SIEMENS

Siemens RDY2000BN BACnet Enabled Commercial Room Thermostat Installation Instructions

Siemens RDY2000BN BACnet Enabled Commercial Room Thermostat

Product Information

The BACnet Enabled Commercial Room Thermostat is designed for use with any Energy Management A system providing BACnet MS/TP communication. Use Commercial Room Thermostat RDY2000BN for stand-alone operations. Scan the QR code on the thermostat rear housing for additional information.

 

Product Number
RDY2000BN

Product Specifications

System Compatibility
Conventional Up to 3 Heating/3 Cooling stages
Heat Pumps Up to 4 Heating/2 Cooling stages
Electrical Characteristics
Power Supply 24 Vac +/-20%, Class 2, 4A max.
Power Usage 4 VA (maximum)
Output Relay

Ratings

Pilot duty, 1A max. per output, 4A

max. total

MS/TP Load 1/8 (96 KΩ), internal network bias
Ambient Limitations
Operating

Temperature

23°F to 122°F (-5°C to 50°C)
Storage/Shipping

Temperature

-13°F to 158°F (-25°C to 70°C)
Relative Humidity Up to 95% (non-condensing)
Enclosure
Rating NEMA 1

NOTE
The RDY2000BN is not battery-powered. It
requires 24 Vac power from the HVAC
equipment at terminals RH/RC and C.

Caution Notations

CAUTION: Equipment damage or loss of data may occur if you do not follow the procedures as

specified.

WARNING: Personal injury or loss of life

may occur if you do not follow the procedures as specified.

Required Tools

  • 1 Phillips screwdriver
  • 1/8” flat-blade screwdriver
  • Drill with a 1/8″ drill bit

Expected Installation Time

15 minutes

CAUTION
The RDY2000BN is an advanced controller designed to be installed by professional HVAC technicians. Installation by non-qualified personnel may result in degraded system efficiency, occupant discomfort, or equipment damage.

Prerequisites

WARNING
Turn off power to the HVAC equipment before attempting to remove an existing thermostat or install a new thermostat. All work must be performed in accordance with the applicable codes and standards.

  • Energy Management System Network Plan and HVAC schematics are
  • MS/TP run to thermostat using 24 AWG Low Capacitance 1.5 Twisted Shielded Pair Shield and reference terminator to be earth grounded only at one point on the network.
  • HVAC equipment connections run to the thermostat with 18 gauge thermostat
  • Sensor connections run to the thermostat with 22 gauge twisted pair cable or remote sensor Do not exceed 164 ft (50 m).

Installation

Refer to Energy Management System Network Plan for MS/TP installation and configuration parameters.

  1. Verify power to HVAC equipment is turned
  2. Optional: To replace an existing thermostat:
    1. Remove the existing
    2. Record wiring connections to existing thermostat base plate
    3. Remove the existing base
  3. Install the new thermostat base
    1. Feed all installed wires through the opening in the base plate and strip to 3/16-inch (5 mm).
    2. Secure the base plate to the mounting surface using supplied

NOTE: Ensure that the UP arrows embossed

  1. Attach the HVAC system wires to the appropriate terminals on the thermostat base plate Figure
    • Verify HVAC equipment schematics for required circuit connections to thermostat Wiring Diagrams, Figure 4 and Figure
    • Verify each 24 Vac transformer secondary neutral is connected to the HVAC
    • If a single transformer is used, leave the Jumper RH-RC in place. Connect 24 Vac to RC terminal, and neutral to terminal
    • If separate transformers are used for heating and cooling systems, remove the Jumper RH-RC. Connect cooling 24 Vac to terminal RC, neutral to terminal C and heating 24 Vac to terminal
  2. Optional: Auxiliary Output 3 can be changed to a dry (unpowered) contact by removing Jumper RC-C3 and connecting dry contact wires to OUT3 and C3. See Wiring Diagrams, Figure 6.
  3. Optional: If using Configurable Inputs 1 to 4 or Auxiliary Outputs 1 to 3, use setup parameters P301 to P320 to set functionality.

CAUTION
To ensure signal integrity observe MS/TP network wire polarity, reference terminator and shield earth grounded at one location, two end-of-line terminators, and if required an external network bias device. MS/TP devices from some vendors may refer to input A as (-) and input B as (+) or may require external network bias. For RDY2000BN, NETA is non-inverting input A (+) internally biased high, NETB is inverting input B (-) internally biased low to REF (↓), and external bias is not required.

  • Refer to the network plan for MS/TP wire color code used for (+), (-), and (↓).
  • See Figure 7 for wiring the thermostat at the middle of line (two MS/TP cables) or at the end of line (one MS/TP cable).
  • If the thermostat at the middle of line, connect terminals to two MS/TP cables with (+) to NETA, (-) to NETB, and (↓) to Connect shield wires together and insulate.
  • If the thermostat at the end of line, connect terminals to one MS/TP cable and one end-of-line terminator with (+) and terminator to NETA, (-) and terminator to NETB, and (↓) to REF. Verify shield is connected to the earth’s ground and insulated.
  • Attach the thermostat to the base plate by engaging tabs at the top and rotating the thermostat downward until securely seated on the base plate.
  • Secure the thermostat to the base plate with the Phillips screws (provided), using the holes at the bottom of the housing.
  • Remove the thermostat LCD screen cover.

The installation is now complete. Restore power, and continue to Thermostat Setup.

Thermostat Setup

 

Thermostat Display

Navigation Bar
Only one function can be selected at a time. The small bar (cursor) below the function icon indicates that a function is selected. Pressing an icon twice navigates back to the Main screen.
A double bar cursor below the Settings icon indicates that you are in Programming mode. The navigation bar at the bottom of the display consists of four function icons

Table 1. Navigation Bar Icons

Icon Name Purpose

Setpoint

Enables adustment of temperature and humidity (if applicable) setpoints. Unit will display heating

setpoint if in Heating mode or cooling setpoint if in Cooling mode.

