SIEMENS RDH100RF/SET Room Thermostat Operating Instructions

SIEMENS RDH100RF/SET Room Thermostat

Operating instructions

RDH100RF/SET consists of an RDH100RF wireless temperature controller and an RCR100/433 receiver. The RDH100RF allows you to set the desired room temperature (setpoint) for the desired time. The unit features an ergonomic setting knob for easy temperature control

Display

Commissioning before start-up

Commissioning

  • Remove the black transit tabs from the alkaline batteries.
  • Check to see if the battery compartment is in the correct position.
  • If no batteries are inserted, fit 2 alkaline batteries type AA in the battery compartment

Selecting the required temperature

  • Turn the setting knob counter clockwise to decrease the setpoint, or clockwise to increase the setpoint in increments of 0.5 °C
  • The required temperature is displayed next to the comfort temperature symbol

Changing the batteries

  1. Get two new batteries of type AA alkaline, 1.5 volts.
  2. Within one minute: pull out the battery compartment and remove the batteries, then insert new batteries and replace the battery compartment.
    The original set values must be checked after changing batteries!
  3. Make certain the old batteries are disposed of properly, in compliance with environmental requirements

Energy-saving tips without sacrificing comfort

  • Never allow room temperatures to exceed 21􀃛C.
  • Air out rooms: Air out rooms for short periods with open windows and doors.

RED regulation

RDH100RF/SET

  • Operating frequency: 433.94 MHz
  • Maximum Radio-Frequency power: 3.25 dBm

Siemens Switzerland Ltd. declares that the radio equipment type RDH100RF/SET is in compliance with Directive 2014/53/EU. The full text of the EU declaration of conformity is available at www.siemens.com/download?A6V10223354.

Disposal

The device is considered electrical and electronic equipment for disposal in terms of the applicable European Directive and may not be disposed of as domestic garbage.

  • Dispose of the device through channels provided for this purpose.
  • Comply with all local and currently applicable laws and regulations.
  • Dispose of empty batteries in the designated collection

Front View Receiver

LED Signal Indicator

Configuration instructions for the Siemens RDH100RF/SET

The transmitter RDH100RF and the receiver RCR100/433 are set to communicate (bonded) with each other at the factory. If they fail it is necessary to re-bond the units due to the loss of communication, please follow the below instructions.

  1. Reset the receiver by simultaneously pressing the LEARN & OVERRIDE button for 4 seconds.
  2. Press and release the LEARN button. This sets the receiver to the learn mode.
  3. Press and release the LEARN button on the back of the transmitter.
  4. A green flashing or solid LED indicates a good signal, a red flashing or solid LED indicates no signal.
  5. To test transmission, press the TEST button on the transmitter, and switch the relay on in the receiver regardless of temperature. The RF TEST symbol appears on the thermostat display.
  6. An orange LED indicates that the relay is on.

NOTE:
You can press the OVERRIDE button on the receiver to manually switch ON/OFF for a faulty room unit or transmission protocol.

NOTE:
You must re-execute the workflow for commissioning the set to reestablish a connection between the room controller and receiver.

Parameter setting

  • Parameter setting mode
    • Press LEARN on the rear for 5 seconds until “P01” appears.
    • Press LEARN again and the parameter value on the second line flashes and is ready for adjustment.
    • Adjust the parameter using the setting knob.
    • Press LEARN once to confirm the setting.
    • Rotate the setting knob clockwise to the next parameter and repeat steps 2 to 4.
    • Exit parameter setting mode by rotating the setting knob clockwise to “End” and pressing LEARN button once.
  • Parameters:
    • P01 Control behavior: 2-position 1K / 2-position 0.5 K / PID fast / PID slow (factory-setting)
    • P02 Maximum temperature range
    • P03 Minimum temperature range

Mounting and siting notes RDH100RF, RCR100/433

The units should be sited such that transmitted and received signals will be disturbed as little as possible:

  • Do not mount the units on metal surfaces
  • Do not mount the units near electrical wires or electronic equipment such as PCs, TV sets, microwave equipment, etc.
  • Do not mount the units in the vicinity of large metal structures or other construction elements with fine metal meshes like special glass or special concrete
  • The distance between the controller/transmitter and receiver should not exceed 20 m or 2 floors
  • The local regulations for electrical installations must be complied with
  • External preliminary protection with max. C 10 A circuit breaker is required in all cases
  • Make sure the RCR100/433 receiver is mounted a minimum distance of 450 mm away from the boiler
  • EMI filter (e.g., KEILS EMI CW4L2-3-R) can be used to reduce EMI disturbance

Siemens Switzerland. Ltd declares that the radio equipment types RDH100RF/SET and RDJ100RF/SET are in compliance with Directive 2014/53/ EU. The full text of the EU Declaration of Conformity is available at http://www.siemens.com/download?A6V10223354.

Issued by
Siemens Switzerland Ltd Smart Infrastructure Global Headquarters Theilerstrasse 1a CH-6300 Zug
Tel. +41 58 724 2424
www.siemens.com/buildingtechnologies
© Siemens Switzerland Ltd, 2018 Technical specifications and availability are subject to change without notice.

Contact for regulatory topics:

  • (EU) Siemens AG, Berliner Ring 23, DE-76437 Rastatt
  • (GB) Siemens plc, Sir William Siemens House, Princess Road, Manchester, M20 2UR

REFERENCE:

DOWNLOAD MANUALS:

SIEMENS RDH100RFSET Room thermostat Operating Instructions

OTHER MANUALS:

SIEMENS RDH100RF/SET Room thermostat Product Specifications Guide

SIEMENS RDH100RF/SET Room thermostat Operating Instructions

wpx_thermostats

Recent Posts

Johnson Controls T7000e LCD Digital Thermostat Installation Guide

Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide

1 year ago

Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’S GUIDE

Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE

1 year ago

Hetta HS01RF WIRELESS THERMOSTAT KIT USER MANUAL

Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…

1 year ago

HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat USER MANUAL

HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…

1 year ago

Honeywell RLV450 PROGRAMMABLE THERMOSTAT USER GUIDE

Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…

1 year ago

Honeywell RLV431 Programmable Thermostat User Guide

Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…

1 year ago