Lockout Temp | 30 | 0 – 75 Degrees | 35 |
58 | Lockout Aux Heat with Outdoor Temp | 30 | On, Off | Off |
59 | Aux Heat Lockout Temp | 30 | 20 – 75 Degrees | 75 |
60 | Dualfuel | 30 | On, Off | Off |
61 | Dualfuel Changeover on Outdoor Temp | 31 | On, Off | Off |
62 | Dualfuel Balance Point | 31 | 0 – 60 Degrees | 35 |
63 | Dualfuel Changeover Delay in Seconds | 31 | 0 – 90 Seconds | 30 |
64 | Fan Off Delay | 28 | 0 – 120 Seconds | 0 |
65 | F/C | 31 | Fahrenheit (F), Celsius (C) | F |
66 | Aux Output Polarity | 32 | Open, Closed | Open |
Step# Description | Pg# | Range | Df | |
67 | Aux Output | 32 | Time, Temp, External, Free Cooling, Venting | Time |
68 | Aux Output Program Days | 32 | 1 Day, 5/2 Day, 7 Day | 1 |
69 | Day Of Week To Program | 32 | Sunday – Monday (S – M) | MTWTFSS |
70 | Aux Output Start Time | 32 | 12am – 12am | 7am |
71 | Aux Output Stop Time | 32 | 12am – 12am | 9pm |
72 | Copy | 32 | Yes, No | No |
73 | Aux Output Temp Source | 33 | Thermostat, Outdoor, Remote, External | Remote |
74 | Aux Output Trigger Point Temp | 33 | 0 – 120 Degrees | 65 |
75 | Free Cooling with A/C | 34 | With A/C, Without A/C | With A/C |
76 | Free Cooling Usuable Temp | 34 | 40 – 80 Degrees | 65 |
77 | Comfort Recovery | 28 | On, Off | Off |
78 | Dry Contact Polarity | 34 | Open, Closed | Open |
79 | Dry Contact Use | 34 | Condensate, Vacation, FDD | Vacation |
80 | Humidity Polarity | 29 | Open, Closed | Open |
81 | Dehumidify Polarity | 29 | Open, Closed | Open |
82 | Dehumidify only with Cooling | 29 | On, Off | On |
83 | Skyport | 33 | On, Off | On |
84 | Local API | 33 | On, Off | Off |
85 | ADR | 38 | On, Off | On |
86 | ADR Action | 38 | Observe Setpoint Offset, Observe Static Setpoints | Observe SP Offsets |
87 | Event Max Cool Setpoint | 38 | 65 – 90 | 90 |
88 | Event Min Heat Setpoint | 38 | 50 – 85 | 50 |
89 | Static Cool Setpoint | 38 | 65 – 85 | 82 |
90 | Static Heat Setpoint | 38 | 65 – 85 | 60 |
91 | Cool Setpoint Offset | 39 | 1 to 10 | 4 |
92 | Heat Setpoint Offset | 39 | -1 to -10 | -4 |
93 | Press Fan To Clear All Messages | 33 |
One-Year Warranty – This Product is warranted to be free from defects in material and workmanship. If it appears within one year from the date of original installation, whether or not actual use begins on that date, that the product does not meet this warranty, a new or remanufactured part, at the manufacturer’s sole option to replace any defective part, will be provided without charge for the part itself provided the defective part is returned to the distributor through a qualified servicing dealer. THIS WARRANTY DOES NOT INCLUDE LABOR OR OTHER COSTS incurred for diagnosing, repairing, removing, installing, shipping, servicing or handling of either defective parts or replacement parts. Such costs may be covered by a separate warranty provided by the installer. THIS WARRANTY APPLIES ONLY TO PRODUCTS IN THEIR ORIGINAL INSTALLATION LOCATION AND BECOMES VOID UPON REINSTALLATION. LIMITATIONS OF WARRANTIES – ALL IMPLIED WARRANTIES (INCLUDING IMPLIED WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE AND MERCHANTABILITY) ARE HEREBY LIMITED IN DURATION TO THE PERIOD FOR WHICH THE LIMITED WARRANTY IS GIVEN. SOME STATES DO NOT ALLOW LIMITATIONS ON HOW LONG AN IMPLIED WARRANTY LASTS, SO THE ABOVE MAY NOT APPLY TO YOU. THE EXPRESSED WARRANTIES MADE IN THIS WARRANTY ARE EXCLUSIVE AND MAY NOT BE ALTERED, ENLARGED, OR CHANGED BY ANY DISTRIBUTOR, DEALER, OR OTHER PERSON WHATSOEVER. ALL WORK UNDER THE TERMS OF THIS WARRANTY SHALL BE PERFORMED DURING NORMAL WORKING HOURS. ALL REPLACEMENT PARTS, WHETHER NEW OR REMANUFACTURED, ASSUME AS THEIR WARRANTY PERIOD ONLY THE REMAINING TIME PERIOD OF THIS WARRANTY.
THE MANUFACTURER WILL NOT BE RESPONSIBLE FOR:
S1-TBSU306-S Thermostat Controllers
Power Requirements | 20 – 30 VAC 50/60 Hz, 3.0 VA @ 24V nominal. | |
Output Rating | W1, W2, W3 = 0.2A max, 0.01A min, 3A inrush, 20 – 30 VAC Y1, Y2, G = 0.4A max, 0.01A min, 3A inrush, 20 – 30 VAC HUM, DEHUM, AUX = 0.1A max, 0.01A min, 3A inrush, 20 – 30 VAC | |
Local Temperature Sensor Type | Thermistor, NTC 10K @ 25˚C | |
Remote Temperature Sensor Type | Thermistor, NTC 10K @ 25˚C | |
Wire Size | 16 AWG (100 ft max) to 24 AWG (36 ft max) | |
Temperature Adjustment Range | 35˚ to 99˚ deg F (2˚ to 36˚ deg C) | |
Accuracy | 35˚ to 65˚ deg F +/- 3˚ degF, greater than 65˚ to less than 80 degF +/- 2 degF, 80˚ to 99˚ deg F +/- 3˚ degF, greater than 99˚ to 104˚ deg F +/- 5˚ deg F | |
Humidity | +/- 10% RH from 30-70% RH, 50˚- 90˚ F | |
Deadband | Adjustable 1˚ to 6˚ deg first stage, 0˚ – 10˚ deg 2nd & 3rd stages | |
Ambient Conditions | Operating | 35˚ to 104˚ deg F (2˚ to 40˚ deg C), 5 – 95% RH non-condensing, 86˚ deg F max dew point |
Storage | -22˚ to 122˚ deg F (-30˚ to 50˚ deg C), 5-95% RH non-condensing, 86˚ deg F max dew point | |
Compliance | UL/cUL listed, file E468676, NEC Class 2 | |
Dimensions | 4.4” H x 5.2” W x 1.0”D | |
Shipping Weight | 0.34 kg |
DOWNLOAD MANUALS:
Source1 S1-TBSU306-S Programmable Digital Thermostat Owners Manual
Source1 S1-TBSU306-S Programmable Digital Thermostat Owners Manual
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…