Fan Control Enables fan relay to be controlled as needed by thermostat (AUTO) or

to be on continuously (ON).

 

 

Mode Selector

Enables manual changeover between Heating and Cooling mode. AUTO will enable the thermostat to automatically switch between heating and cooling mode as required. OFF will disable all

control functions.

Settings

Enables Scheduler, Time/Date, and Installer Set Up configuration. Also enables access to service reminder

and fault messages.

Service Reminders and Fault Messages

  • Service reminders appear on the right side of the screen:
    • SERVICE UV LAMP
    • SERVICE HUMIDIFIER
    • SERVICE AIR FILTER

They are determined by the timer set in the Installer Setup Menu and can be cleared by pressing the Settings icon , and then SERVICE. See Clearing Service Reminders.

  • Active fault messages appear at the left side of the home screen:
    • CONNECTION LOST (Not applicable to this model)
    • DEMAND RESPONSE (Not applicable to this model)
    • SERVICE REQUIRED (See Viewing Fault Messages)

Fault messages are automatically cleared when the root cause of the failure is resolved.

Status Bar
The status bar at the top of the display consists of 11 icons

Table 2. Status Bar Icons

Icon Name Meaning

Occupied

Space is occupied, based on Schedule and/or Occupancy Sensor.
Keypad Lock Keypad is locked.
Scheduler Unit is running on the local schedule.

Override

The Scheduler is being overridden by local control.

 

 

Humidity Control Indicator

Droplet and (+) indicates humidification relay is on. Droplet and (-) indicates dehumidification relay is on. If neither relay is on,

the water droplet does not appear.

Fan Fan relay is on.
Fresh Air Economizer Enable/ Ventilation relay is on.
Cool Mode The system is actively in cooling mode.
Heat Mode The system is actively in heating mode.
Heating/Cooling Stages Each segment represents one stage of heating or cooling.

Auxiliary Heating

Auxiliary heating stage: AUX=Stage 1: Aux

2=Stage 2

Wiring Diagrams

 

Figure 5. Wiring Schematic, Heat Pump

 

Set-up Wizard

When unit is powered up for the first time, WIZARD displays. This tool is used to program the basic system parameters. Additional parameters can be accessed directly via Installer/Expert Set-up menus.

NOTE: The thermostat will not start the control sequence until Set-up Wizard is complete.

  1. Press WIZARD to access the

NOTE:     Press left and right arrows to select parameters. Press + or – to change parameter settings.

  1. After completing all Wizard parameters, press

Confirm to save and complete.

  1. INSTALLER
  2. Press INSTALLER to access Installer
  3. Enter values obtained from the Energy Management System Network Plan for the 600 Series BACnet Configuration Parameters. See Table

NOTE: Required to communicate with the Energy Management System

  1. If setup is complete, press the Settings icon to exit the Set-up Wizard. If further setup is needed, continue to Step
  2. Select and modify additional parameters. See Table 3 through Table 9 for all parameter descriptions. Use the space provided in Table 16 to record any modified parameter
  3. Press the Settings icon [ ] when finished to exit

Programming Temperature Setpoints

  1. Touch the center of the Home screen to access the room temperature screen. Use the leftand right  arrows adjacent to the text line to display the room temperature and
  2. Touch the Setpoint icon of the screen toaccess room temperature and humidity setpoints.

NOTE: Only the setpoints in the current mode display and can be modified. For instance, if the thermostat is in heating mode, only the heating setpoint displays and can be modified. If the thermostat is in AUTO mode, both the heating and cooling setpoints will be displayed and can be modified Use the left and right  arrows to access the different setpoints, and the + and – icons to adjust the setpoints.

Programming Time and Date

  1. Touch the center of the Home screen.
  2. Press the Settings icon. SCHEDULER displays.
  3. Use the left  and right  arrows to access the Time menu. Press TIME. Press the two-digit hour display to change the hour, or press the two-digit minute display to change the minutes. Press the left arrow to decrease the value, and the right arrow to increase the value.
  4. Press the Settings icon to save.
  5. Use the left and righ arrows to access the Date menu. Press DATE. Use the arrows to select the month and year; use +/- to set the date.
  6. Press the Settings icon to save.

Installer Menu

  1. Touch the center of the Home screen.
  2. Press the Settings icon
  3. SCHEDULER displays.
  4. Press the left arrow
  5. Press INSTALLER.
  6. Using the lower left and right arrows, enter the password.
  7. Press PASSWORD to accept the password.
    NOTE: The Installer Level default password is 00:00
  8. Press the Settings icon  to accept  changes and return the unit to the Home screen.
    NOTE: If you do not provide input, the thermostat will automatically exit the Installer menu and resume normal system control after five minutes.

Programming the Schedule

  1. Touch the center of the Home screen.
  2. Press the Settings icon . SCHEDULER will display.
  3. Press SCHEDULER.
  4. Use the left  and right arrows to select the day. Press the day to select.
  5. Use the + and – icons to set the mode: Comfort (ON) or Economy (ECO).
  6. Use the left  and right arrows to adjust the start time for each programming period. Adjust the hours and minutes individually by pressing the two-digit hour or two-digit minute fields.
  7. Use the left  and right arrows to select the next event for the given day. Configur  remaining events as desired.
  8. Press the Settings icon  then the left  and right arrows to select the next day. Repeat steps 5 through 7 until the schedule is fully programmed

Maintenance

Locking/Unlocking the Touch Screen To prevent unauthorized access to thermostat settings, use Parameter P211 to configure screen lockouts. The lock icon  indicates that the screen is locked. To unlock the keypad, do the following:

  1. Touch the center of the Home screen to access the room temperature screen.
  2. Press the Settings icon once and LOCKED displays.
  3. Press and hold the Settings icon for 5 seconds; PASSWORD displays.
  4. Using the lower left and right  arrows, enter the INSTALLER password.
  5. Press PASSWORD to accept the password.
  6. Set Parameter 211 (Keypad Lockout) to OFF to disable keypad lockout.
  7. Touch the Setpoint icon of the screen to return to the Home screen.

