Applications
Room temperature control (heating or cooling) in individual rooms and zones by means of:
The room thermostat controls:
Used in systems with:
The room thermostat is delivered with a fixed set of applications. The relevant application is selected and activated during commissioning using one of the following tools:
Functions
Product no. | Stock no. | Operating voltage | Control outputs | Fan types | Backlit LCD | Input | Suitable conduit box | Color | |||
On/Off | 3-pos | DC 0…10 V | 3-speed | DC 0…10 V | |||||||
RDF660MB/ MM | S55770- T433 | AC 230 V | ✓ | ✓ | – | – | ✓ | ✓ | Basic B1, S1 | Square or round | White |
RDF660MB | S55770- T439 | AC 230 V | ✓ | ✓ | – | – | ✓ | ✓ | Basic X1, X2 | Square or round | White |
Ordering
When ordering, specify both product number/stock number and name: e.g. RDF660MB/MM / S55770-T433 Modbus room thermostat Order valve actuators and accessories separately
Accessories
Equipment combinations
On/Off actuators
.3-position actuators
Mechanical design
The thermostats consist of 2 parts:
Operation and settings
Product Documentation
Title | Document ID |
Operating instructions | A6V12060783 |
Basic documentation | A6V12114068 |
CE declarations | A5W00156993A |
RCM | A5W00156996A |
Environmental product declaration | A5W00139322A |
Engineering
Mounting
Wiring
Operating mode
In Protection mode, press any button to activate the screen, then press the mode button to change to another operating mode.
Applications
Display “NONE”:
If “NONE” is displayed on the LCD, the DIP switches are set to OFF-OFF-OFF for remote configuration, but the application has not yet been assigned to the device. The application can be set using commissioning tools via RS485 Modbus.
The thermostat’s control parameters can be set to ensure optimum performance of the entire system. The parameters can be adjusted via
Control sequence
The control sequence may need to be set via parameter P01 depending on the application. The factory setting for the 2-pipe application is “Cooling only”; and “Heating and cooling” for the 4-pipe application.
Compressor-based application
When the thermostat is used with a compressor, adjust the minimum output On-time (P48) and Off-time (P49) for Y1/Y2 to avoid damaging the compressor or shortening its life due to frequent switching
Calibrate sensor
Recalibrate the temperature sensor if the room temperature displayed on the thermostat does not match the room temperature measured (after minimum 1 hour of operation). To do this, change P05.
Setpoint and range limitation
We recommend reviewing the setpoints and setpoint ranges (P08…P12) and changing them as needed to achieve maximum comfort and save energy
Disposal
This symbol or any other national label indicate that the product, its packaging, and, where applicable, any batteries may not be disposed of as domestic waste. Delete all personal data and dispose of the item(s) at separate collection and recycling facilities in accordance with local and national legislation. For additional details, refer to www.siemens.com/bt/disposal.
Open Source Software (OSS)
All open source software components used within the product (including their copyright holders and the license conditions) can be found from the website https://www.siemens.com/download?A6V11893104.
Technical data on specific applications are valid only together with Siemens products listed under “Equipment combinations”. Siemens rejects any and all warranties in the event that third-party products are used.
Power supply | |
Operating voltage | AC 230 V +10/-15 % |
Frequency | 50/60 Hz |
Power consumption | 9 VA |
●No internal fuse! External preliminary protection with max. C 10 A circuit breaker is required in all cases. |
Outputs | |
DC fan control DC 0…10 V; Y50 | SELV DC 0…10 V, max. 5 mA |
Control output Y1-N / Y2-N (N.O.) Rating | AC 230 V Max. 5(2) A |
Multifunctional inputs | |
S1 (X2)-M/B1 (X1)-M | |
Temperature sensor input | |
Type | NTC (3 kΩ at 25 °C) |
Temperature range | 0…49 °C |
Cable length | Max. 80 m |
Digital input | |
Operating action | Selectable (NO/NC) |
Contact sensing | SELV DC 0…3.3 V, max. 1 mA |
Parallel connection of several thermostats for one switch | Max. 20 thermostats per switch |
Insulation against mains voltage (SELV) | III (4 kV), reinforced insulation |
Modbus | |
Interface type | RS485 Modbus RTU Wire (ref.): 16 AWG, 1 pair, shielded serial line with 1.5 mm2 and length < 1200 m |
Bus Current | Max. 50 mA |
Bus topology: See Modbus manual (Modbus over serial line specification and implementation guide from http://www.modbus.org) |
Operational data | |
Switching differential, adjustable | |
Heating (P30) | 2 K (0.5…6 K) |
Cooling (P31) | 1 K (0.5…6 K) |
Setpoint setting and setpoint range | |
Comfort (P08) | 21 °C (5…40 °C) |
Economy (P11-P12) | 15 °C/30 °C (OFF, 5…40 °C) |
Protection (P65-P66) | 8 °C/OFF (OFF, 5…40 °C) |
Multifunctional input B1 (RDF660MB/MM only) | Selectable (0, 1, 2, 9) |
Input default value (P38) | 9: H/C changeover (DI) |
Multifunctional input S1 (RDF660MB/MM only) | Selectable (0, 3, 10, 11) |
Input default value (P40) | 3: Window contact (DI) |
Multifunctional inputs X1/X2 (RDF660MB only) | Selectable (0…11) |
Input X1 | 3 (P38) Window contact (DI) |
Input X2 | 1 (P40) External temperature sensor |
Built-in room temperature sensor | |
Measuring range | 0…49 °C |
Accuracy at 25 °C | < ±0.5 K |
Temperature calibration range | ±5 K |
Settings and display resolution | |
Setpoint | 0.5 °C |
Current temperature value displayed | 0.5 °C |
Environmental conditions | |
Storage | IEC 60721-3-1 |
Climatic conditions | Class 1K3 |
Transport | IEC 60721-3-2 |
Climatic conditions | Class 2K3 |
Operation | IEC 60721-3-3 |
Climatic conditions | Class 3K5 1) |
Standards and directives | |
EU conformity (CE) | A5W00156993A* |
RCM conformity | A5W00156996A* |
Safety class | II as per EN 60730-1 |
Pollution class | Class 2 |
Degree of protection of housing | IP30 as per EN 60529 |
Housing flammability class according to UL94 | V-0 |
Environmental compatibility | The product environmental declaration (A5W00139322A *) contains data on environmentally compatible product design and assessments (RoHS compliance, materials composition, packaging, environmental benefit, disposal). |
General | |
Connection terminals | Solid wires or prepared stranded wires 1 x 0.4…1.5 mm2 |
Housing front color | RAL 9003 white |
Weight without/with packaging | 148 g/241 g |
Connection terminals
Connection diagrams
Application examples
The thermostats support the following applications, that can be configured using the DIP switches inside the front panel of the unit or a Modbus commissioning tool.
Applications for fan coil systems
Application and output signal, DIP switches, diagram
Application for heat pump systems
Issued by
DOWNLOAD MANUALS:
Siemens RDF660MB Flush Mount Room Thermostat Product Specifications Guide
Other manuals:
Siemens RDF660MB Flush Mount Room Thermostat Operating Instruction
Siemens RDF660MB Flush Mount Room Thermostat Product Specifications Guide
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…