Siemens RDG20KN Room Thermostats
For fan coil units, universal applications and compressors in DX-type equipment applications
- KNX bus communication (S-Mode, LTE-Mode)
- Built-in temperature, humidity and indoor air quality (CO2: RDG204KN & RDG264KN) sensor
- Control room temperature, humidity and indoor air quality (CO2: RDG204KN & RDG264KN) level
- Green leaf indication
- RDG20..KN triac control outputs for On/Off, PWM or 3-position
- RDG26..KN control outputs for DC 0…10 V or On/Off
- Fan outputs for 3-speed, 1-speed or DC 0…10 V
- 2 multifunctional inputs X1, X2 and 1 multifunctional input/output U1 for keycard, external sensor, etc.
- Operating modes: Comfort, Economy and Protection
- Automatic or manual fan speed control
- Automatic or manual heating/cooling changeover
- Commissioning via local HMI or with tools such as SyncoTM ACS or ETS
- Commissioning via Siemens smartphone application PCT Go
- Operating voltage:
- RDG20..KN: AC 24 V or AC 230 V (selectable)
- RDG26..KN: AC 24 V or DC 24 V
Functions
Control application
The RDG2..KN KNX room thermostats are designed for use with the following:
Fan coil units via On/Off or modulating/DC control outputs:
- 2-pipe system
- 2-pipe system with electric heater
- 2-pipe system with radiator/floor heating
- A 2-pipe/2-stage system also suitable for applications with 1-stage heating/ 2-stage cooling, or 2-stage heating/1-stage cooling
- 4-pipe system
- A 4-pipe system with electric heater
- 4-pipe system with a 6-port ball valve (RDG26..KN)
- 4-pipe system with 6-port PICV (RDG26..KN)
- 4-pipe system with PICV and 6-port ball valve as changeover (RDG26..KN)
- 4-pipe/2-stage system also suitable for applications with 1-stage heating/ 2-stage cooling, or 2-stage heating/1-stage cooling
Chilled/heated ceilings (or radiators) via On/Off or modulating/DC control outputs:
- Chilled/heated ceiling
- Chilled/heated ceiling with electric heater
- Chilled/heated ceiling and radiator/floor heating
- Chilled ceiling and radiator/floor heating
- Chilled and/or heated ceiling/2-stage
- Chilled/heated ceiling (4-pipe) with 6-port ball valve (RDG26..KN)
- Chilled/heated ceiling (4-pipe) with 6-port PICV (RDG26..KN)
- Chilled/heated ceiling with PICV and 6-port ball valve as changeover (RDG26..KN)
Compressor applications via On/Off control:
- Heating or cooling, compressor in DX-type equipment
- Heating or cooling, compressor in DX-type equipment with electric heater
- Heating and cooling, compressor in DX-type equipment
- Heating or cooling/2-stage, compressor in DX-type equipment
General functions
- Weekly scheduler
- M/S – manager/subordinate function between thermostats
- Room temperature control via built-in temperature sensor or external room temperature/return air temperature sensor
- Room relative humidity control via built-in humidity sensor or external room humidity sensor (humidity function can be disabled.)
- Min./max. humidity control by shifting temperature setpoint and releasing contact for the de-humidifier/humidifier
- Floor heating temperature limitation
- Min. and max. supply air temperature limitation
- Selection of operating modes via operating mode button
- Button lock for all buttons independently (automatically or manually)
- Changeover between heating and cooling mode (automatic via local sensor or bus, or manually)
- Parameters protected by password (disabled by default)
- Purge function together with 2-port valve
- Valve kick/exercising function to prevent gripping
- Reminder to clean fan filters
- Indoor air quality monitoring and controlling (CO2) via fresh air damper (RDG204KN & RDG264KN)
- Black color versions (RDG200KN/BK & RDG260KN/BK)
- Delta temperature control Limiting temperature difference between flow and return temperature for water to optimize the system and reduce energy consumption in district heating systems
Setpoints and display
- Min. and max. limitation of room temperature setpoint:
- Comfort limitation (min. and max. limitation)
- Energy saving concept (min. and max. limitation separate for heating and cooling)
- Temporary Comfort mode extension
- Green leaf indication function
- Display of current room temperature or setpoint in ℃, ℉ or both
- Absolute and relative setpoint indication
- Display of CO2 value in ppm (parts per million) or text (GOOD; POOR; BAD: RDG204KN & RDG264KN)
Setting
- Application selection via DIP switches or external commissioning software (ACS, ETS and Siemens smartphone application PCT Go)
- Parameter download with external commissioning software (ACS, ETS and Siemens smartphone application PCT Go)
- Reloading factory settings for commissioning and control parameters
Fan
- 1-speed, 3-speed or DC 0…10 V fan control on RDG20..KN and RDG26..KN (automatic or manual fan)
- Advanced fan control function, e.g. fan kick, fan start delay, selectable fan operation (enable, disable, depending on heating/cooling mode, or min. and max. speed setting)
- Fan start depending on fan coil temperature (heating) to avoid cool air while heating
- Enabling fan output only in the 2nd stage (2-pipe/2-stage, 4-pipe/2-stage)
- Switching fan speed from manual to automatic in the dead zone to avoid energy waste (selectable function)
Special functions
- Swap function for 2-pipe and 2-stage application by switching the 1st stage heating to 2nd stage cooling
- In 2-stage applications, limit the number of heating or cooling sequence to one
