Icons used in this manual:
Thank you for purchasing the SALUS BTRP230 Thermostat. This thermostat is a device that lets you customize the heating and cooling of your home as needed. The BTRP230 device from SALUS Controls is a stylish and accurate digitial programmable room thermostat for flush mount and designed for Bezel 55mm range. It thermostat that is fitted with a large easy-to-read LCD screen and one-touch buttons. You can now simply adjust your home temperature as desired in order to create a comfortable home environment.
We hope you enjoy our product.
Install the BTRP230 digital room thermostat roughly about 1.5m above floor level. It should be mounted in a location where the thermostat is easily accessible and away from direct sunlight. You can mount the thermostat directly on the wall or you can install it on top of a wall box.
Note: You can wire the thermostat directly to the KL08NSB wiring center or to an actuator (purchased separately).
Note: LCD backlight is activated by pressing any key.
When you first power up your device you will have to set up the date and time.
You can customise your programs by long pressing
Note: If you want to select another Program Profile (from the available 5), please enter in Installer Mode, choose option d17 and after that select the desired program.
You can select and customise any of the following programs:
| 5 days (Monday to Friday) | |||
| Program | Program Time | Heat set point | Cool set point |
| 1 | 6:00 | Sunny | Sunny |
| 2 | 9:00 | Moon | Moon |
| 3 | 16:00 | Sunny | Sunny |
| 4 | 23:00 | Moon | Moon |
| 5 | –:– | –:– | –:– |
| 6 | –:– | –:– | –:– |
| 2 days (Saturday to Sunday) | |||
| Program | Program Time | Heat set point | Cool set point |
| 1 | 7:00 | Sunny | Sunny |
| 2 | 23:00 | Moon | Moon |
| 3 | –:– | –:– | –:– |
| 4 | –:– | –:– | –:– |
| 5 | –:– | –:– | –:– |
| 6 | –:– | –:– | –:– |
| 5 days (Monday to Friday) | |||
| Program | Program Time | Heat set point | Cool set point |
| 1 | 6:00 | Sunny | Sunny |
| 2 | 22:30 | Moon | Moon |
| 3 | –:– | –:– | –:– |
| 4 | –:– | –:– | –:– |
| 5 | –:– | –:– | –:– |
| 6 | –:– | –:– | –:– |
| 2 days (Saturday to Sunday) | |||
| Program | Program Time | Heat set point | Cool set point |
| 1 | 7:00 | Sunny | Sunny |
| 2 | 23:00 | Moon | Moon |
| 3 | –:– | –:– | –:– |
| 4 | –:– | –:– | –:– |
| 5 | –:– | –:– | –:– |
| 6 | –:– | –:– | –:– |
| 5 days (Monday to Friday) | |||
| Program | Program Time | Heat set point | Cool set point |
| 1 | 5:00 | Sunny | Sunny |
| 2 | 8:00 | Moon | Moon |
| 3 | 14:00 | Sunny | Sunny |
| 4 | 22:00 | Moon | Moon |
| 5 | –:– | –:– | –:– |
| 6 | –:– | –:– | –:– |
| 2 days (Saturday to Sunday) | |||
| Program | Program Time | Heat set point | Cool set point |
| 1 | 7:30 | Sunny | Sunny |
| 2 | 22:30 | Moon | Moon |
| 3 | –:– | –:– | –:– |
| 4 | –:– | –:– | –:– |
| 5 | –:– | –:– | –:– |
| 6 | –:– | –:– | –:– |
| 5 days (Monday to Friday) | |||
| Program | Program Time | Heat set point | Cool set point |
| 1 | 6:00 | Sunny | Sunny |
| 2 | 9:00 | Moon | Moon |