Clearing Service Reminders

The thermostat displays SERVICE REQUIRED and an associated service reminder if the reminder timer (Parameters 208 – 210) has timed out. To clear these, do the following:

  1. Touch the center of the Home screen to access the room temperature screen.
  2. Press the Settings icon  and SERVICE displays.
  3. Use the left and right arrows to select the service reminder.
  4. To clear, touch the + icon and the display changes from  to OFF.
  5. Counter resets and reminder icons turn off.

Viewing Fault Messages
The thermostat displays SERVICE REQUIRED if a sensor fails or a service reminder has timed out. To view these, do the following:

  1. Touch the center of the Home screen to access the room temperature screen.
  2. Press the Settings icon and SERVICE isplays.
  3. Press SERVICE and review faults. Use the left and right  arrows to see all faults.

NOTE: The fault message is automatically cleared when the root cause of the failure is resolved.

Resetting the Unit to Factory Defaults

CAUTION
The following steps set ALL parameters to factory defaults (including passwords), and restart the Set-up Wizard.

  1. Log in as either an Installer or Expert.
  2. Press the left arrow. RESTORE displays.
  3. Press + to change the setting to YES.
  4. Press RESTORE.
    This resets the unit and restarts the Set-up Wizard.

Table 3. 100 Series Parameters

Parameter Definition Display Value Range Default Extended Definition Notes
P101* System Type SYS TYPE CO(1)

HP(2)

CO CO = Conventional HP = Heat Pump

P102*

Cooling Stages

COOL STGS

0

1

2

3

2

Sets number of cooling stages

P103*

Heating Stages

HEAT STGS

0

1

2

3

2

Sets number of heating stages

P104*

Aux Heating Stages

AUX HT STG

0

1

2

0

Sets number of auxilary heat stages

P105*

Fan Operation

HTG FAN

ELE

gAS

ELE

ELE =      Fan Relay energized on call for heat

gAS =      Fan Relay always energized unless Aux Heat calls for heat.

P106*

Reversing Valve

REV VALVE

0

b

0

0 = Energize reversing valve on cooling b = Energize reversing valve on heating ~ This parameter only

appears if system is heat pump

 

P107*

 

Scheduler Days

 

SCHEDULER

1

2

3

7

OFF

 

2

1 = Schedule all days with same schedule 2 = One schedule for M-F and another for

Sat + Sun

3 = One schedule for M-F, Sat + Sun scheduled individually

7 = Schedule each day individually

OFF = Scheduler Disabled

P109* Units UNITS F C F

P110

Changeover

AUTO CHNGE

YES NO

YES

~ This parameter does not appear on systems that are heat only or

cool only

 

 

P111

 

Changeover Deadband

 

 

DEADBAND

3

4

5

6

7

8

9

 

 

5°F

 

 

Deadband in degrees F

~ This parameter does not appear if CHANGEOVER = M

~ This parameter does not appear on systems that are heat only or

cool only

P112

Daylight Savings

DAYLT SAVE

YES NO

NO

Y = Auto adjust for daylight savings time N = Does not auto adjust for daylight

savings time

P113 Display Temp Setpoint TMP SP DIS 0=Absolute 1=Relative 0=Absolute Selection of setpoint display: absolute or relative value

Table 4. 200 Series Parameters

Parameter Definition Display Value Range Default Extended Definition Notes
P201 Heat Temp Limit HEAT LIMIT 45 – 95 95°F Sets maximum allowable heating setpoint ~ Does not appear if HEAT STAGES = 0
P202 Cool Temp Limit COOL LIMIT 50 – 95 50°F Sets minimum allowable cooling set point ~ Does not appear if COOL STAGES = 0

P203

Temperature Display Offset

TMP OFFSET

-5 to +5

0°F

Enables adjustment of control temp and display temperature in 1 degree increments.Applies only to onboard temp sensor. Indoor temp only.

 

 

 

P204

 

 

Override Time Limit

 

 

 

HRS OVR RD

“—” = unlimited; 0 = none;

2 =2 hours;

4 = 4 hours;

6 = 6 hours;

8 = 8 hours

10 = 10 hours

12 = 12 hours

24 = 24 hours

96=96 hours

 

 

 

2

 

 

Number of hours that scheduled setpoint can be manually overridden. 0 = no override allowed

 

 

~ This parameter does not appear if SCHEDULER = OFF

 

 

 

P205

 

 

 

Override Temp Limit

 

 

 

TMP OVR RD

— 1

2

3

4

5

6

7

8

9

10

 

 

 

 

 

Number of degrees F that are allowed above or below scheduled setpoint.

— = Unlimited

 

 

~ This parameter does not appear if SCHEDULER = OFF

 

 

P206

 

Heat Pump Compressor Lock Out

 

 

HP COMP LO

OFF 15=15°F

20=20°F

25=25°F

30=30°F

35=35°F

40=40°F

45=45°F

 

 

OFF

 

Heat pump compressor will not operate below this outdoor temp — forcing unit to auxiliary heat

~ Only shown if SYS TYPE = HP with AUX HEAT and there is an outdoor temp sensor

~ Must be lower than HP AUX LO

 

P207

Heat Pump Auxiliary Heat Lockout

 

HP AUX LO

OFF 40=40°F

45=45°F

50=50°F

55=55°F

60=60°F

 

OFF

 

Heat pump auxiliary heat will not operate above this outdoor temp.

~ Only shown if SYS TYPE = HP with AUX HEAT and there is an outdoor temp sensor

~ Must be higher than HP COMP LO

P208

Service UV Lamp

UV LAMP

0-365

0

Number of days until SERVICE UV LAMP message is displayed.