- Control of 6-port ball valve and for 6-port PICV, DC 0…10 V, DC 2…10 V and inverted signals DC 10…0 V, DC 10…2 V (RDG26..KN)
- Control of 6-port ball valve as changeover (On/Off – open/close signal) and PICV DC 0…10 V
- Control of 6-port ball valve via KNX S-Mode objects (RDG20..KN and RDG26..KN)
- Flow limitation function for PICV in heating and cooling mode (RDG26..KN)
- Set holiday period to reduce energy consumption during absences (holidays)
- For 6-port PICV (RDG26..KN)
- During commissioning, maximal water flow selection in l/h for heating (P260) and for cooling (P261) independently via PCT Go
- During operation, read water flow (l/h) via PCT Go live data function
- Selectable relay functions
- Switch off external equipment during Protection mode
- Switch on external equipment (e.g. pump) during heating/cooling demand
- Output status heating/cooling sequence
- Dehumidification/humidification control output
Inputs/outputs
- 2 multifunctional inputs X1, X2, and 1 multifunctional input/output U1 set as input, selectable for:
- Window contact switches operating mode to Protection
- Presence detector switches operating mode to Comfort
- Sensor for automatic heating/cooling changeover
- Switch for manual heating/cooling changeover
- External room temperature or return air temperature sensor
- Dewpoint sensor
- Enable electric heater
- Fault input
- Monitor input for temperature sensor or switch status
- Supply air temperature sensor
- Coil temperature sensor
- External temperature limit
- Hotel presence detector
- 1 multifunctional input/output U1 set automatically as output for:
- 4-pipe/2-stage as 2nd stage cooling output (RDG26..KN)
- IAQ control (damper and fan) (RDG204KN & RDG264KN)
KNX communication features
- KNX bus (terminals CE+ and CE-) for communication with Synco™ devices or KNX compatible devices
- M/S – manager/subordinate function via LTE-Mode or S-Mode to synchronize equipment and save energy in open spaces
- M/S – manager/subordinate alarm management via LTE-Mode allowing for subordinate alarm display on the manager
- Display of outside temperature, humidity, CO2 or time of day from KNX bus
- Time scheduling and central control of setpoints from KNX bus
- Control of Economy setpoints via KNX bus
- Relative humidity setpoint via KNX bus
- Control of KNX actuators and fan via S-Mode objects
- Energy supply optimization via energy demand signal via Synco™ RMB795B central control unit
- Interworking with Siemens AQR.. and QMX.. sensors for room humidity, room temperature and CO2 measurement
- Interworking with Siemens QMX.. room operator units for room humidity, room temperature and operating commands for fan, operating mode and setpoints
- Commissioning KNX area, line and device address via mobile application PCT Go
Power supply
selection for RDG20..KN
- The RDG20..KN can be powered either on AC 230 V (default) or AC 24 V.
- To select the correct power supply, use the power switch on the rear of the device.
Note
- The outputs (triacs and relays) follow the main power supply, either AC 230 V or AC 24 V.
- The device will be damaged if set to AC 24 V, but powered on AC 230 V.
Applications
Remote configuration
- The RDG2..KN room thermostats support the following applications, which can be configured using the DIP switches on the rear of the unit or via the commissioning tool.
- Set DIP switches 1…5 to Off (remote configuration, factory setting) to select an application via the commissioning tool.
Remote configuration via commissioning tool (factory setting)
|
ON =![]() DIP NO.: 1…5 |
OFF =![]() DIP NO.: 1…5 |
Applications for fan coil systems
Product No. | Control output | Fan output |
RDG200KN, RDG204KN | PWM, On/Off, 3-pos | 3-speed, 1-speed, DC 0…10 V |
RDG260KN, RDG264KN | DC 0…10 V | 3-speed, 1-speed, DC 0…10 V |
On/Off | DC 0…10 V |
Applications for universal systems
Product No. | Control outputs |
RDG200KN, RDG204KN | On/Off, PWM, 3-position |
RDG260KN, RDG264KN | On/Off, DC 0…10 V |
Application for heat pump systems
N1 Thermostat
Output Y10/Q1: Heating or heating/cooling Output Y20/Q2: Cooling only (heating/cooling) |
B1 Return air temperature sensor or external room temperature sensor (optional) |
YE Electric heaters | D3 Dewpoint sensor |
Product No. | Control output | Fan |
RDG200KN, RDG204KN | On/Off | Disabled, 1-speed, 3-speed, DC 0…10 V |
RDG260KN, RDG264KN | On/Off | Disabled, DC 0…10 V |
Type summary
For fan coil units, universal applications and compressors in DX-type equipment applications
Product no. | Stock no. | Housing color | Operating voltage | Fan | Number of control outputs | Built-in sensor | |||||
3-speed | DC | On/Off | PWM | 3-pos | DC | On/Off (3-wire) | T: Temperature H: Humidity
CO2 |
||||
RDG200KN | S55770-T409 | White | AC 24 V or AC 230 V | ✓ | ✓ 1) | 4 | 4 | 2 | ‒ | 2 |
T, H |
RDG200KN/BK | S55770-T452 | Black | AC 24 V or AC 230 V | ✓ | ✓ 1) | 4 | 4 | 2 | ‒ | 2 |
T, H |
RDG204KN | S55770-T410 | White | AC 24 V or AC 230 V | ✓ | ✓ 1) | 4 | 4 | 2 | 1 | 2 |
T, H, CO2 |
RDG260KN | S55770-T412 | White | AC 24 V or DC 24 V | ✓ | ✓ 1) | ‒ | ‒ | ‒ | 4 | ‒ |
T, H |
‒ | ✓ 1) | 2 2) | ‒ | ‒ | ‒ | ‒ | |||||
RDG260KN/BK | S55770-T453 | Black | AC 24 V or DC 24 V | ✓ | ✓ 1) | ‒ | ‒ | ‒ | 4 | ‒ |
T, H |
‒ | ✓ 1) | 2 2) | ‒ | ‒ | ‒ | ‒ | |||||
RDG264KN | S55770-T413 | White | AC 24 V or DC 24 V | ✓ | ✓ 1) | ‒ | ‒ | ‒ | 4 | ‒ |
T, H, CO2 |
‒ | ✓ 1) | 2 2) | ‒ | ‒ | ‒ | ‒ |
- The terminal Y50 is used as DC 0…10 V output.
