Room thermostats with KNX communications
The RDG40..KN room thermostats are designed for the following types of systems: VAV systems via On/Off or modulating control outputs or KNX LTE-Mode:
The room thermostats are delivered with a fixed set of applications.
The required application is selected and activated during commissioning using one of the following tools:
The thermostat supports the following applications, which can be configured using the DIP switches at the rear of the unit or a commissioning tool.
DIP switches 1…5 need to be set to OFF (remote configuration, factory setting) to select an application via the commissioning tool
Note
Type summary
Product No. | Features | |||||||
Operating voltage | Number of control outputs | Backlit LCD | ||||||
On/Off | PWM | 3-pos. | DC 0…10 V | VAV control via KNX LTE-Mode | IAQ | |||
RDG400KN | AC 24 V | 1 1) | 1 1) | 1 1) | 1 | ü | — | ü |
RDG405KN | AC 24 V | 1 1) | 1 1) | 1 1) | 1 | ü | ü | ü |
Selectable: On/Off, PWM or 3-position (triac outputs)
Product No. | Stock No. | Description |
RDG400KN | S55770-T165 | Room thermostat |
RDG405KN | S55770-T346 | Room thermostat |
Order valve actuators separately.
Sensors
Type of unit | Product No. | Data Sheet |
Cable temperature sensor | QAH11.1 | 1840 |
Room temperature sensor | QAA32 | 1747 |
Condensation monitor | QXA21.. | A6V10741072 |
AQR2576N.. | ||
Flush-mount KNX room sensor (base and front module) | AQR2532NNW AQR2530NNW AQR2532NNW | 1411 |
AQR2535NNWQ |
Wall-mount KNX sensor | QMX3.P30 QMX3.P70 | 1602 |
Valve actuators DC 0…10 V
Electric actuator, DC 0…10 V (for radiator valves) | SSA61.. | 4893 |
Electric actuator, DC 0…10 V (for 2- and 3-port valves/V..P45) | SSC61.. | 4895 |
Electric actuator, DC 0…10 V (for small valves 2.5 mm V..P47) | SSP61.. | 4864 |
Electric actuator, DC 0…10 V (for small valves 5.5 mm V..P45) | SSB61.. | 4891 |
Electric actuator, DC 0…10 V (for CombiValves VPI46) | SSA61.. | 4893 |
Electromotoric actuator, DC 0…10 V (for valves 5.5 mm) | SAS61.. | 4581 |
Thermal actuator, DC 0…10 V (for small valves and radiator valves) | STP63 | 4884 |
Damper actuators DC 0…10 V and 3-position, VAV compact controllers
Damper actuator DC 0…10 V, damper actuator 3-position | GQD161.. GQD131.. | 4605 | |
GDB161.. GDB131.. | 4634 | ||
GLB161.. GLB131.. | |||
GMA161.. GMA131.. | 4614 | ||
GEB161.. GEB131.. | 4621 | ||
GCA161.. GCA131.. | 4613 | ||
GBB161.. GBB131.. | 4626 | ||
GIB161.. GIB131.. | |||
VAV compact controller | GDB181.1E/3 | 3544 | |
GLB181.1E/3 |
VAV compact controllers KNX LTE-Mode
VAV compact controller for KNX LTE-Mode | GDB181.1E/KN | 3547 |
GLB181.1E/KN |
On/Off valve actuators AC 24 V
Electromotoric On/Off valve and actuator (only available in AP, UAE, SA and IN) | MVI../MXI.. | 4867 | |
Electromotoric On/Off actuator | SFA71.. | 4863 |
On/Off/PWM valve actuators AC 24 V
Thermal actuator (for radiator valves) | STA73.. | 4884 | |
Thermal actuator (for small valves 2.5 mm) | STP73.. | 4884 |
3-position valve actuators AC 24 V
An electric actuator, 3-position (for radiator valves) | SSA81.. | 4893 | |
An electric actuator, 3-position (for small valves 2.5 mm V..P47) | SSP81.. | 4864 | |
An electric actuator, 3-position (for small valves 5.5 mm V..P45) | SSB81.. | 4891 | |
An electric actuator, 3-position (for CombiValves VPI46) | SSA81.. | 4893 | |
Electromotor actuator, 3-position (for valves 5.5 mm) | SAS81.. | 4581 |
With PWM control, it is not possible to ensure exact parallel running of more than one thermal actuator. If several actuators are controlled by the same room thermostat, preference should be given to motorized actuators with On/Off or 3-position control
Note
For more information about parallel operation and the maximum number of actuators that can be used, refer to the Data Sheets of the selected type of actuator and the following listing:
Maximum number of actuators in parallel operation in connection with RDG400KN and RDG405KN:
Description | Product No./stock No. | Data Sheet*) |
KNX power supply unit 160 mA (Siemens BT LV) | 5WG1 125-1AB02 | — |
KNX power supply unit 320 mA (Siemens BT LV) | 5WG1 125-1AB12 | — |
KNX power supply unit 640 mA (Siemens BT LV) | 5WG1 125-1AB22 | — |
Documents can be downloaded from http://siemens.com/bt/download
Mechanical design
The room thermostat consists of 2 parts:
The housing engages in the mounting plate and is secured with 2 screws.
