For fan coil units, universal applications and compressors in DX-type equipment applications
Control application
The RDG2..KN KNX room thermostats are designed for use with the following:
Fan coil units via On/Off or modulating/DC control outputs:
Chilled/heated ceilings (or radiators) via On/Off or modulating/DC control outputs:
Compressor applications via On/Off control:
General functions
Setpoints and display
Setting
Fan
Special functions
Inputs/outputs
KNX communication features
selection for RDG20..KN
Note
Remote configuration
Remote configuration via commissioning tool (factory setting)
| ON = DIP NO.: 1…5 |
OFF = DIP NO.: 1…5 |
Product No. | Control output | Fan output |
RDG200KN, RDG204KN | PWM, On/Off, 3-pos | 3-speed, 1-speed, DC 0…10 V |
RDG260KN, RDG264KN | DC 0…10 V | 3-speed, 1-speed, DC 0…10 V |
On/Off | DC 0…10 V |
Applications for universal systems
Product No. | Control outputs |
RDG200KN, RDG204KN | On/Off, PWM, 3-position |
RDG260KN, RDG264KN | On/Off, DC 0…10 V |
Application for heat pump systems
N1 Thermostat Output Y10/Q1: Heating or heating/cooling Output Y20/Q2: Cooling only (heating/cooling) | B1 Return air temperature sensor or external room temperature sensor (optional) |
YE Electric heaters | D3 Dewpoint sensor |
Product No. | Control output | Fan |
RDG200KN, RDG204KN | On/Off | Disabled, 1-speed, 3-speed, DC 0…10 V |
RDG260KN, RDG264KN | On/Off | Disabled, DC 0…10 V |
For fan coil units, universal applications and compressors in DX-type equipment applications
Product no. | Stock no. | Housing color | Operating voltage | Fan | Number of control outputs | Built-in sensor | |||||
3-speed | DC | On/Off | PWM | 3-pos | DC | On/Off (3-wire) | T: Temperature H: Humidity CO2 | ||||
RDG200KN | S55770-T409 | White | AC 24 V or AC 230 V | ✓ | ✓ 1) | 4 | 4 | 2 | ‒ | 2 | T, H |
RDG200KN/BK | S55770-T452 | Black | AC 24 V or AC 230 V | ✓ | ✓ 1) | 4 | 4 | 2 | ‒ | 2 | T, H |
RDG204KN | S55770-T410 | White | AC 24 V or AC 230 V | ✓ | ✓ 1) | 4 | 4 | 2 | 1 | 2 | T, H, CO2 |
RDG260KN | S55770-T412 | White | AC 24 V or DC 24 V | ✓ | ✓ 1) | ‒ | ‒ | ‒ | 4 | ‒ | T, H |
‒ | ✓ 1) | 2 2) | ‒ | ‒ | ‒ | ‒ | |||||
RDG260KN/BK | S55770-T453 | Black | AC 24 V or DC 24 V | ✓ | ✓ 1) | ‒ | ‒ | ‒ | 4 | ‒ | T, H |
‒ | ✓ 1) | 2 2) | ‒ | ‒ | ‒ | ‒ | |||||
RDG264KN | S55770-T413 | White | AC 24 V or DC 24 V | ✓ | ✓ 1) | ‒ | ‒ | ‒ | 4 | ‒ | T, H, CO2 |
‒ | ✓ 1) | 2 2) | ‒ | ‒ | ‒ | ‒ |
Accessories
Type | Product/stock no. | Datasheet |
KNX power supply 160 mA (Siemens BT LV) | 5WG1 125-1AB02 | TPI_N125 |
KNX power supply 320 mA (Siemens BT LV) | 5WG1 125-1AB12 | TPI_N125 |
KNX power supply 640 mA (Siemens BT LV) | 5WG1 125-1AB22 | TPI_N125 |
Mounting adapter for RDG2..KN 1) | ARG200: S55770-T438 | – |
Ordering
Type of unit | Product no. | Datasheet *) | |
Cable temperature or changeover sensor, cable length 2.5 m NTC (3 kΩ at 25 °C) | | QAH11.1 | 1840 |
Cable temperature sensor PVC 2 m, LG- Ni1000 | | QAP22 | 1831 |
Room temperature sensor NTC (3 kΩ at 25 °C) | | QAA32 | 1747 |
Room temperature sensor LG-Ni1000 | | QAA24 | 1721 |