- The output is relay On/Off.
Accessories
Type | Product/stock no. | Datasheet |
KNX power supply 160 mA (Siemens BT LV) | 5WG1 125-1AB02 | TPI_N125 |
KNX power supply 320 mA (Siemens BT LV) | 5WG1 125-1AB12 | TPI_N125 |
KNX power supply 640 mA (Siemens BT LV) | 5WG1 125-1AB22 | TPI_N125 |
Mounting adapter for RDG2..KN 1) | ARG200: S55770-T438 | – |
- ARG200 mounting adapter is used to wall-mount the RDG2..KN where a conduit box is not available. For easier wiring, removable knockouts on all sides are available. For dimensions, see Dimensions.
Ordering
- When ordering, specify both product number/stock number and name: e.g. RDG200KN / S55770-T409 room thermostat
- Order valve actuators and accessories separately.
Equipment combinations
Type of unit | Product no. | Datasheet *) | |
Cable temperature or changeover sensor, cable length 2.5 m NTC (3 kΩ at 25 °C) | ![]() |
QAH11.1 | 1840 |
Cable temperature sensor PVC 2 m, LG- Ni1000 | ![]() |
QAP22 | 1831 |
Room temperature sensor NTC (3 kΩ at
25 °C) |
![]() |
QAA32 | 1747 |
Room temperature sensor LG-Ni1000 | ![]() |
QAA24 | 1721 |
Front modules with passive temperature measurement LG-Ni1000 | ![]() |
AQR2531ANW | 1408 |
Strap-on temperature sensor LG-Ni1000 | ![]() |
QAD22 | 1801 |
Condensation monitor | ![]() |
QXA21.. | A6V10741072 |
Flush-mount KNX room sensor (base and front module) | ![]() |
AQR2570N.. AQR2532NNW AQR2533NNW AQR2535NNW | 1411 |
Wall-mounted KNX sensors | ![]() |
QMX3.P30 QMX3.P70 | 1602 |
On/Off and PWM actuators 1)
Type of unit | Product no. | Datasheet *) |
Thermal actuator (for radiator valves) AC 230 V, NC | Under development | |
Thermal actuator (for radiator valves) AC 24 V, NC | ||
Thermal actuator AC 230 V (for small valves 2.5 mm), NO | ||
Thermal actuator AC 24 V (for small valves 2.5 mm), NO |
3-positon actuators AC 230 V
Type of unit | Product no. | Datasheet *) | |
Electric actuator, 3-position (for radiator valves) AC 230 V | ![]() |
SSA331.. | A6V11858276 |
Electric actuator, 3-position (for 2- and 3- port valves/V..P45) AC 230 V | ![]() |
SSC31 | 4895 |
Electric actuator, 3-position (for small valves 2.5 mm) AC 230 V | ![]() |
SSP31.. | 4864 |
Electric actuator, 3-position (for small valves 5.5 mm) AC 230 V | ![]() |
SSB31.. | 4891 |
Electric actuator, 3-position (for small valve 5 mm) AC 230 V | ![]() |
SSD31.. | 4861 |
Electric actuator, 3-position (for valves
5.5 mm) AC 230 V |
![]() |
SAS31.. | 4581 |
Rotary actuators for ball valves, 3- position | ![]() |
GDB331.9E | 4657 |
Rotary actuators for ball valves, 2 or 3- position | ![]() |
GDB141.9E GDB341.9E | A6V10636150 |
3-positon actuators AC 24 V
Type of unit | Product no. | Datasheet *) | |
Electric actuator, 3-position (for radiator valves) AC 24 V | ![]() |
SSA131.. | A6V11858276 |
Electric actuator, 3-position (for 2- and 3- port valves/V..P45) AC 24 V | ![]() |
SSC81 | 4895 |
Electric actuator, 3-position (for small valves 2.5 mm) AC 24 V | ![]() |
SSP81.. | 4864 |
Electric actuator, 3-position (for small valves 5.5 mm) AC 24 V | ![]() |
SSB81.. | 4891 |
Electric actuator, 3-position (for small valve 5 mm) AC 24 V | ![]() |
SSD81.. | 4861 |
On/Off actuators
Type of unit | Product no. | Datasheet *) | |
Electromotive On/Off actuator | ![]() |
SFA21.. SFA71.. | 4863 |
Electromotive On/Off valve and actuator (only available in AP, UAE, SA and IN) | ![]() |
MVI../MXI.. | A6V11251892 |
Zone valve actuator (only available in AP, UAE, SA and IN) | ![]() |
SUA | A6V10446174 |
DC 0…10 V actuators
Type of unit | Product no. | Datasheet *) | |
Electric actuator, DC 0…10 V (for radiator valves) | ![]() |
SSA161.. | A6V11858278 |
Electric actuator, DC 0…10 V (for 2- and 3- port valves/V..P45) | ![]() |
SSC161.. | A6V12681511 |
Electric actuator, DC 0…10 V (for small valves 2.5 mm) | ![]() |
SSF161.. | A6V12681511 |
Electric actuator, DC 0…10 V (for small valves 5.5 mm) | ![]() |
SSB161.. | A6V12681511 |
Electromotive actuator, DC 0…10 V (for valves 5.5 mm) | ![]() |
SAS61.. | 4581 |
Electrothermal actuator, AC 24 V, NC, DC 0…10 V, 1 m | Under development | ||
Electrothermal actuator, AC 24 V, NO, DC 0…10 V, 1 m | |||
Rotary actuators for ball valves AC 24 , DC 0…10 V | ![]() |
GDB161.9E | 4657 |
DC 0…10 V actuators 6-port / PICV (RDG26..KN)
Note: Set the control signal accordingly if RDG26.. is required to control GDB161.9E, see Control output configuration for 6-port valve in Basic documentation.