Engineering notes
See “Reference documentation” below for information on how to engineer the KNX bus (topology, bus repeaters, etc.) and how to select and size connecting cables for power supply and field devices
Do not mount on a wall in niches or bookshelves, behind curtains, above or near heat sources, or exposed to direct solar radiation. Mount about 1.5 m above the floor.
Mounting
Mount the room thermostat on a clean, dry indoor place without direct air flow from a heating/cooling device, and not exposed to drip or splash water
See Mounting Instructions M3192 (RDG400KN) or A6V10733804 (RDG405KN) enclosed with the thermostat.
Applications
The room thermostats are delivered with a fixed set of applications.
Select and activate the required application during commissioning using one of the following tools:
Set the DIP switches before snapping the unit to its mounting plate, if you want to select an application via DIP switches.
All DIP switches must be set to OFF (remote configuration), if you want to select an application via the commissioning tool.
After power is applied, the thermostat resets and all LCD segments flash, indicating that the reset was made correctly. After the reset, which takes about 3 seconds, the thermostat is ready for commissioning by qualified HVAC staff.
If all DIP switches are set to OFF, the display reads NO APPL to indicate that application commissioning via tool is required
Note
Each time the application is changed, the thermostat reloads the factory settings for all control parameters, except for KNX device and zone addresses!
Connect to
For commissioning, connect the Synco ACS or ETS tool to the KNX bus cable at any point:
ACS and ETS3 require an interface:
Note
An external KNX bus power supply is required if an RDG.. is connected directly to a tool (ACS or ETS) via KNX interface
Control parameters
The thermostat’s control parameters can be changed to ensure optimum performance of the entire system (see Basic Documentation P3192).
The parameters can be adjusted using
Control sequence
The control sequence may need to be set via P01 depending on the application. The factory setting is “Cooling only
Calibrating the sensor
Recalibrate the temperature sensor if the room temperature displayed on the thermostat does not match the room temperature measured (after min. 1 hour of operation). To do this, change P05
Setpoint and setpoint range limitation
We recommend to review the setpoints and setpoint ranges (P08…P12) and to change them as needed to ensure maximum room comfort and to save energy
Programming mode
The programming mode helps identify the thermostat in the KNX network during commissioning.
Assigning the KNX device address
Assigning the KNX group addresses
Use ETS to assign the KNX group addresses of the RDG communication objects.
KNX serial number
Each device has a unique KNX serial number inside the plastic housing. An additional sticker with the same KNX serial number is enclosed in the packaging box. This sticker is intended for installers for documentation purposes.
Disposal
The device is considered electrical and electronic equipment for disposal in terms of the applicable European Directive and may not be disposed of as domestic garbage.
Application
Dimensions in mm
© Siemens Switzerland Ltd, 2010 – 2019
Technical specifications and availability are subject to change without notice.
Issued by
Siemens Switzerland Ltd
Smart Infrastructure
Global Headquarters
Theilerstrasse 1a
CH-6300 Zug
Tel. +41 58 724 2424
www.siemens.com/buildingtechnologies
RDG40..KN Room thermostats with KNX communications
Siemens
Smart Infrastructure
DOWNLOAD MANUALS:
Siemens RDG405KN Room Thermostat Product Specifications Guide
OTHER MANUALS:
Siemens RDG405KN Room Thermostat Operating Instruction
Siemens RDG405KN Room Thermostat Product Specifications Guide
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…