0 = function disabled.

P209

Service Humidifier HMDFR SRVC

0-365

0

Number of days until SERVICE HUMIDIFIER message is displayed. 0 = function disabled.

P210

Service Air Filter

FLTR SRVC

0-365

0

Number of days until SERVICE AIR FILTER message is displayed.

0 = function disabled.

P211

Keypad Lockout

KEY LOCK

OFF 2

3

OFF

OFF = No lockout

2 = Partial Lockout (only temp setpoint can be adjusted)

3= Total Lockout

P212 Clock Format CLOCK 12

24

12 12 = 12-hour format 24 = 24-hour format
Parameter Definition Display Value Range Default Extended Definition Notes

P213

Backlight

LIGHT

0-99

15

Number of seconds that backlight stays on after screen is touched. 0 = always off.

P220

Heating Setpoint Comfort

COMF HT SP

As defined in Heat Temp Limit (P201)

70°F

Normal occupied heating setpoint

P221

Cooling Setpoint Comfort

COMF CL SP

As defined in Cool Temp Limit (P202)

75°F

Normal occupied cooling setpoint

P222

Heating Setpoint Economy

ECO HT SP

40 – 104

62°F

Normal unoccupied heating setpoint

P223

Cooling Setpoint Economy

ECO CL SP

45 – 104

82°F

Normal unoccupied cooling setpoint

P224

Heating Setpoint Protection

PROT HT SP

40 – 104

40°F

Normal minimum heating setpoint

P225

Cooling Setpoint Protection

PROT CL SP

45 – 104

104°F

Normal maximum cooling setpoint

Table 5.  300 Series Parameters

Parameter Definition Display Value Range Default Extended Definition Notes

 

 

 

P301

 

 

Configurable Input 1 (IN1)

 

 

 

INPUT 1

1

2

3

4

5

6

7

8

9

OFF

 

 

 

OFF

1 = Indoor Temperature (Remote) 2 = Indoor Temperature (Average) 3 = Supply Temp

4 = Return Temp 5 = Outdoor Temp

6 = Humidity (0-10V) 7 = CO2 (0-10V)

8 = Occupancy (DI) 9 = Fault

OFF = Not Used

 

~ Cannot have duplicate selections for inputs 1-4

~ If set to 9 (fault), a DI here causes SERVICE REQUIRED segment to activate

P302 Temperature Input 1 Type TMP IN 1 1

2

1 1= Type 2 Thermistor

2 = 0-10V

~ Only appears if INPUT 1 = 1/2/3//4/5

P303

Temperature Input 1 Low

TMP 1 LO

-58 —

+250F

-50 —

+120C

0

Calibrates thermostat to low end of temp sensor signal (e.g., 0V = -40F)

Only appears if TMP IN 1 = 1 Must be lower than TMP 1 HI

P304

Temperature Input 1 High

TMP 1 HI

-58 —

+250F

-50 —

+120C

120

Calibrates thermostat to high end of temp sensor signal at 10 volts (e.g., 10V = 250F) Only appears if TMP IN 1 = 1 Must be higher than TMP 1 LO

 

 

 

P305

 

 

Configurable Input 2 (IN2)

 

 

 

INPUT 2

1

2

3

4

5

6

7

8

9

OFF

 

 

 

OFF

1 = Indoor Temperature (Remote) 2 = Indoor Temperature (Average) 3 = Supply Temp

4 = Return Temp 5 = Outdoor Temp

6 = Humidity (0-10V) 7 = CO2 (0-10V)

8 = Occupancy (DI) 9 = Fault

OFF = Not Used

 

~ Cannot have duplicate selections for inputs 1-4

~ If set to 9 (fault), a DI here causes SERVICE REQUIRED segment to activate

P306

Temperature Input 2 Type

TMP IN 2

1

2

1

1 = Type 2 Thermistor

2= 0-10V

~ Only appears if INPUT 2 = 1/2/3/4/5

~ SCW can be 0 or 1

Parameter Definition Display Value Range Default Extended Definition Notes

P307

Temperature Input 2 Low

TMP 2 LO

-58 —

+250F

-50 —

+120C

0

Calibrates thermostat to low end of temp sensor signal (e.g., 0V = -40°F)

Only appears if TMP IN 2 = 1 Must be lower than TMP 2 HI

P308

Temperature Input 2 High

TMP 2 HI

-58 —

+250F

-50 —

+120C

120

Calibrates thermostat to high end of temp sensor signal at 10 volts (e.g., 10V = 250°F) Only appears if TMP IN 2 = 1 Must be higher than TMP 2 LO

 

 

 

P309

 

 

Configurable Input 3 (IN3)

 

 

 

INPUT 3

1

2

3

4

5

6

7

8

9

OFF

 

 

 

OFF

1 = Indoor Temperature (Remote) 2 = Indoor Temperature (Average) 3 = Supply Temp

4 = Return Temp 5 = Outdoor Temp

6 = Humidity (0-10V) 7 = CO2 (0-10V)

8 = Occupancy (DI) 9 = Fault

OFF = Not Used

 

~ Cannot have duplicate selections for inputs 1-4

~ If set to 9 (fault), a DI here causes SERVICE REQUIRED segment to activate

P310 Temperature Input 3 Type TMP IN 3 1

2

1 1 = Type 2 Thermistor

2 = 0-10V

~ Only appears if INPUT 3 = 1/2/3/4/5

P311

Temperature Input 3 Low

TMP 3 LO

-58 —

+250F

-50 —

+120C

0

Calibrates thermostat to low end of temp sensor signal (e.g., 0V = -40°F)