DC 0…10 V damper actuators
On/Off damper actuators 230 V
Type of unit | Product no. | Datasheet *) | |
Air damper actuators 2-position, AC 230 V | ![]() |
GQD32..1 | 4604 |
![]() |
GMA32..1 | 4614 |
![]() |
GCA32..1 | 4613 |
On/Off damper actuators AC 24 V
Type of unit | Product no. | Datasheet *) | |
Air damper actuators 2-position, AC/DC 24 V | ![]() |
GQD12..1 | 4604 |
![]() |
GMA12..1 | 4614 | |
![]() |
GCA12..1 | 4613 |
KNX actuators
Type of unit | Product no. | Datasheet *) | |
Rotary actuators for ball valves KNX S-Mode | ![]() |
GDB111.9E/KN | A6V10725318 |
- The documents can be downloaded from https://hit.sbt.siemens.com
- With PWM control, exact parallel run of 2 or more thermal actuators is not possible. If several fan coil units are controlled by the same room thermostat, motorized actuators with On/Off or 3-position control are preferred.
Note
For more information about the parallel operation and the max. a number of actuators that can be used, refer to the data sheets of the selected actuator type and the following list:
Max. number of actuators in parallel on RDG20..KN (AC 230 V):
- 6 SS..31.. actuators (3-position)
- 10 SFA.., SUA.., MVI.., MXI.. On/Off actuators
- Parallel operation of SAS31 not available
Max. number of actuators in parallel on RDG20..KN (AC 24 V):
- 6 SS..31.. actuators (3-position)
- 2 SFA71.. On/Off actuators
- Parallel operation of SAS81 not available
Max. number of actuators in parallel on RDG26..KN (AC 24 V):
- 10 SS..61.. actuators (DC)
- 10 SFA.., SUA.., MVI.., MXI.. On/Off actuators
- 10 SAS61.. actuators (DC)
- 10 GDB161.9E
Recommended RDG actuators and 6-port valves combinations
Use the following RDG260..KN versions (see below) to ensure the optimal temperature control performance of GDB161.9../6W actuators (with 6-port ball valves VWG41.. or 6-port PICV VWPG51..):
- RDG26..KN.. with product index D or higher
Check the device version compatibility in the Control output configuration for 6-port valve in Basic documentation for applications with older RDG product indices, GDB161.9E or competitor actuators.
Mechanical design
The room thermostat consists of two parts:
- Plastic housing with electronics, operating elements, and room temperature sensor
- Mounting plate with screw terminals
The housing engages in the mounting plate and is secured with 2 screws.
Operation and settings
Number | Description |
① | ![]() |
② | ![]() |
③ | Capacitive rotary knob to adjust setpoints and parameters |
④ | ![]() |
⑤ | ![]() |
⑥ | ![]() |
Display
Green leaf indication
Green leaf indication (green or red leaf) informs users if the equipment operates within the energy-efficient setting range (leaf is green). When the setting exceeds the preset energy efficiency range, the leaf color changes to red. End users can press the red leaf to return to energy efficiency.
The functions are defined as follows:
- Green leaf: Settings are within the preset energy-efficiency range:
- The setpoint range is defined by the Comfort basic setpoint (P011) plus/minus the energy indicator range (P111). It applies only to the Comfort setpoint concept (P010 = 1)
- Fan speed: The manual fan is below or equal to the auto fan speed value
- Operating mode: The manual mode is lower or equal to the scheduler mode
- Red leaf: The settings exceed the preset energy-efficiency range
P110 configures the green leaf function:
- 0 = Disabled (OFF)
- 1 = Green and red dimmed down
- 2 = Green dimmed down / red fixed
- 3 = Green and red fixed
Product Documentation
Title | Document ID |
Mounting instructions | RDG200KN, RDG204KN: A6V11546008 RDG260KN, RDG264KN: A6V11844861 |
Operating instructions | A6V11545973 |
Basic documentation | A6V11545892 |
CE declarations | A5W00120120A |
RCM | A5W00120121A |
Environmental product declaration | RDG200KN: A5W00085404A RDG200KN/BK: A5W00242785A RDG204KN: A5W00242787A RDG260KN: A5W00116569A RDG260KN/BK: A5W00242797A RDG264KN: A5W00242790A |
Related documents such as environmental declarations, CE declarations, etc., can also be downloaded at the following Internet address: http://siemens.com/bt/download
Security
CAUTION
National safety regulations
Failure to comply with national safety regulations may result in personal injury and property damage.
- Observe national provisions and comply with the appropriate safety regulations.
Mounting and installation
Mounting
- The devices are suitable for wall mounting.
Warning: Do not mount the device on a metallic surface: Use mounting adapter ARG200 where this is not possible. - Recommended height: 1.5 m above the floor.
- Do not mount the devices in recesses, shelves, behind curtains or doors, or above or near heat sources.
- Avoid direct solar radiation and drafts.
- Avoid unheated (uncooled) building area such as outside walls.
- Seal the conduit box or the installation tube if any, as air currents can affect sensor readings.
- Adhere to allowed ambient conditions.
- An external room temperature sensor is recommended if the above situations cannot be avoided in the installation area.
Wiring
- Comply with local regulations to wire, protect and earth the thermostat.
Warning: No internal line protection for supply lines to external consumers (Q1, Q2, Q3, Yx or Yxx)! Risk of fire and injury due to short circuits!. - Adapt the line diameters as per local regulations to the rated value of the installed over current protection device.