Front modules with passive temperature measurement LG-Ni1000 | | AQR2531ANW | 1408 |
Strap-on temperature sensor LG-Ni1000 | | QAD22 | 1801 |
Condensation monitor | | QXA21.. | A6V10741072 |
Flush-mount KNX room sensor (base and front module) | | AQR2570N.. AQR2532NNW AQR2533NNW AQR2535NNW | 1411 |
Wall-mounted KNX sensors | | QMX3.P30 QMX3.P70 | 1602 |
On/Off and PWM actuators 1)
Type of unit | Product no. | Datasheet *) |
Thermal actuator (for radiator valves) AC 230 V, NC | Under development | |
Thermal actuator (for radiator valves) AC 24 V, NC | ||
Thermal actuator AC 230 V (for small valves 2.5 mm), NO | ||
Thermal actuator AC 24 V (for small valves 2.5 mm), NO |
3-positon actuators AC 230 V
Type of unit | Product no. | Datasheet *) | |
Electric actuator, 3-position (for radiator valves) AC 230 V | SSA331.. | A6V11858276 | |
Electric actuator, 3-position (for 2- and 3- port valves/V..P45) AC 230 V | SSC31 | 4895 | |
Electric actuator, 3-position (for small valves 2.5 mm) AC 230 V | SSP31.. | 4864 | |
Electric actuator, 3-position (for small valves 5.5 mm) AC 230 V | SSB31.. | 4891 | |
Electric actuator, 3-position (for small valve 5 mm) AC 230 V | SSD31.. | 4861 |
Electric actuator, 3-position (for valves 5.5 mm) AC 230 V | SAS31.. | 4581 | |
Rotary actuators for ball valves, 3- position | GDB331.9E | 4657 | |
Rotary actuators for ball valves, 2 or 3- position | GDB141.9E GDB341.9E | A6V10636150 |
3-positon actuators AC 24 V
Type of unit | Product no. | Datasheet *) | |
Electric actuator, 3-position (for radiator valves) AC 24 V | SSA131.. | A6V11858276 | |
Electric actuator, 3-position (for 2- and 3- port valves/V..P45) AC 24 V | SSC81 | 4895 | |
Electric actuator, 3-position (for small valves 2.5 mm) AC 24 V | SSP81.. | 4864 | |
Electric actuator, 3-position (for small valves 5.5 mm) AC 24 V | SSB81.. | 4891 | |
Electric actuator, 3-position (for small valve 5 mm) AC 24 V | SSD81.. | 4861 |
On/Off actuators
Type of unit | Product no. | Datasheet *) | |
Electromotive On/Off actuator | SFA21.. SFA71.. | 4863 | |
Electromotive On/Off valve and actuator (only available in AP, UAE, SA and IN) | MVI../MXI.. | A6V11251892 | |
Zone valve actuator (only available in AP, UAE, SA and IN) | SUA | A6V10446174 |
DC 0…10 V actuators
Type of unit | Product no. | Datasheet *) | |
Electric actuator, DC 0…10 V (for radiator valves) | SSA161.. | A6V11858278 | |
Electric actuator, DC 0…10 V (for 2- and 3- port valves/V..P45) | SSC161.. | A6V12681511 | |
Electric actuator, DC 0…10 V (for small valves 2.5 mm) | SSF161.. | A6V12681511 | |
Electric actuator, DC 0…10 V (for small valves 5.5 mm) | SSB161.. | A6V12681511 |
Electromotive actuator, DC 0…10 V (for valves 5.5 mm) | SAS61.. | 4581 | |
Electrothermal actuator, AC 24 V, NC, DC 0…10 V, 1 m | Under development | ||
Electrothermal actuator, AC 24 V, NO, DC 0…10 V, 1 m | |||
Rotary actuators for ball valves AC 24 , DC 0…10 V | GDB161.9E | 4657 |
DC 0…10 V actuators 6-port / PICV (RDG26..KN)
Note: Set the control signal accordingly if RDG26.. is required to control GDB161.9E, see Control output configuration for 6-port valve in Basic documentation.
