Download via ETS
Local via Dip Switches
CONFIGURE PARAMETERS via WIZARD
Note: Refer to
IF UNIT in PROTECTION MODE
CHANGE ROOM TEMPERATURE SETPOINT
ADJUST FAN MODE / FAN SPEED
CHANGE OPERATING MODES
SELECT ADDITIONAL INFO
MANUAL HEAT/COOL CHANGEOVER (P01=2)
| FUNCTION DESCRIPTIONS | RANGE | FACTORY SETTINGS | |
| P01 | Control Sequence (RDF800… only) | 0: Heating only 1: Cooling only 2: Manual changeover 3: Auto changeover 4: Heating and Cooling | 2-pipe = 1 4-pipe = 4 |
| P02 | User Operating Mode Profile | 1: COMF > PROT 2: COMF > ECON > PROT | 1 |
| P04 | Selection of °C or °F | 0: °C 1: °F | 0 |
| P05 | Sensor Calibration | -3…3 K | 0 K |
| P06 | Standard Display | 0: Room temperature 1: Setpoint | 0 |
| P07 | Display Info Line (2nd Line of LCD Display) | 0: — (No display) 3: Time of day (12h) via bus 4: Time of day (24h) via bus | 0 |
| P08 | Comfort Setpoint | 5…40 °C | 21 °C |
| P09 | Comfort Min. Setpoint | 5…40 °C | 5 °C |
| P10 | Comfort Max. Setpoint | 5…40 °C | 35 °C |
| P11 | Econ Heating Setpoint | OFF, 5…WcoolEco WcoolEco = 40°C Max. | 15 °C |
| P12 | Econ Cooling Setpoint (RDF800… only) | OFF, WheatEco…40°C WheatEco = 5°C Min. | 30 °C |
| P13 | Electric Heater in Cooling Mode (RDF800… only) | ON: Enabled OFF: Disabled | ON |
| P14 | Keylock Function | 0: Unlock 1: Total lock 2: Setpoint | 0 |
| P15 | Fan Stage in Deadzone (Comfort Mode) (RDF800… only) | 0: Fan OFF 1: Fan speed 1 Heat / Cool 2: Fan speed 1 Cool only | 0 |
| P16 | Buzzer Function | OFF: Disable ON: Enable | ON |
Installer Level Control Parameters
| P38 P40 | Functionality of X1 and X2
| 0: — No function 1: Ext / Return Temp (AI) 2: H/C changeover (AI/DI) 3: Window open detect (DI) 4: Dew point sensor (DI) 5: Enable electr. Heater (DI) 6: Fault input (DI) 7: Monitor input (Digital) 8: Monitor input (Temp) 10: Presence detection (DI) | P38 X1 = 3
P40 X2 = 1 |
| P39 P41 | Operating action of X1, X2 as digital inputs | NO: Normally Open / Open NC: Normally Close / Close | P39: X1=NO P41: X2=NO |
| P71 | Reload factory setting | OFF: Disable ON: Reload Start | OFF |
ALARMS & SERVICE REMINDERS (IF ANY)
| PRIORITY | ALARM/SERVICE | DISPLAY | ERROR CODE | TYPE |
| 1 | Bus Power Supply | BUS | 5000 | Fault |
| 2 | Condensation | CON | 4930 | |
| 3 | Ext Fault Input 1 | AL1 | 9001 | |
| 4 | Ext Fault Input 2 | AL2 | 9002 | |
| 5 | Clean Filter Reminder (Use + / – to remove reminder) | FIL | 3911 | Service |
2-pipe, 3 position output
4-pipe fan coil
2-pipe & el. heater
2-pipe fan coil
RDF800KN/NF, RDD810KN/NF
RDF800KN
Issued by
Siemens Switzerland Ltd
Smart Infrastructure
Global Headquarters
Theilerstrasse 1a
CH-6300 Zug
Tel. +41 58 724 2424
www.siemens.com/buildingtechnologies
© Siemens Switzerland Ltd, 2014 – 2022 Technical specifications and availability subject to change without notice.
Touch Room Thermostats Installation Instructions
DOWNLOAD MANUAL:
Siemens RDF800KN Touch Screen Room Thermostats Operating Instruction
OTHER MANUALS:
Siemens RDF800KN Touch Screen Room Thermostats Product Specifications Guide
Siemens RDF800KN Touch Screen Room Thermostats Operating Instruction
Free Money Online Casino No Deposit Canada However, and players have no control over it.…
Eureka Casino No Deposit Bonus Codes For Free Spins 2026 Furthermore, and beginner-friendly as well.…
Top 10 Online Canada Casinos Top 10 online canada casinos you can contact Easy Slots'…
2026 Canada Changes In Blackjack 2026 canada changes in blackjack an online casino reload bonus…
Mannheim Casino No Deposit Bonus Codes For Free Spins 2026 Don't miss out on this…
Slot Games For Real Money I should start with a variety of gambling options, you…