- The AC 230 V mains supply line must have an external circuit breaker with a rated current of no more than 10 A.
- Properly size the cables to the thermostat, fan and valve actuators for AC 230 V mains voltage.
- Use valve actuators rated for AC 230 V / AC 24 V / DC 24 V depending on mains voltage.
- Inputs X1-M, X2-M or U1-M: Multiple switches (e.g. summer/winter switch) may be connected in parallel. Consider overall maximum contact sensing current for switch rating.
- When mains voltage is AC 230 V, SELV inputs X1-M, X2-M and U1-M use cables with min. 230 V insulation.
- Selectable relay function: Follow instructions in basic documentation A6V11545892 (Relay functions) to connect external equipment to the relay outputs.
- Disconnect thermostat from power supply before removing from the mounting plate.
- If a KNX bus power supply is connected to the line with communicating thermostats and Synco™ controller, the internal KNX power supply of the Synco™ controllers must be switched off.
Commissioning
Applications and settings
The room thermostats are delivered with a fixed set of applications and related parameters. Select and activate the relevant application and settings during commissioning using one of the following tools:
- Local DIP switches and HMI
- Synco™ ACS
- ETS5 or higher versions
- Siemens smartphone application PCT Go
DIP switches
- Set the DIP switches before snapping the thermostat to the mounting plate when selecting an application via DIP switches.
- Set all DIP switches to Off (remote configuration) when selecting an application via commissioning tool.
- After power is On, the thermostat resets and all LCD segments light up, indicating that reset is correct. After the reset of 3 seconds, the thermostat is ready for commissioning by qualified HVAC staff.
- If all DIP switches are Off, NO APPL displays, indicating that application commissioning via a tool is required.
Commissioning via Siemens smartphone application PCT Go.
The setting via the Siemens smartphone application Product Commissioning Tool (PCT Go) is used to set the application and parameters settings of the thermostat. DIP switches can be either all set to Off or preset with an application. (DIP switch setting has higher priority.) This tool allows for wireless setting of the thermostat with smartphone and read/write parameters. The commissioning tool works directly after users scan either the antenna area of the thermostat or the NFC area on the individual package box.
In addition, users can:
- Scan the antenna area without powering on the thermostat.
- Scan the NFC area without unpacking the thermostat from the individual box.
Notes
- Each time the application is changed, the thermostat reloads the factory settings for all control parameters excepting KNX device and zone addresses.
- The commissioning via Siemens smartphone application PCT Go can be disabled via parameters to avoid unexpected changes of the thermostat.
Connect tools
- Connect the Synco™ ACS or ETS tools to the KNX bus cable at any point for commissioning.
ACS and ETS require an interface:
- KNX interface (e.g. Siemens N148…)
- OCI702 USB-KNX interface
Control sequence
- Set the control sequence via parameter P001 depending on the application.
Factory setting:
Application | Factory setting P001 |
2-pipe and chilled/heated ceiling, and 2- stage | 1 = cooling only |
4-pipe, chilled ceiling and el. heater,
6-port ball valve applications, and 2-stage |
4 = heating and cooling |
Calibrate sensor
Recalibrate the temperature sensor, if the room temperature displayed on the thermostat does not match the room temperature measured (after min. 1 hour of operation). To do this, change parameter P006.
Setpoint and range limitation
- We recommend to review the setpoints and setpoint ranges (P011, P013…P016, P019, P020) and change them as needed to achieve maximum comfort and save energy.
Programming mode
- The programming mode helps identify the thermostat in the KNX network during commissioning.
- Touch both the left and right buttons simultaneously for 6 seconds to activate programming mode, indicated on the display by PROG.
- Programming mode remains active until thermostat identification is complete.
Assign KNX address
Assign complete KNX address (area, line and device) via:
- HMI or Siemens smartphone application PCT Go by setting parameters P898 (area address), P899 (line address) and P900 (device address)
- ACS or ETS (P900: device address)
Set the device address to 255 to deactivate the communication (no exchange of process data).
Assign KNX group address
- Use ETS to assign the KNX group addresses of the thermostat’s communication objects.
KNX serial number
- Each device has a unique KNX serial number on the rear.
- An additional sticker with the same KNX serial number is enclosed in the package. This sticker is intended for the documentation purposes of installers.
Disposal
This symbol or any other national label indicates that the product, its packaging, and, where applicable, any batteries may not be disposed of as domestic waste. Delete all personal data and dispose of the item(s) at separate collection and recycling facilities in accordance with local and national legislation. For additional details, refer to Siemens’s information on disposal.
Open Source Software (OSS)
All open-source software components used within the product (including their copyright holders and the license conditions) can be found from the website http://www.siemens.com/download?A6V12046962.
Warranty
Technical data on specific applications are valid only together with Siemens products listed under “Equipment combinations”. Siemens rejects any and all warranties in the event that third-party products are used.