DC 0…10 V damper actuators
On/Off damper actuators 230 V
Type of unit | Product no. | Datasheet *) | |
Air damper actuators 2-position, AC 230 V | GQD32..1 | 4604 | |
GMA32..1 | 4614 |
GCA32..1 | 4613 |
On/Off damper actuators AC 24 V
Type of unit | Product no. | Datasheet *) | |
Air damper actuators 2-position, AC/DC 24 V | GQD12..1 | 4604 | |
GMA12..1 | 4614 | ||
GCA12..1 | 4613 |
KNX actuators
Type of unit | Product no. | Datasheet *) | |
Rotary actuators for ball valves KNX S-Mode | GDB111.9E/KN | A6V10725318 |
Note
For more information about the parallel operation and the max. a number of actuators that can be used, refer to the data sheets of the selected actuator type and the following list:
Max. number of actuators in parallel on RDG20..KN (AC 230 V):
Max. number of actuators in parallel on RDG20..KN (AC 24 V):
Max. number of actuators in parallel on RDG26..KN (AC 24 V):
Recommended RDG actuators and 6-port valves combinations
Use the following RDG260..KN versions (see below) to ensure the optimal temperature control performance of GDB161.9../6W actuators (with 6-port ball valves VWG41.. or 6-port PICV VWPG51..):
Check the device version compatibility in the Control output configuration for 6-port valve in Basic documentation for applications with older RDG product indices, GDB161.9E or competitor actuators.
The room thermostat consists of two parts:
The housing engages in the mounting plate and is secured with 2 screws.
Number | Description |
① | |
② | |
③ | Capacitive rotary knob to adjust setpoints and parameters |
④ | |
⑤ | |
⑥ |
Green leaf indication
Green leaf indication (green or red leaf) informs users if the equipment operates within the energy-efficient setting range (leaf is green). When the setting exceeds the preset energy efficiency range, the leaf color changes to red. End users can press the red leaf to return to energy efficiency.
The functions are defined as follows:
P110 configures the green leaf function:
Title | Document ID |
Mounting instructions | RDG200KN, RDG204KN: A6V11546008 RDG260KN, RDG264KN: A6V11844861 |
Operating instructions | A6V11545973 |
Basic documentation | A6V11545892 |
CE declarations | A5W00120120A |
RCM | A5W00120121A |
Environmental product declaration | RDG200KN: A5W00085404A RDG200KN/BK: A5W00242785A RDG204KN: A5W00242787A RDG260KN: A5W00116569A RDG260KN/BK: A5W00242797A RDG264KN: A5W00242790A |
Related documents such as environmental declarations, CE declarations, etc., can also be downloaded at the following Internet address: http://siemens.com/bt/download
CAUTION
National safety regulations
Failure to comply with national safety regulations may result in personal injury and property damage.
Mounting
Applications and settings
The room thermostats are delivered with a fixed set of applications and related parameters. Select and activate the relevant application and settings during commissioning using one of the following tools:
DIP switches
Commissioning via Siemens smartphone application PCT Go.
The setting via the Siemens smartphone application Product Commissioning Tool (PCT Go) is used to set the application and parameters settings of the thermostat. DIP switches can be either all set to Off or preset with an application. (DIP switch setting has higher priority.) This tool allows for wireless setting of the thermostat with smartphone and read/write parameters. The commissioning tool works directly after users scan either the antenna area of the thermostat or the NFC area on the individual package box.
