Change room temperature
Adjust fan speed / fan mode
Change thermostat operating mode
Change from heating to cooling mode
Temporary timer to extend the Comfort mode
Operate switching groups
Button lock
Reminder to clean filters and for external faults
Note: Economy mode
You can adjust a number of different control parameters to adapt the thermostat to your system and optimize control performance. You can do this during operation either via the buttons on the thermostat or using a commissioning tool.
Control sequence
Recalibrating the sensor
Control parameters
Proceed as follows to change the most important control parameters: (Your HVAC installer can set additional parameters)
| Para- meter | Description | Factory setting | Setting range | Adj
|
| P01 | Control sequence | 2-pipe: [0…3] 1 (Cooling only)
4-pipe: [2…4] 4 (Heating&Cooling) | 0 = Heating only 1 = Cooling only 2 = Manual H or C 3 = Auto Changeover 4 = Heating & cooling | |
| P02 | Mode selection by user via operating mode button | 1 (Auto **, Protection) | 1 = Auto **, Protection 2 = Auto **, Comfort, Economy, Protection | |
| P04 | Selection of °C or °F | 0 (°C) | 0 = °C 1 = °F | |
| P05 | Sensor calibration | 0.0 °C | – 3 … +3 °C | |
| P06 | Standard temperature display | 0 (Room temp.) | 0 = Room temperature 1 = Setpoint | |
| P07 | Additional user information | 0 (no display) | 0 = No display 1 = Temp. in °C / °F 2 = Outside temperature (via bus) 3 = Time of day (12h, via bus) 4 = Time of day (24h, via bus) | |
| P08 | Comfort basic setpoint | 21 °C | 5 … 40 °C | |
| P09 | Minimum setpoint limitation in Comfort (WminComf) | 5 °C | 5 … 40 °C | |
| P10 | Maximum setpoint limitation in Comfort (WmaxComf) | 35 °C | 5 … 40 °C | |
| P11 | The setpoint of heating in Economy (WheatEco) | 15 °C | OFF, 5 °C…WcoolEco | |
| P12 | Setpoint of cooling in Economy (WcoolEco) | 30 °C | OFF, WheatEco…40°C | |
| P13 *** | Electric heater in cooling mode | ON | OFF = disabled ON = enabled | |
| P14 | Button lock (Press the operating mode button for 3 seconds to lock or unlock the buttons) | 0 (Disabled) | 0 = Disabled 1 = Auto lock 2 = Manual lock | |
| P15 | Fan control dead zone in Comfort | 0 (fan OFF) | 0:= fan OFF 1:= fan speed 1 in H or C mode 2:= fan speed 1 in C mode only |
DOWNLOAD MANUALS:
SIEMENS RDF600KN Flush mount KNX Room Thermostat OPERATING INSTRUCTION
OTHER MANUALS:
SIEMENS RDF600KN Flush mount KNX room thermostat Product Specifications Guide
SIEMENS RDF600KN Flush mount KNX Room Thermostat Operating Instructions
Bad Ragaz Casino No Deposit Bonus Codes For Free Spins 2026 Details pertaining to the…
Online Slot Games For Money Playing online casinos UK on a mobile device Spin the…
Prime Fortune Casino No Deposit Bonus Codes For Free Spins 2026 Fantasy sports became a…
Online Casino Real Money Uk No Deposit Get ready to play the most realistic card…
Sin88 Casino No Deposit Bonus Codes For Free Spins 2026 This can be part of…
How To Always Win Blackjack Casino offer terms and conditions in UK Here is how…