Technical data
Power supply (RDG20..KN) | |
Operating voltage (L-N) | AC 24 V ±20 % or
AC 230 V +10/-15 % (selectable via slider) |
Frequency | 50/60 Hz |
Power consumption | 4 VA @ AC 24 V
7 VA @ AC 230 V |
![]()
|
Outputs (RDG20..KN) | |
Fan control Q1, Q2, Q3 – N | AC 24 V or AC 230 V (linked to power supply) |
Qx rating min., max. resistive (inductive) | 5 mA…5 (4) A |
![]() No internal fuse! External preliminary protection with max. C 10 A circuit breaker is required for all cases. |
|
Do not connect 3-speed fans in parallel! Connect one fan directly, one relay for each speed for additional fans. |
|
Use for actuator control (Q1, Q2)
|
5 mA…1 A
5 mA…1 A |
Use for external equipment (Q1, Q2, Q3)
|
5 mA…1 A
2 A |
DC 0…10 V fan control; Y50-M | SELV DC 0…10 V, max. ±5 mA |
Damper control (RDG204KN): DC (U1)
On/Off (Q3/Y4) |
SELV DC 0…10 V, ±1 mA See Qx and Y4 |
Control outputs
Y1, Y2, Y3, Y4-N Yx power limitation |
Solid state (triacs)
AC 24 V or AC 230 V (linked to power supply) 8 mA…1 A 3 A fast microfuse, cannot be exchanged |
Power supply (RDG26..KN) | |
Operating voltage (G-G0)
DC 24 V: Make sure to connect G to + and G0 to – |
AC 24 V ±20 %
DC 24 V ±2 V |
Frequency | 50/60 Hz |
Power consumption | 4 VA @ AC 24 V |
![]() No internal fuse! External preliminary protection with max. C 10 A circuit breaker required for all cases. |
Outputs (RDG26..KN) | |
Fan control Q1/Q2/Q3/L–N | AC 24…230 V / DC 24 V |
Use for 3-speed fan control
Rating min, max resistive (inductive) |
AC 24…230 V: 5 mA…5 (4) A DC 24 V: 3 A |
No internal fuse! External preliminary protection with max. C 10 A circuit breaker is required for all cases. |
|
Do NOT connect 3-speed fans in parallel! Connect one fan directly, for additional fans, one relay for each speed. |
|
Use for actuator control (Q1, Q2)
|
5 mA…1 A 5 mA…5 (4) A 5 A |
Use for external equipment (Q1, Q2, Q3)
|
5 mA…1 A 2 A |
![]() No internal fuse! External preliminary protection with max. C 10 A circuit breaker required for all cases. |
|
DC 0…10 V fan control (Y50-M) | SELV DC 0…10 V, max. ±5 mA |
Actuator control (Y10-G0/Y20-G0/Y30-G0 (G)) | SELV DC 0…10 V, max. ±1 mA |
Damper control (RDG264KN): DC (U1)
On/Off (Q3) |
SELV DC 0…10 V, ±1 mA See Qx |
Multifunctional inputs | |
X1-M/X2-M/U1-M | |
Temperature sensor input | |
Type | NTC 3k |
Temperature range | -20…70 °C |
Temperature sensor input | |
Type | LG-Ni1000 |
Temperature range | -40…70 °C |
Digital input | |
Operating action | Selectable (NO/NC) |
Contact sensing | DC 0…5 V, max. 5 mA |
Insulation against mains | SELV |
KNX bus | |
Interface type | KNX, TP Uart 2 (electrically isolated) |
Bus current | 5 mA |
Bus topology: See KNX manual (“Reference documentation”) |
Operational data | |||
Switching differential, adjustable | |||
Heating mode | (P051) | 1 | K (0.5…6 K) |
Cooling mode | (P053) | 1 | K (0.5…6 K) |
P-band Xp | |||
Heating mode | (P050) | 2 | K (0.5…6 K) |
Cooling mode | (P052) | 1 | K (0.5…6 K) |
Setpoint setting and setpoint range | |||
Comfort mode | (P011) | 21 °C (5…40 °C) | |
Economy mode | (P019-P020) | 15 °C/30 °C (OFF, 5…40 °C) | |
Protection mode | (P100-P101) | 8 | °C/OFF (OFF, 5…40 °C) |
Multifunctional inputs X1/X2/U1 | Selectable (0…14) | ||
Input X1 default value | (P150) | 1 (external temperature sensor, room or return air) | |
Input X2 default value | (P153) | 0 (no function) | |
Input U1 default value | (P155) | RDG2..0KN: 3 (window contact) RDG2..4KN: 0 (no function) |
Built-in room temperature sensor | |
Measuring range | 0…49 °C |
Accuracy at 25 °C | < ±0.5 K |
Temperature calibration range | ±3 K |
Built-in humidity sensor | |
Measuring range | 10…90 % |
Accuracy (after calibration via P007) | < 5 % |
Humidity calibration range | ±10 % |
Built-in CO2 sensor | |
Measuring range | 0…5000 ppm |
Measuring accuracy at 25 °C and 1013 hPa | ±(50 ppm +4 % of measured value) |
Temperature stability in the range of 0..50 °C |
3 ppm / °C |
Long-time drift | 80 ppm over 5 years (typically) |
Time constant t63 | < 5 min |
Calibration | ASC |
Settings and display resolution | |
Setpoint | 0.5 °C |
Present temperature value displayed | 0.5 °C |
Environmental conditions | |
Storage | IEC 60721-3-1 |
Climatic conditions | Class 1K3 |
Temperature | -25…65 °C |
Humidity | < 95 % r.h. |
Transport | IEC 60721-3-2 |
Climatic conditions | Class 2K3 |
Temperature | -25…65 °C |
Humidity | < 95 % r.h. |
Mechanical conditions | Class 2M2 |
Operation | IEC 60721-3-3 |
Climatic conditions | Class 3K5 |
Temperature | 0…50 °C |
Humidity | < 95 % r.h. |
Standards and directives | |
EU conformity (CE) | A5W00120120A* |
Electronic control type | 2.B (micro-disconnection on operation) |
RCM conformity | A5W00120121A* |
Protection class | II as per EN 60730 |
Pollution class | Normal |
Degree of protection of housing | IP30 as per EN 60529 |
Eco-design and labeling directives | Based on EU directive 813/2013 (Eco design directive) and 811/2013 (Labelling directive) concerning space heaters, and combination heaters, the following classes apply: |
RDG20..KN | |
Application with On/Off | Class, I value 1 % |