In addition, users can:
Notes
Connect tools
ACS and ETS require an interface:
Control sequence
Factory setting:
Application | Factory setting P001 |
2-pipe and chilled/heated ceiling, and 2- stage | 1 = cooling only |
4-pipe, chilled ceiling and el. heater, 6-port ball valve applications, and 2-stage | 4 = heating and cooling |
Calibrate sensor
Recalibrate the temperature sensor, if the room temperature displayed on the thermostat does not match the room temperature measured (after min. 1 hour of operation). To do this, change parameter P006.
Setpoint and range limitation
Programming mode
Assign KNX address
Assign complete KNX address (area, line and device) via:
Set the device address to 255 to deactivate the communication (no exchange of process data).
Assign KNX group address
KNX serial number
Open Source Software (OSS)
All open-source software components used within the product (including their copyright holders and the license conditions) can be found from the website http://www.siemens.com/download?A6V12046962.
Technical data on specific applications are valid only together with Siemens products listed under “Equipment combinations”. Siemens rejects any and all warranties in the event that third-party products are used.
Power supply (RDG20..KN) | |
Operating voltage (L-N) | AC 24 V ±20 % or AC 230 V +10/-15 % (selectable via slider) |
Frequency | 50/60 Hz |
Power consumption | 4 VA @ AC 24 V 7 VA @ AC 230 V |
|
Outputs (RDG20..KN) | |
Fan control Q1, Q2, Q3 – N | AC 24 V or AC 230 V (linked to power supply) |
Qx rating min., max. resistive (inductive) | 5 mA…5 (4) A |
No internal fuse! External preliminary protection with max. C 10 A circuit breaker is required for all cases. | |
Do not connect 3-speed fans in parallel! Connect one fan directly, one relay for each speed for additional fans. | |
Use for actuator control (Q1, Q2)
| 5 mA…1 A 5 mA…1 A |
Use for external equipment (Q1, Q2, Q3)
| 5 mA…1 A 2 A |
DC 0…10 V fan control; Y50-M | SELV DC 0…10 V, max. ±5 mA |
Damper control (RDG204KN): DC (U1) On/Off (Q3/Y4) | SELV DC 0…10 V, ±1 mA See Qx and Y4 |
Control outputs Y1, Y2, Y3, Y4-N Yx power limitation | Solid state (triacs) AC 24 V or AC 230 V (linked to power supply) 8 mA…1 A 3 A fast microfuse, cannot be exchanged |
Power supply (RDG26..KN) | |
Operating voltage (G-G0) DC 24 V: Make sure to connect G to + and G0 to – | AC 24 V ±20 % DC 24 V ±2 V |
Frequency | 50/60 Hz |
Power consumption | 4 VA @ AC 24 V |
No internal fuse! External preliminary protection with max. C 10 A circuit breaker required for all cases. |
Outputs (RDG26..KN) | |
Fan control Q1/Q2/Q3/L–N | AC 24…230 V / DC 24 V |
Use for 3-speed fan control Rating min, max resistive (inductive) | AC 24…230 V: 5 mA…5 (4) A DC 24 V: 3 A |
No internal fuse! External preliminary protection with max. C 10 A circuit breaker is required for all cases. | |
Do NOT connect 3-speed fans in parallel! Connect one fan directly, for additional fans, one relay for each speed. | |
Use for actuator control (Q1, Q2)
| 5 mA…1 A 5 mA…5 (4) A 5 A |