Only appears if TMP IN 3 = 1 Must be lower than TMP 3 HI

P312

Temperature Input 3 High

TMP 3 HI

-58 —

+250F

-50 —

+120C

120

Calibrates thermostat to high end of temp sensor signal at 10 volts (e.g., 10V = 250°F) Only appears if TMP IN 3 = 1 Must be higher than TMP 3 LO

 

 

 

P313

 

 

Configurable Input 4 (IN4)

 

 

 

INPUT 4

1

2

3

4

5

6

7

8

9

OFF

 

 

 

OFF

1 = Indoor Temperature (Remote) 2 = Indoor Temperature (Average) 3 = Supply Temp

4 = Return Temp 5 = Outdoor Temp

6 = Humidity (0-10V) 7 = CO2 (0-10V)

8 = Occupancy (DI) 9 = Fault

OFF = Not Used

 

~ Cannot have duplicate selections for inputs 1-4

~ If set to 9 (fault), a DI here causes SERVICE REQUIRED segment to activate

P314 Temperature Input 4 Type TMP IN 4 1

2

1 1= Type 2 Thermistor

2= 0-10V

Only appears if INPUT 2 = 1/2/3/4/5

P315

Temperature Input 4 Low

TMP 4 LO

-58 —

+250F

-50 —

+120C

0

Calibrates thermostat to low end of temp sensor signal (e.g., 0V = -40°F)

~ Only appears if TMP IN 4 = 1

~ Must be lower than TMP 4 HI

P316

Temperature Input 4 High

TMP 4 HI

-58 —

+250F

-50 —

+120C

120

Calibrates thermostat to high end of temp sensor signal at 10 volts (e.g., 10V = 250°F) ~ Only appears if TMP IN 4 = 1

~ Must be higher than TMP 4 LO

 

 

P317

 

 

Aux Output 1 (OUT1)

 

 

AUX OUT 1

1

2

3

4

5

OFF

 

 

OFF

 

1 = Humidification

2 = Dehumidification

3 = Occupied 4 = Air Quality

5 = Economizer Enable OFF = Not Used

~ Cannot have duplicate selections for outputs 1-3

~ Air Quality not an option unless an input is set to CO2 sensor

~ If system is conventional with 3H +3C, AO1 will default to, and be locked as, stage 3 cooling.

Parameter Definition Display Value Range Default Extended Definition Notes

 

 

P318

 

Aux Output 2 (OUT2)

 

 

AUX OUT 2

1

2

3

4

5

OFF

 

 

OFF

1 = Humidification

2 = Dehumidification

3 = Occupied 4 = Air Quality

5 = Economizer Enable OFF = Not Used

~ Cannot have duplicate selections for outputs 1-3

~ Air Quality not an option unless an input is set to CO2 sensor

 

 

P319

 

Aux Output 3 (OUT3 & C3)

 

 

AUX OUT 3

1

2

3

4

5

OFF

 

 

OFF

1 = Humidification

2 = Dehumidification

3 = Occupied 4 = Air Quality

5 = Economizer Enable OFF = Not Used

~ Cannot have duplicate selections for outputs 1-3

~ Air Quality not an option unless an input is set to CO2 sensor

 

P320

Independent Humidity Control

 

IND HMDTY

YES NO

 

NO

NO = Humidification & Dehumidification only when heating or cooling relay is energized

Yes = Humidification or dehumidification independent of heating/cooling

Parameter Definition Display Value Range Default Extended Definition Notes

 

P401

 

Unit Number

 

UNIT NMBR

 

0-999

 

Installer can use this field to link a thermostat to an HVAC unit or zone number. If any value other than — is entered, the “sleep” screen should display UNIT NUMBER in text box

above room temp display.

P402 CO2 Set Point CO2 SET PT 500 —

2000

1000 Only appears if an analog input is configured as a C02 sensor

P403

Pre- Occupancy Purge

PRE OC PRG

OFF 1

2

3

OFF

OFF = Disabled 1 = 1 Hour

2 = 2 Hours

3 = 3 Hours

~ Only show if an output is set to economizer and scheduler function is active

P404

Occupancy

Sensor Min Run Timer

OCC MRT

3 — 60

30

Minimum run time in minutes for

occupancy detected via digital input from external sensor

~ Only shown if an input is set to Occupancy Sensor

P405

Semi- Continuous Fan

CONT FAN

0=NO

1=Yes

NO

~ Only shown if a schedule is present or if an input is configured for occupancy

sensor

P407 Installer Password INSTALL PW 0000 —

4999

Current PW

Expert Level Menus

  1. Touch the center of the Home screen.
  2. Press the Settings icon SCHEDULER displays.
  3. Press the left  arrow.
  4. Press INSTALLER.
  5. Using the lower left and right arrows, enter the password
  6. Press PASSWORD to accept the password and return the unit to the Setup Menu.
    NOTE: The Expert Level default password is 99:99.
  7. See Table 3 through Table 10 and Wiring Diagrams for additional information.
  8. Press the Settings icon to accept changes and return the unit to the Home screen

Recovering a Lost Password

If either of the default passwords is changed, the new password(s) should be recorded and maintained for future reference. If the records are misplaced, the following procedure can be used to set new passwords:

  1. Cycle power to the thermostat. This can be done by loosening the securing screws on the bottom of the housing and momentarily separating the thermostat from the base plate.
  2. Within 80 seconds of restoring power, navigate to the Installer Set-up screen and enter 98:21 as the password.
  3. The thermostat will go directly to the Expert Level password screen. A new Expert Level password can now be set.
  4. After setting a new Expert Level password, the thermostat will return to the Home screen.
  5. The new Expert Level password can be used to enter the full Expert Level set-up menu where both the Expert Level and Installer Level passwords can now be set to new values.

Table 7. 500 Series Expert Settings Parameters.
(Only available if logged in as an Expert.)
NOTE: P500 Series parameters are factory-set for optimum system performance. Changing these settings may degrade efficiency and/or compromise occupant comfort.