operation of a heater | |
PWM (TPI) room thermo- stat, for use with On/Off | Class IV value 2 % |
output heaters | |
RDG26..KN | |
Application with On/Off | Class, I value 1 % |
operation of a heater | |
PWM (TPI) room thermostat, for use with On/Off | Class IV value 2 % |
output heaters |
Meets the requirements for eu.bac certification See product list at: http://www.eubaccert.eu/licences-by-criteria.asp
|
||||
Application | Device | Actuator outputs | CA value (K) | License No. |
Fan coil units (2 pipes)
Variable speed fan |
RDG20..KN | Thermal actuator | Heating 0.4 Cooling 0.3 |
220019 |
RDG26..KN | Motorized DC | Heating 0.1 Cooling 0.1 |
220020 |
Fan coil units
(2 pipes,2 wires)
Variable speed fan |
RDG20..KN | Thermal actuator | Heating 0.1 Cooling 0.3 |
220019 |
RDG26..KN | Motorized DC | Heating 0.1 Cooling 0.1 |
220020 | |
Fan coil units (4 pipes) Variable speed fan | RDG20..KN | Thermal actuator | Heating 0.4 Cooling 0.3 |
220019 |
RDG26..KN | Motorized DC | Heating 0.1 Cooling 0.1 |
220020 | |
Ceiling systems | RDG26..KN | Motorized DC | Heating 0.2 Cooling 0.2 |
220020 |
6-port control ball valves VWG41.10… | Heating 0.2 Cooling 0.4 |
220020 | ||
6-port control ball valves VWG41.20… | Heating 0.2 Cooling 0.4 |
220020 | ||
Environmental compatibility | The product environmental declaration (RDG200KN: A5W00085404A*, RDG260KN: A5W00116569A*, RDG200KN/BK: A5W00242785A*, RDG260KN/BK: A5W00242797A*, RDG204KN: A5W00242787A*, RDG264KN: A5W00242790A*) contains data on environmentally compatible product design and assessments (RoHS compliance, materials composition, packaging, environmental benefit, disposal). |
General | |
Connection terminals | Solid wires or stranded wires with wire-end sleeves 1 x 0.4…2.5 mm2 or 2 x 0.4…1.5 mm2 |
Minimal wiring cross-section on L, N, Q1, Q2, Q3, Y1, Y2, Y3, Y4 | Min. 1.5 mm2 |
Maximal wiring cross-section on L, N, Q1, Q2, Q3, Y1, Y2, Y3, Y4 | Max. 2.5 mm2 |
Housing font color | RAL 9016 white RAL 9011 black (RDG2..KN/BK) |
Weight without/with packaging RDG200KN / RDG200KN/BK RDG204KN RDG260KN / RDG260KN/BK RDG264KN | 266 g/336 g 270.3 g/345.9 g 242 g/311 g 269.5 g/324.6 g |
Reference documentation | Handbook for Home and Building Control – Basic Principles (EN:https://my.knx.org/shop/product?langua ge=en&product_type_category=books&prod uct_type=handbook
DE: https://my.knx.org/shop/product?language=d e&product_type_category=books&product_t ype=handbook) |
SyncoTM | CE1P3127 Communication via KNX bus for Synco 700, 900 and RXB/RXL Basic documentation |
Design | CM1Y9775 Desigo RXB integration – S- Mode CM1Y9776 Desigo RXB/RXL integration – individual addressing CM1Y9777 Third-party integration CM1Y9778 Synco integration CM1Y9779 Working with ETS |
*) The documents can be downloaded from https://hit.sbt.siemens.com.
Diagrams
Connection terminals
RDG20..KN | |
![]()
|
|
L, N | Operating voltage AC 230 V / AC 24 V |
X1, X2 | Multifunctional input for temperature sensor (NTC 3k or LG-Ni1000) or potential-free switch (function can be selected via parameter) |
U1 | Selectable input/output function:
|
M | Measuring neutral for sensors and switches |
CE+, CE- | KNX Bus + and – terminals |
Q1 | Control output for fan speed I AC 230 V / AC 24 V |
Q2 | Control output for fan speed II AC 230 V / AC 24 V |
Q3 | Control output for fan speed III AC 230 V / AC 24 V |
Q1…Q3 | Also for special functions AC 230 V / AC 24 V |
Y1…Y4 | Control outputs “Valve” AC 230 V or AC 24 V (Normally open triac, for normally closed valves), output for electric heater via external relay |
Y50 | Control output “Fan” DC 0…10 V |
RDG26..KN | |
|
|
G, G0 | Operating voltage AC 24 V / DC 24 V |
L1 | Feed for relays AC 24…230 V |
X1, X2 | Multifunctional input for temperature sensor (NTC 3k or LG-Ni1000) or potential-free switch (function can be selected via parameter) |
U1 | Selectable input/output function:
|
M | Measuring neutral for sensors and switches |
CE+, CE- | KNX bus + and – terminals |
Q1 (L1) | Control output for fan speed I AC 230 V / AC 24 V |
Q2 (L1) | Control output for fan speed II AC 230 V / AC 24 V |
Q3 (L1) | Control output for fan speed III AC 230 V / AC 24 V |
Q1…Q3 (L1) | For special functions AC 24…230 V |
Y10, Y20, Y30 | Control outputs “Valve” DC 0…10 V |
Y50 | Control output “Fan” DC 0…10 V |
Connection diagrams
The connection workflow is as follows:
- Select fan control type: DC, 1-speed or 3-speed fan
- Select application type, e.g. 4-pipe
- Columns V1, V2, V3, V4 show the type of the outputs (e.g. for 4-pipe: YH for heating and YC for cooling) as well the available control signals
- Select the requested control output signals (e.g. 2-pos for heating, 2-pos for cooling)
- Equipments V1, V2 etc. stands for the connected equipment on each terminal, e.g. 4-pipe with outputs of 2-pos and 2-pos, V1 (valve actuator) connects to Y1 and V2 (valve actuator) to Y2
Notes
- “2-pos” can be used for control signal On/Off and PWM
- For universal application, fan function needs to be switched off via P350
- N1: Room thermostat RDG20..KN
- S1, S2, S3: Switch (keycard, window contact, presence detector etc.)
