The device comprises of 1 RDH100RF (transmitter) and 1 RCR100/433 (receiver), is used to control the room temperature in heating systems.
Typical applications:
The device can be used together with the following equipment:
Temperature control
RDH100RF/SET offers both 2-position and PID intelligent learning temperature control, configurable via parameter P01 (control behavior).
2-position control algorithm to switch on and off the heating system within a switching differential (SD) as per the difference between setpoint setting and measured room temperature.
PID intelligent learning control algorithm periodically switches on and off the heating system. The period time (T) and pulse length (P) of the control signal (PWM) are determined by the setpoint and the measured room temperature.
In general, PID control provides more comfort and is more energy efficient than 2-position control.
Control behavior (P01)
The factory setting for control is “PID slow”, ideal for most heating systems. Optimum control can be selected if control does not provide the desired result:
2-position controller with 1 [K] switching hysteresis
2-position, 1 K
PID slow
PID control behavior for slow heating systems that require longer minimum On times and a limited number of switching cycles per hour.
Typical applications:
Minimum switch on/off time | > 4 minutes |
Minimum period | Approximately 12 minutes |
PID fast
PID control behavior for fast heating systems that tolerate a high number of switching cycles.
Typical applications:
Minimum switch on/off time | > 1 minute |
Minimum period | Approximately 6 minutes |
WARNING: Do not use PID fast for oil boilers or electric mechanical actuators!
Backup: When removing the batteries, the setpoints and information required for operating mode changeover are retained for max. 2 minutes.
Parameter | Description | Factory setting | Setting range | Remark |
P01 | Control behavior | PID slow (4) | 0 = 2P, 1.0 K 1 = 2P, 0.5 K 2 = PID fast 4 = PID slow | |
P02 | Maximum temperature range | 30 °C | P03…30 °C | Limit of comfort and economy setpoint |
P03 | Minimum temperature range | 5 °C | 5 °C…P02 | Limit of comfort and economy setpoint |
End | Exit parameter setting |
Parameter setting
The parameter setting remains in non-volatile memory and is not erased when the battery is removed. The reset function on the rear of the thermostat reloads the factory settings.
Parameter setting mode
Note: The thermostat automatically exits parameter setting mode one minute after the last action.
Equipment combinations
Description | Product number | Data sheet *) | |
Electrothermal actuator (for radiator valves) | | STA321 | A6V12986007 |
Electrothermal actuator (for small valves 2.5mm) | | STP321 | A6V12986007 |
Electromotoric actuator | SFA21.. | 4863 |
The documents can be downloaded from http://siemens.com/bt/download.
Display: The digital display shows the current room temperature and the comfort temperature setpoint. When the heating output is active, the triangle symbol is displayed.
When ordering, specify both name and product number, e.g. room temperature controller RDH100RF/SET.
Order valves and actuators as separate items.
The transmitter consists of 4 parts:
The housing engages in the baseplate and snaps on. There is a reset button on the rear of the transmitter.
Elements | 1 | Display of the room temperature in °C / °F | |
2 | Indicates a request for heating | ||
3 | Temperature setting knob | ||
4 | Battery compartment | ||
5 | Comfort temperature setpoint | ||
6 | RF TEST | Indicates RF signal test | |
7 | Indicates low battery power; replace batteries |
The receiver is located in a plastic housing with LEDs and buttons.
The transmitter is located in a plastic housing. Two buttons are visible on the rear when removing the baseplate.
Override allows for temporarily overriding the active value from the sender. Override responds differently depending on the radio connection (normal or fault).