Parameter Definition Display Value Range Default Extended Definition
P501 Interstage Delay – Cooling STG DLY CL 1 to 10 minutes 5 Time delay before next stage of cooling will be activated.
P502 Interstage Differential – Cooling STG DIF CL 1°F (0.5°C) to

10°F (5.0°C)

1°F Degrees above cooling deadband before Stage Delay timer is initiated.
P503 Cooling Minimum Off Time M O T CL 1 to 10 minutes 5 Minimum time between compressor starts.
P504 Cooling Minimum On Time M R T CL 1 to 10 minutes 3 Minimum run time for any stage of cooling.
P505 Changeover Delay C-O DLY 1 to 60 10 Delay in minutes before system will automatically

switch from heating to cooling (or vice versa).

P506

Cooling Deadband

CL DEADBND

1°F (0.5°C) to

5°F (4.0°C)

1°F

The deadband is divided equally above and below setpoint. Cooling will begin when temperature exceeds upper point of deadband and ceases

when temperature falls below lower point of deadband.

P507 Interstage Delay – Heating STG DLY HT 1 to 10 minutes 5 Time delay before next stage of heating will be

activated.

P508

Interstage Differential – Heating

STG DIF HT

1°F (0.5°C) to

5°F (5.0°C)

Conv. = 1°F (0.5°C) HP = 2°F

(1.0°C)

Degrees below heating deadband before Stage Delay timer is initiated.

P509 Heating Minimum Off Time M O T HT 1 to 10 minutes 5 Minimum time between heating starts.
P510 Heating Minimum On Time M R T HT 1 to 10 minutes Conv = 3

HP = 10

Minimum run time for any stage of heating.

P511

Heating Deadband

HT DEADBND

1°F (0.5°C) to

5°F (4.0°C)

1°F (0.5°C)

The deadband is divided equally above and below setpoint. Heating will begin when temperature falls below lower point of deadband and ceases when temperature rises above upper port of

deadband.

Parameter Definition Display Value Range Default Extended Definition

 

 

P601

 

 

MS/TP MAC address

 

 

MS–TP MAC

 

 

0-255

 

 

255

MS/TP MAC address must be unique for the entire network 1 to 254.

In systems that support and use Master Nodes valid range to use is from 1 to 127.

In systems that support and are using auto discovery leave value at default 255

NOTE: When integrating with APOGEE®, set

this parameter to be a Master Node.

 

P602

 

Baud Rate

 

BAUD RATE

A       = Auto

9.6     = 9600

19.2 =19200

38.4 = 38400

57.6 = 57600

76.8 = 76800

115.2 =115200

 

A=Auto

This parameter will set the network’s baud rate. Auto value will match detected Baud Rate in systems that support and are using auto discovery leave value at default “A”

P603

Device Instance

DEV ID

0 – 4194303

4194303

Device Instance (unsigned integer 0-4194303) In systems that support and are using auto

discovery leave value at default 4194303

P604 Max Master MAX MASTER 1–127 127 Max Master
P605 Serial number SER NR Display Only Display Only Display Serial number, 10 digit hex, programmed in factory
P606 Max Info Frames MAX FRAME 1– 10 1 Max Info Frames

CAUTION
See the Energy Management System Network Plan before entering values in the RDY2000BN 600 Series BACnet Configuration Parameters. Incorrect values will prevent connection to the Energy Management System

Parameter Definition Display Value Range Default Extended Definition
P701 Firmware FIRMWARE Display only Display only Display Firmware Version

Table 10. 900 Series Expert Settings Parameters. (Only available if logged in as an Expert.)
P900 Series parameters are used by professional HVAC technicians during the system commissioning process. Interlocks and time delays are defeated while using P900 parameters. Use of these parameters by non-qualified personnel may result in equipment damage.

Parameter Definition Display Value Range Default Extended Definition
P901 Test Compressor 1 Y1 Test 1=OFF

0=ON

OFF OFF = Relay not energized ON = Relay energized

P902

Test Compressor 2

Y2 Test

1=OFF

0=ON

OFF

OFF = Relay not energized ON = Relay energized

P903

Test Reversing Valve

O/B TEST

1=OFF

0=ON

OFF

OFF = Relay not energized ON = Relay energized

P904

Test Fan

G Test

1=OFF

0=ON

OFF

OFF = Relay not energized ON = Relay energized

P905

Test Heat Stg 1

W1 Test

1=OFF

0=ON

OFF

OFF = Relay not energized ON = Relay energized

P906

Test Heat Stg 2

W2 Test

1=OFF

0=ON

OFF

OFF = Relay not energized ON = Relay energized

P907

Test Output 1

OUT1 TST

1=OFF

0=ON

OFF

OFF = Relay not energized ON = Relay energized

P908

Test Output 2

OUT2 TST

1=OFF

0=ON

OFF

OFF = Relay not energized ON = Relay energized

P909

Test Output 3

OUT3 TST

1=OFF

0=ON

OFF

OFF = Relay not energized ON = Relay energized

P911

Expert Password

XPRT PW

5000 — 9999

Current PW

P999

Restore Factory Defaults

RESTORE

0=No

1=Yes

No

Auxiliary Sequences
The RDY2000BN primary sequences are designed to control single and multi-stage heating/cooling systems to maintain a user-selected temperature setpoint. The following auxiliary sequences are available to optimize occupant comfort and system efficiency:

Humidification

Parameters

  • P317/ P318/P319: One of these must be set to 1
  • P320: NO (default) = Humidification will only occur if there is a call for heating. YES = Humidification relay will be energized independently of heating and cooling
  • Humidity Setpoint: User adjustable to desired level in humidification
  • Sensors: Onboard humidity sensor or optional remote humidity sensor.

The humidification relay will energize when measured humidity drops approximately 4% below setpoint and will de-energize when measured humidity reaches setpoint. Deadbands and proof timers are in force to prevent short cycling.