- V1, V2, V3, V4, Valve actuators: On/Off or PWM, 3-position, heating, cooling, radiator, heating/cooling, 1st or 2nd stage
- YE: Electric heater
- K: Relay
- CE+: KNX data +
- CE-: KNX data –
- M1: 1-speed or 3-speed fan, DC 0…10 V fan
- B1, B2, B3: Temperature sensor (return air temperature, external room temperature, changeover sensor, etc.)
- YH: Heating valve actuator
- YC: Cooling valve actuator
- YHC: Heating/cooling valve actuator
- YR: Radiator valve actuator
- YHC1/YH1/ YH2/YHC2/ YC1/YC2: 1st/2nd stage
- N1: Room thermostat RDG26..KN
- S1, S2, S3: Switch (keycard, window contact, presence detector etc.)
- YE: Electric heater
- YH: Heating valve actuator
- YC: Cooling valve actuator
- CE+: KNX data +
- CE-: KNX data –
- M1: 1-speed or 3-speed fan, DC 0…10 V fan
- V1, V2, V3, V4 Valves actuators: On/Off or DC 0…10 V, heating, cooling, radiator, heating/cooling, 1st or 2nd stage
- B1, B2, B3: Temperature sensor (return air temperature, external room temperature, changeover sensor, etc.)
- YHC: Heating/cooling valve actuator
- YR: Radiator valve actuator
- YHC1/YH1/YH2/ YHC2/YC1/YC2: 1st/2nd stage
- N2: Room thermostat RDG26..KN
- S1, S2, S3: Switch (keycard, window contact, presence detector etc.)
- B1, B2, B3: Temperature sensor (return air temperature, external room temperature, changeover sensor, etc.)
- CE-: KNX data –
- V3: 6-port modulating control actuator
- V4: PICV control valve
- M1: 1-speed or 3-speed fan, DC 0…10 V fan
- CE+: KNX data +
Note: In application “4-pipe with 6-port ball valve as changeover and PICV”, Y50 can be connected with a DC 0…10 V fan.
IAQ – CO2 connection diagrams
The fresh air damper (DC or On/Off) can be controlled via KNX S-Mode objects or directly connected to the thermostat as follows:
- DC damper is connected to terminal U1
- ON/Off damper is connected to terminal Q3 (relay output). Exception: RDG204KN, for applications with 3-speed fan: terminal Y4 (triac output)
RDG204KN fan coil and universal (CLC, with no fan) applications with IAQ control:
FCU
application |
CLC
app 3) |
Fan 1) | H/C Control outputs signal combination | Damper signal 2) | ||
DC | 3-speed | DC | On/Off | |||
2-pipe | ✓ | ✓ |
|
✓ | ✓ | |
✓ | ✓ | ✓ | ✓ | |||
2-pipe+ RAD
2-pipe+ el. heat 2-pipe/2-stage 4-pipe |
✓ | ✓ |
|
✓ | ✓ | |
✓ | ✓ | ✓ | ||||
✓ | ✓ |
|
✓ | |||
4-pipe+ el. heater | ✓ | ✓ |
|
✓ | ✓ | |
✓ | ✓ | ✓ | ||||
✓ | ✓ |
|
✓ | |||
4-pipe/2-stage | ✓ | ✓ |
|
✓ | ✓ | |
✓ | ✓ | ✓ |
RDG264KN fan coil and universal (CLC) applications with IAQ control:
FCU
application |
CLC
app 3) |
Fan 1) | H/C Control outputs signal combination | Damper signal 2) | ||
DC | 3-speed | DC | On/Off | |||
2-pipe | ✓ | ✓ |
|
✓ | ✓ | |
✓ | ✓ | ✓ | ||||
2-pipe+ RAD
2-pipe+ el. heat 2-pipe/2-stage 4-pipe |
✓ | ✓ |
|
✓ | ✓ | |
✓ | ✓ | ✓ | ||||
4-pipe+ el. heater | ✓ | ✓ |
|
✓ | ✓ | |
✓ | ✓ | ✓ | ||||
4-pipe/2-stage | ✓ | ✓ |
|
✓ | ||
4-pipe with 6-port ball valve | ✓ |
|
✓ | ✓ | ||
4-pipe with PICV + 6-port valve as changeover | ✓ | ✓ |
|
✓ | ✓ |
- Selectable via P351 (Fan speeds)
- Selectable via P453 (Indoor air quality damper)
- Universal (CLC) applications can be set by switching off the fan functions (P350 = 0)
Note for IAQ control on universal (CLC) heating and cooling systems
- The application can be set as per Applications for universal systems [➙ 6] and by switching off the fan function (P350 = 0).
- On applications without fan control, the thermostat controls the position of the damper when the IAQ setpoint P023 is exceeded. An independent fresh air system guarantees fresh air flow to the room.
- See the possible combinations of applications, control signals and damper types in the above table for RDG204KN and RDG264KN.
- The frost protection function is not available on universal applications.
Dimensions
RDG2..KN
Issued by
- Siemens Switzerland Ltd Smart Infrastructure
- Global Headquarters
- Theilerstrasse 1a CH-6300 Zug
- +41 58 724 2424
- www.siemens.com/buildingtechnologies
© Siemens Switzerland Ltd, 2020
Technical specifications and availability are subject to change without notice.
Document ID: A6V11545853_en–_d
Edition: 2023-02-14