Use for external equipment (Q1, Q2, Q3)
| 5 mA…1 A 2 A |
No internal fuse! External preliminary protection with max. C 10 A circuit breaker required for all cases. | |
DC 0…10 V fan control (Y50-M) | SELV DC 0…10 V, max. ±5 mA |
Actuator control (Y10-G0/Y20-G0/Y30-G0 (G)) | SELV DC 0…10 V, max. ±1 mA |
Damper control (RDG264KN): DC (U1) On/Off (Q3) | SELV DC 0…10 V, ±1 mA See Qx |
Multifunctional inputs | |
X1-M/X2-M/U1-M | |
Temperature sensor input | |
Type | NTC 3k |
Temperature range | -20…70 °C |
Temperature sensor input | |
Type | LG-Ni1000 |
Temperature range | -40…70 °C |
Digital input | |
Operating action | Selectable (NO/NC) |
Contact sensing | DC 0…5 V, max. 5 mA |
Insulation against mains | SELV |
KNX bus | |
Interface type | KNX, TP Uart 2 (electrically isolated) |
Bus current | 5 mA |
Bus topology: See KNX manual (“Reference documentation”) |
Operational data | |||
Switching differential, adjustable | |||
Heating mode | (P051) | 1 | K (0.5…6 K) |
Cooling mode | (P053) | 1 | K (0.5…6 K) |
P-band Xp | |||
Heating mode | (P050) | 2 | K (0.5…6 K) |
Cooling mode | (P052) | 1 | K (0.5…6 K) |
Setpoint setting and setpoint range | |||
Comfort mode | (P011) | 21 °C (5…40 °C) | |
Economy mode | (P019-P020) | 15 °C/30 °C (OFF, 5…40 °C) | |
Protection mode | (P100-P101) | 8 | °C/OFF (OFF, 5…40 °C) |
Multifunctional inputs X1/X2/U1 | Selectable (0…14) | ||
Input X1 default value | (P150) | 1 (external temperature sensor, room or return air) | |
Input X2 default value | (P153) | 0 (no function) | |
Input U1 default value | (P155) | RDG2..0KN: 3 (window contact) RDG2..4KN: 0 (no function) |
Built-in room temperature sensor | |
Measuring range | 0…49 °C |
Accuracy at 25 °C | < ±0.5 K |
Temperature calibration range | ±3 K |
Built-in humidity sensor | |
Measuring range | 10…90 % |
Accuracy (after calibration via P007) | < 5 % |
Humidity calibration range | ±10 % |
Built-in CO2 sensor | |
Measuring range | 0…5000 ppm |
Measuring accuracy at 25 °C and 1013 hPa | ±(50 ppm +4 % of measured value) |
Temperature stability in the range of 0..50 °C | 3 ppm / °C |
Long-time drift | 80 ppm over 5 years (typically) |
Time constant t63 | < 5 min |
Calibration | ASC |
Settings and display resolution | |
Setpoint | 0.5 °C |
Present temperature value displayed | 0.5 °C |
Environmental conditions | |
Storage | IEC 60721-3-1 |
Climatic conditions | Class 1K3 |
Temperature | -25…65 °C |
Humidity | < 95 % r.h. |
Transport | IEC 60721-3-2 |
Climatic conditions | Class 2K3 |
Temperature | -25…65 °C |
Humidity | < 95 % r.h. |
Mechanical conditions | Class 2M2 |
Operation | IEC 60721-3-3 |
Climatic conditions | Class 3K5 |
Temperature | 0…50 °C |
Humidity | < 95 % r.h. |
Standards and directives | |
EU conformity (CE) | A5W00120120A* |
Electronic control type | 2.B (micro-disconnection on operation) |
RCM conformity | A5W00120121A* |
Protection class | II as per EN 60730 |
Pollution class | Normal |
Degree of protection of housing | IP30 as per EN 60529 |