Dehumidification

Parameters

  • p317/ P318/P319: One of these must be set to 2
  • P320: NO (default) = Dehumidification will only occur if there is a call for cooling. YES = Dehumidification relay will be energized independently of heating and cooling
  • Dehumidity Setpoint: User adjustable to desired level in dehumidification

Sensors: Onboard humidity sensor or optional remote humidity sensor.
The dehumidification relay will energize when measured humidity rises approximately 4% above setpoint and will de-energize when measured humidity reaches setpoint. Deadbands and proof timers are in force to prevent short cycling.

Economizer Enable
Parameters

  • P317/P318/P319: One of these must be set to 5.
  • P301/P305/P309/P313: One of these must be set to 8 if the optional occupancy sensor is used.

Sensors: None required, however an optional occupancy sensor can be used instead of, or in conjunction with the scheduler to determine occupancy.
The Economizer Enable relay will be energized whenever a cooling relay is energized or the space is occupied. The thermostat uses the scheduled Comfort mode to determine if the space is occupied. An optional occupancy sensor can also be used for definitive proof of occupancy. An output configured for Occupancy Notification can also be used for Economizer Enable.

Pre-Purge
Parameters

  • P317/P318/P319: One of these must be set to 5.
  • P403

Sensors: None required.
To enable the economizer and energize the fan relay prior to scheduled occupancy, set P403 to the number of hours before scheduled occupancy for pre-purge to begin. This function requires a schedule to be configured.

Occupancy Notification
Parameters

  • P301/P305/P309/P313: If the optional occupancy sensor is used, one of these must be set to 8.
  • P317/P318/P319: To signal an external device that the space is occupied, one of these must be set to 3
  • P404: If the optional occupancy sensor is used, P404 can be used to set a minimum run timer for any actions that are activated by occupancy, such as Economizer Enable, control to occupied temperature setpoints, and so on. Note that many occupancy sensors also have onboard proof timers.

There are two primary methods by which the thermostat can assume the space is occupied.

  1. The space is assumed to be occupied when the schedule mode is set to Comfort.
  2. During periods in which the schedule indicates the space is unoccupied, any human interaction with the thermostat (for example, setpoint adjustment) will put the thermostat into Occupied mode.

The optional occupancy sensor can be used in conjunction with the schedule. The thermostat will follow the assumptions above, but an input from the occupancy sensor during a scheduled unoccupied period will put the thermostat in the Occupied mode for the duration of the timer set in P404. To utilize the Occupancy functions, the thermostat must have an active schedule.

Air Quality Management
Parameters

  • P301/P305/P309/P313: One of these must be set to 7.
  • P317/P318/P319: One of these must be set to 4.
  • P402: CO2 Setpoint Sensors: Optional CO2 Sensor
  • If measured CO2 exceeds setpoint by 200 PPM for a minimum of 60 seconds, the Air Quality output and fan relays will be energized. The minimum run time is 5 minutes.
  • When measured CO2 falls below setpoint and appropriate minimum run time has been met, the Air Quality output relay will be de-energized and the fan relay shall revert to normal operation.

Table 11. Daily Schedule Example – 6 Periods per Day, Parameter 107 = 1.

Day Monday – Sunday (Each day is the same)
Event 1 2 3 4 5 6
Mode COM ECO COM ECO COM ECO
Time 6:00 AM 11:00 AM 1:00 PM 2:00 PM 3:00 PM 10:00 PM

Table 12. Work Week Schedule with Weekend Example – 6 Periods per Day, Parameter 107 = 2.

Day Work Week (Monday-Friday) Weekend (Saturday-Sunday)
Event 1 2 3 4 5 6 1 2 3 4 5 6
Mode COM ECO COM ECO COM ECO COM ECO COM ECO COM ECO
Time 6:00

AM

11:00

AM

1:00

PM

2:00

PM

3:00

PM

10:00

PM

8:00

AM

11:00

AM

1:00

PM

2:00

PM

3:00

PM

10:00

PM

Table 13. Work Week Schedule with Separate Weekend Days Example – 6 Periods per Day, Parameter 107 = 3.

Work Week (Monday-Friday) Saturday Sunday
Event 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6
Mode COM ECO COM ECO COM ECO COM ECO COM ECO COM ECO COM ECO COM ECO
Time 6:00

AM

11:00

AM

1:00

PM

2:00

PM

3:00

PM

10:00

PM

8:00

AM

11:00

AM

1:00

PM

2:00

PM

3:00

PM

10:00

PM

10:00

AM

12:00

PM

2:00

PM

3:00

PM

–:– –:–

Table 14. Individual Days (Monday – Sunday) Example – 6 Periods per Day, Parameter 107 = 7.

Day Monday – Sunday (Each day can be unique)
Event 1 2 3 4 5 6
Mode Comfort Economy Comfort Economy Comfort Economy
Time 6:00 AM 11:00 AM 1:00 PM 2:00 PM 3:00 PM 10:00 PM

NOTE
The Scheduler default setting consists of two events: Event 1 = ON (Comfort) at 7:00 AM, Event 2 = ECO (Economy) at 7:00 PM.

Table 15. Suggested Sensors for Use with RDY2000BN.

Siemens Part Number Description Signal Format
QAA2330.EWNN Remote Wall-Mounted Sensor – Temperature Only 10K Ohm, Type II NTC
QFA33SS.EWNN Remote Wall-Mounted Temperature and Humidity Sensor 0-10V
QAM2030.010 Duct-Mounted Temperature Sensor 10K Ohm, Type II NTC
QFM2160U Duct-Mounted Temperature & Humidity Sensor 0-10V
QPA2000 Wall-Mounted CO2 Sensor 0-10V
QPA2062 Wall-Mounted Temperature + Humidity + CO2 Sensor 0-10V
QPM2162 Duct-Mounted Temperature + Humidity + CO2 Sensor 0-10V
QAC2030 Outdoor Air Temperature Sensor 10K Ohm, Type II NTC
QAD2030 Surface-Mount Pipe Temperature Sensor 10K Ohm, Type II NTC

Federal Communications Commission Notice

This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:

  • Reorient or relocate the receiving antenna.
  • Increase the separation between the equipment and the receiver.
  • Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
  • Consult the dealer or an experienced radio/TV technician for help.