RF LED
RF state | RF LED |
Power up (first 5 seconds) | Flash RED |
Power up (after 5 seconds) | RED |
Press OVERRIDE switch | Flash RED + ORANGE (amber) (4 seconds) |
Learning period | No LED |
Software reset | RED |
RF receive | GREEN |
No RF within last 25 minutes | RED |
Manual override (RF receive) | Flash ORANGE |
Relay state | Relay LED |
From OUT to ON (first 5 seconds) | Flash ORANGE |
ON | ORANGE |
From ON to OFF (after 5 seconds) | Flash ORANGE |
OFF | OFF |
When mounting the transmitter, attach the baseplate first. You need to mount the transmitter on a flat wall. (For details, refer to the separate mounting instructions A6V10974421.)
The transmitter comes with a fold-out stand and may be used as a “mobile” device.
Mounting the receiver does not require a baseplate. Connect the electrical connections first and then fit and secure the receiver in compliance with local regulations. (For details, refer to the separate mounting instructions A6V10974421.)
EMI filter (e.g., KEILS EMI CW4L2-3-R) can be used to reduce EMI disturbance. (For details, see Connection diagram [▶ 14].)
DANGER: Electric shock on directly touches of EMI filter
If the reference room contains thermostatic radiator valves, set them to their fully open position.
For commissioning, refer to the operating instructions A6V101035988. Communication of the RDH100RF/SET (transmitter and receiver) is paired ex factory.
Change of batteries: If the battery symbol appears, the batteries are almost empty and must be replaced.
Simultaneously press the TEST and LEARN buttons on the rear of the transmitter to reset it.
Simultaneously press the OVERRIDE and LEARN buttons to reset the receiver. This resets all individual settings to their default values.
The transmitter and receiver are maintenance-free except for the transmitter battery.
For additional details, refer to Siemens information on disposal.
Instructions for the replacement of alkaline batteries
WARNING: Explosion due to fire or short-circuit, even with discharged batteries Risk of injury due to flying parts
WARNING
Leakage of electrolyte: Severe burns
Observe the following
Topic | Title | Document ID: |
Operating | Operating instructions | A6V101035988 |
Installation | Mounting instructions | A6V10974421 |
CE declaration | A6V101123354 |
Related documents such as CE declarations, etc., can be downloaded from the following address: http://siemens.com/bt/download.
Power supply | |
Operating voltage | DC 3 V (2 x 1.5 V AA alkaline batteries) |
Battery life | >1 year (with AA alkaline batteries) |
Sensor inputs | |
Internal thermistor | 10 kΩ ± 1% at 25 °C |
Operational data | ||
PID control: Minimum period Minimum pulse length | Slow 4 min 12 min | Fast 2 min 6 min |
Setpoint setting range | 5…30 °C | |
Factory setting comfort setpoint | 20 °C |
Environmental conditions | |
Resolution of settings and displays Setpoints Actual value displays | 0.5 °C 0.5 °C |
Operation | IEC 60721-3-3 |
Climatic conditions | Class 3K5 |
Temperature | 0…+40 °C |
Humidity | <90% r.h. |
Transport | IEC 60721-3-2 |
Climatic conditions | Class 2K3 |
Temperature | -25…+60 °C |
Humidity | <95% r.h. |
Mechanical conditions | Class 2M2 |
Storage | IEC 60721-3-1 |
Climatic conditions | Class 1K3 |
Temperature | -10…+60 °C |
Humidity | <90% r.h. |
Standards, directives and approvals | |
EU conformity (CE) | A6V101123354 *) |
RCM conformity to EMC emission standard | A6V101123355 *) |
Safety class | III as per EN 60950-1 |
Pollution degree | 2 |
Degree of protection of housing | IP20 |
Environmental compatibility | The product environmental declaration (A6V101123359 *) contains data on environmentally compatible product design and assessments (RoHS compliance, materials composition, packaging, environmental benefit, disposal). |
The documents can be downloaded from: http://siemens.com/bt/download.