Eco-design and labeling directives | Based on EU directive 813/2013 (Eco design directive) and 811/2013 (Labelling directive) concerning space heaters, and combination heaters, the following classes apply: |
RDG20..KN | |
Application with On/Off | Class, I value 1 % |
operation of a heater | |
PWM (TPI) room thermo- stat, for use with On/Off | Class IV value 2 % |
output heaters | |
RDG26..KN | |
Application with On/Off | Class, I value 1 % |
operation of a heater | |
PWM (TPI) room thermostat, for use with On/Off | Class IV value 2 % |
output heaters |
Meets the requirements for eu.bac certification See product list at: http://www.eubaccert.eu/licences-by-criteria.asp | ||||
Application | Device | Actuator outputs | CA value (K) | License No. |
Fan coil units (2 pipes)
Variable speed fan | RDG20..KN | Thermal actuator | Heating 0.4 Cooling 0.3 | 220019 |
RDG26..KN | Motorized DC | Heating 0.1 Cooling 0.1 | 220020 |
Fan coil units (2 pipes,2 wires)
Variable speed fan | RDG20..KN | Thermal actuator | Heating 0.1 Cooling 0.3 | 220019 |
RDG26..KN | Motorized DC | Heating 0.1 Cooling 0.1 | 220020 | |
Fan coil units (4 pipes) Variable speed fan | RDG20..KN | Thermal actuator | Heating 0.4 Cooling 0.3 | 220019 |
RDG26..KN | Motorized DC | Heating 0.1 Cooling 0.1 | 220020 | |
Ceiling systems | RDG26..KN | Motorized DC | Heating 0.2 Cooling 0.2 | 220020 |
6-port control ball valves VWG41.10… | Heating 0.2 Cooling 0.4 | 220020 | ||
6-port control ball valves VWG41.20… | Heating 0.2 Cooling 0.4 | 220020 | ||
Environmental compatibility | The product environmental declaration (RDG200KN: A5W00085404A*, RDG260KN: A5W00116569A*, RDG200KN/BK: A5W00242785A*, RDG260KN/BK: A5W00242797A*, RDG204KN: A5W00242787A*, RDG264KN: A5W00242790A*) contains data on environmentally compatible product design and assessments (RoHS compliance, materials composition, packaging, environmental benefit, disposal). |
General | |
Connection terminals | Solid wires or stranded wires with wire-end sleeves 1 x 0.4…2.5 mm2 or 2 x 0.4…1.5 mm2 |
Minimal wiring cross-section on L, N, Q1, Q2, Q3, Y1, Y2, Y3, Y4 | Min. 1.5 mm2 |
Maximal wiring cross-section on L, N, Q1, Q2, Q3, Y1, Y2, Y3, Y4 | Max. 2.5 mm2 |
Housing font color | RAL 9016 white RAL 9011 black (RDG2..KN/BK) |
Weight without/with packaging RDG200KN / RDG200KN/BK RDG204KN RDG260KN / RDG260KN/BK RDG264KN | 266 g/336 g 270.3 g/345.9 g 242 g/311 g 269.5 g/324.6 g |
Reference documentation | Handbook for Home and Building Control – Basic Principles (EN:https://my.knx.org/shop/product?langua ge=en&product_type_category=books&prod uct_type=handbook DE: https://my.knx.org/shop/product?language=d e&product_type_category=books&product_t ype=handbook) |
SyncoTM | CE1P3127 Communication via KNX bus for Synco 700, 900 and RXB/RXL Basic documentation |
Design | CM1Y9775 Desigo RXB integration – S- Mode CM1Y9776 Desigo RXB/RXL integration – individual addressing CM1Y9777 Third-party integration CM1Y9778 Synco integration CM1Y9779 Working with ETS |
*) The documents can be downloaded from https://hit.sbt.siemens.com.