Modifications
This device complies with Part 15 of the FCC rules and IC rules. Changes or modifications not expressly approved by Siemens Industry Inc. could void the user’s authority to operate the equipment.

Industry Canada
This Class B digital apparatus meets all requirements of the Canadian Interference-Causing Equipment Regulations.

Limited Warranty

Siemens Product Guard Warranty warrants the purchased from it or its authorized reseller to be free from defects in material and workmanship under normal use during the two-year period commencing on the date of purchase. The written proof of purchase is required for such warranty period to apply. The software included in this Siemens product is licensed for use subject to the Siemens end-user license agreement (“ EULA”) posted at www.usa.siemens.com/btcpseula (Siemens’ EULA web site) for this software identified by product model or part number on the Siemens EULA web site.

Information in this publication is based on current specifications. The company reserves the right to make changes in specifications and models as design improvements are introduced. APOGEE is a registered trademark of Siemens Industry, Inc. Other product or company names mentioned herein may be the trademarks of their respective owners. © 2016 Siemens Industry, Inc.

Table 16.  Record Field Settings

Parameter Definition Default Field Value
P101 System Type CO
P102 Cooling Stages 2
P103 Heating Stages 2
P104 Aux Heating Stages 0
P105 Fan Operation ELE
P106 Reversing Valve O
P107 Scheduler Days 2
P109 Units F
P110 Changeover YES
P111 Changeover Deadband 5°F (2.5°C)
P112 Daylight Savings NO
P113 Display Temp Setpoint 0 = Absolute
P201 Heat Temp Limit 95°F (35.0°C)
P202 Cool Temp Limit 50°F (10.0°C)
P203 Temperature Display Offset 0°F (0°C)
P204 Override Time Limit 2
P205 Override Temp Limit
P206 Heat Pump Compressor Lock Out OFF
P207 Heat Pump Auxiliary Heat Lockout OFF
P208 Service UV Lamp 0
P209 Service Humidifier 0
P210 Service Air Filter 0
P211 Keypad Lockout OFF
P212 Clock Format 12
P213 Backlight 15
P220 Heating Setpoint Comfort 70
P221 Cooling Setpoint Comfort 75
P222 Heating Setpoint Economy 62
P223 Cooling Setpoint Economy 82
P224 Heating Setpoint Protection 40
P225 Cooling Setpoint Protection 104
P301 Configurable Input 1 (IN1) OFF
P302 Temperature Input 1 Type 1
P303 Temperature Input 1 Low 0°F (-18.0°C)
P304 Temperature Input 1 High 120°F (50°C)
P305 Configurable Input 2 (IN2) OFF
P306 Temperature Input 2 Type 1
P307 Temperature Input 2 Low 0°F (-18.0°C)
P308 Temperature Input 2 High 120°F (50.0°C)
P309 Configurable Input 3 (IN3) OFF
P310 Temperature Input 3 Type 1
P311 Temperature Input 3 Low 0°F (-18.0°C)
P312 Temperature Input 3 High 120°F (50.0°C)
P313 Configurable Input 4 (IN4) OFF
P314 Temperature Input 4 Type 1
P315 Temperature Input 4 Low 0°F (-18.0°C)
P316 Temperature Input 4 High 120°F (50.0°C)
P317 Aux Output 1 (OUT1) OFF
P318 Aux Output 2 (OUT2) OFF
P319 Aux Output 3 (OUT3 & C3) OFF
P320 Independent Humidity Control NO
P401 Unit Number
P402 CO2 Setpoint 1000
P403 Pre-Occupancy Purge OFF
P404 Occupancy Sensor Min Run Timer 30
P405 Semi-Continuous Fan NO
P407 Installer Password Current PW
P501 Interstage Delay – Cooling 5
Parameter Definition Default Field Value
P502 Interstage Differential – Cooling 1°F (0.5°C)
P503 Cooling Minimum Off Time 5
P504 Cooling Minimum On Time 3
P505 Changeover Delay 10
P506 Cooling Deadband 1°F
P507 Interstage Delay – Heating 5
P508 Interstage Differential – Heating Conv. = 1°F (0.5°C); HP = 2°F (1°C)
P509 Heating Minimum Off Time 5
P510 Heating Minimum On Time 3 (10 if heat pump)
P511 Heating Deadband 1°F (0.5°C)
P601 MS/TP MAC address 255
P602 Baud rate A = Auto
P603 Device instance 4194303
P604 Max master 127
P605 Serial number Display only
P606 Max info frames 1
P701 Firmware Display only
P911 Expert Password Current PW

References:

Download Manual

Siemens RDY2000BN BACnet Enabled Commercial Room Thermostat Installation Instructions

OTHER MANUAL

Siemens RDY2000BN BACnet Enabled Commercial Room Thermostat User Guide

Siemens RDY2000BN BACnet Enabled Commercial Room Thermostat Installation Instructions

wpx_thermostats

Recent Posts

Johnson Controls T7000e LCD Digital Thermostat Installation Guide

Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide

1 year ago

Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’S GUIDE

Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE

1 year ago

Hetta HS01RF WIRELESS THERMOSTAT KIT USER MANUAL

Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…

1 year ago

HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat USER MANUAL

HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…

1 year ago

Honeywell RLV450 PROGRAMMABLE THERMOSTAT USER GUIDE

Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…

1 year ago

Honeywell RLV431 Programmable Thermostat User Guide

Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…

1 year ago