Eco design and labeling directives | |||
| Based on EU Regulation 813/2013 (Eco design directive) and 811/2013 (Labeling directive) concerning space heaters, the following classes apply: | ||
Application with On/Off operation of a heator | Class I | Value 1% | |
PWM (TPI) room thermostat, for use with On/Off output heaters | Class IV | Value 2% |
General | |
Weight (including package) RDH100RF/SE | 475 g |
Color of housing front | Signal-white RAL9003 |
Housing material | ABS (LCD lens:PC) |
Receiver RCR100/433
General unit data | |
Operating voltage *) | AC 230 V +10/-15% |
Power | <10 VA |
Frequency | 50…60 Hz |
EMI filter (e.g., KEILS EMI CW4L2-3-R) can be used to reduce EMI disturbance. See Connection diagram [▶ 14].
Outputs | |
Switching capacity of relays | |
Voltage Current | AC 24…250 V 8 (3) A |
No internal fuse! External preliminary protection with max. C 10 A circuit breaker required for all cases. |
Switching outputs (LX, L1, L2) | ||
Relay contacts | Switching voltage | Max. AC 250 V; Min. AC 24 V |
Switching current | Max. 8 A res., 3 A ind. | |
At AC 250 V | Min. 10 mA | |
Contact life at AC 250 V | At 5 A res. | 1 x 105 cycles (guide value) |
Insulating strength | Between relay contacts and coil | AC 5,000 V |
Between relay contacts (same pole) | AC 1,000 V |
Electrical connections | |
Connections terminals (via baseplate) For solid wires For stranded wires | Screw terminals 2 x 1.5 mm2 1 x 2.5 mm2(min. 0.5 mm2) |
Environmental conditions | |
Operation | IEC 60 721-3 |
Climatic conditions | Class 3K3 |
Temperature | 0…+45 °C |
Humidity | <85% r.h. |
Storage and transport | IEC 60 721-3 |
Climatic conditions | Class 2K3 |
Temperature | -25…+70 °C |
Humidity | <93% r.h. |
Mechanical conditions | Class 2M2 |
Standards, directives and approvals | |
EU conformity (CE) | A6V101123354 |
Safety class | II as per EN 60 730-1 |
Degree of pollution | 2 |
Color | |
Unit front | Signal-white RAL 9003 |
Base | Gray RAL 7035 |
Dimensions | 83x104x32 mm |
L – N AC 230 V / Lx – Nx AC 24…250 V | L | Live, AC 230 V |
Lx | Live, AC 24…250 V | |
L1 | N.O. contact, AC 24…250 V / 8 (3) A | |
L2 | N.C. contact, AC 24…250 V / 8 (3) A | |
PE | Protective ground | |
M1 | Circulating pump | |
N | Neutral conductor | |
Nx | Neutral conductor | |
N2 | Receiver RCR100/433 | |
Y1 | Actuating device |
| | ||
Wireless room temperature controller with receiver control of a gas-fired wall-hung boiler | Wireless room temperature controller with receiver control of atmospheric gas burner | ||
| |||
Wireless room temperature controller with receiver control of a heating circuit pump (precontrol by manual mixing valve) | |||
F1 | Thermal reset limit thermostat | N1 | Room temperature controller RDH100RF (Transmitter) |
F2 | Safety limit thermostat | N2 | RCR100/433 (Receiver) |
M1 | Circulating pump | Y1 | 3-port valve with manual adjustment |
Y2 | Magnetic valve |
Room temperature controller
Room temperature controller mounting plate
Room temperature receiver with mounting plate
Index 1) | Date | Changes |
≥C | June 2018 |
|
Z, A | March 2017 | First release. |
The product index can be found next to the production date on the rear of the device “YYMMDDX”.
© Siemens Switzerland Ltd, 2017
Technical specifications and availability subject to change without notice.
DOWNLOAD MANUALS:
SIEMENS RDH100RFSET Room thermostat Product Specifications Guide
OTHER MANUALS:
SIEMENS RDH100RF/SET Room thermostat Operating Instructions
SIEMENS RDH100RF/SET Room Thermostat Product Specifications Guide
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…