Connection terminals
RDG20..KN | |
| |
L, N | Operating voltage AC 230 V / AC 24 V |
X1, X2 | Multifunctional input for temperature sensor (NTC 3k or LG-Ni1000) or potential-free switch (function can be selected via parameter) |
U1 | Selectable input/output function:
|
M | Measuring neutral for sensors and switches |
CE+, CE- | KNX Bus + and – terminals |
Q1 | Control output for fan speed I AC 230 V / AC 24 V |
Q2 | Control output for fan speed II AC 230 V / AC 24 V |
Q3 | Control output for fan speed III AC 230 V / AC 24 V |
Q1…Q3 | Also for special functions AC 230 V / AC 24 V |
Y1…Y4 | Control outputs “Valve” AC 230 V or AC 24 V (Normally open triac, for normally closed valves), output for electric heater via external relay |
Y50 | Control output “Fan” DC 0…10 V |
RDG26..KN | |
| |
G, G0 | Operating voltage AC 24 V / DC 24 V |
L1 | Feed for relays AC 24…230 V |
X1, X2 | Multifunctional input for temperature sensor (NTC 3k or LG-Ni1000) or potential-free switch (function can be selected via parameter) |
U1 | Selectable input/output function:
|
M | Measuring neutral for sensors and switches |
CE+, CE- | KNX bus + and – terminals |
Q1 (L1) | Control output for fan speed I AC 230 V / AC 24 V |
Q2 (L1) | Control output for fan speed II AC 230 V / AC 24 V |
Q3 (L1) | Control output for fan speed III AC 230 V / AC 24 V |
Q1…Q3 (L1) | For special functions AC 24…230 V |
Y10, Y20, Y30 | Control outputs “Valve” DC 0…10 V |
Y50 | Control output “Fan” DC 0…10 V |
The connection workflow is as follows:
Notes
Note: In application “4-pipe with 6-port ball valve as changeover and PICV”, Y50 can be connected with a DC 0…10 V fan.
The fresh air damper (DC or On/Off) can be controlled via KNX S-Mode objects or directly connected to the thermostat as follows:
RDG204KN fan coil and universal (CLC, with no fan) applications with IAQ control:
FCU application | CLC app 3) | Fan 1) | H/C Control outputs signal combination | Damper signal 2) | ||
DC | 3-speed | DC | On/Off | |||
2-pipe | ✓ | ✓ |
| ✓ | ✓ | |
✓ | ✓ | ✓ | ✓ | |||
2-pipe+ RAD 2-pipe+ el. heat 2-pipe/2-stage 4-pipe | ✓ | ✓ |
| ✓ | ✓ | |
✓ | ✓ | ✓ | ||||
✓ | ✓ |
| ✓ | |||
4-pipe+ el. heater | ✓ | ✓ |
| ✓ | ✓ | |
✓ | ✓ | ✓ | ||||
✓ | ✓ |
| ✓ | |||
4-pipe/2-stage | ✓ | ✓ |
| ✓ | ✓ | |
✓ | ✓ | ✓ |
RDG264KN fan coil and universal (CLC) applications with IAQ control:
FCU application | CLC app 3) | Fan 1) | H/C Control outputs signal combination | Damper signal 2) | ||
DC | 3-speed | DC | On/Off | |||
2-pipe | ✓ | ✓ |
| ✓ | ✓ | |
✓ | ✓ | ✓ | ||||
2-pipe+ RAD 2-pipe+ el. heat 2-pipe/2-stage 4-pipe | ✓ | ✓ |
| ✓ | ✓ | |
✓ | ✓ | ✓ | ||||
4-pipe+ el. heater | ✓ | ✓ |
| ✓ | ✓ | |
✓ | ✓ | ✓ | ||||
4-pipe/2-stage | ✓ | ✓ |
| ✓ | ||
4-pipe with 6-port ball valve | ✓ |
| ✓ | ✓ | ||
4-pipe with PICV + 6-port valve as changeover | ✓ | ✓ |
| ✓ | ✓ |
Note for IAQ control on universal (CLC) heating and cooling systems
RDG2..KN
© Siemens Switzerland Ltd, 2020
Technical specifications and availability are subject to change without notice.
Document ID: A6V11545853_en–_d
Edition: 2023-02-14
DOWNLOAD MANUALS:
Siemens RDG20KN Room Thermostats Product Specifications Guide
Siemens RDG20KN Room Thermostats Product Specifications Guide
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…