| 3 | 15:00 | Sunny | Sunny |
| 4 | 22:30 | Moon | Moon |
| 5 | –:– | –:– | –:– |
| 6 | –:– | –:– | –:– |
| 2 days (Saturday to Sunday) | |||
| Program | Program Time | Heat set point | Cool set point |
| 1 | 7:30 | Sunny | Sunny |
| 2 | 23:00 | Moon | Moon |
| 3 | –:– | –:– | –:– |
| 4 | –:– | –:– | –:– |
| 5 | –:– | –:– | –:– |
| 6 | –:– | –:– | –:– |
| 5 days (Monday to Friday) | |||
| Program | Program Time | Heat set point | Cool set point |
| 1 | 6:00 | Sunny | Sunny |
| 2 | 10:00 | Moon | Moon |
| 3 | 16:00 | Sunny | Sunny |
| 4 | 23:00 | Moon | Moon |
| 5 | –:– | –:– | –:– |
| 6 | –:– | –:– | –:– |
| 2 days (Saturday to Sunday) | |||
| Program | Program Time | Heat set point | Cool set point |
| 1 | 7:30 | Sunny | Sunny |
| 2 | 23:30 | Moon | Moon |
| 3 | –:– | –:– | –:– |
| 4 | –:– | –:– | –:– |
| 5 | –:– | –:– | –:– |
| 6 | –:– | –:– | –:– |
| dxx | D setting function | Parameter/ Values | Definition | Default value |
| d01 | Heating Control | 0 | PWM (Pulse-width modulation) | 0 |
| 1 | ON-OFF: 0.5C (± 0.25ºC) | |||
| 2 | ON-OFF: 1.0C (± 0.5ºC) | |||
| d02 | Room temp. offset | -3.0oCto+3.0oC | Offset room temp measuring error (in 0.5ºC) | 0.0ºC |
| d03 | OUT sensor probe (S1/S2) | 0 | Out sensor probe not connected | 0 |
| 1 | Out sensor probe connected | |||
| d04 | Air sensor or Floor sensor | 0 | A: if d03 = 0, IN sensor controls Tr A: if d03 = 1, IN disabled and OUT controls Tr | 0 |
| 1 | F: if d03 = 0, IN sensor controls Tr F: if d03 = 1, IN disabled and OUT controlsTr Floor Protection | |||
| d05 | Cooling Control | 1 | ON-OFF: 0.5ºC (± 0.25ºC) | 2 |
| 2 | ON-OFF: 1.0ºC (± 0.5ºC) | |||
| d07 | Valve Protection | 0/1 | 0 = VP disabled 1 = Enable | 1 |
| d08 | Frost Setpoint | 5ºC-17ºC | 5.0ºC |
| d09 | 12/24 Hour Format | 0 | 12hr | 1 |
| 1 | 24hr | |||
| d11 | Daylight Saving Time (DST) | 0 1 | Off | 1 |
| On | ||||
| d12 | Maximum limitation of heating setpoint | 5ºC – 35ºC | 35ºC | |
| d13 | Maximum limitation of cooling setpoint | 5ºC – 40ºC | 5ºC | |
| d14 | Floor sensor protection limit (heating high limit-HL) | 11ºC – 45ºC | Turn off relay output when floor sensing temp > protecting limit, step is 0.5ºC | 27ºC |
| d15 | Floor sensor protection limit (heating low limit-LL) | 6ºC – 40ºC | Turn on relay output when floor sensing temp < protecting limit, step is 0.5ºC | 10ºC |
| d16 | Floor sensor protection limit (cooling) | 6ºC – 45ºC | Turn off relay output when floor sensing temp < protecting limit, step is 0.5ºC | 6ºC |
| d17 | Preset program selection | 1-5 | Select one of these 5 default programs. Once selected, default program will overwrite present program. Selected default program can be edited by the user in the User Setting Mode. | 1 |
| d18 | Heat/Cool Mode Selection | 0 or 1 | 0: No connection 1: Connection | 0 |
| d19 | Cooling Blocked | 0 or 1 | 0: Cooling allowed 1: Cooling disabled | 0 |
| d20 | Actuators loading selection for different temperature compensation. | 1 to 5 | 1: x 1 actuator loading 2: x 2 actuators loading 3: x 3 actuators loading 4: x 4 actuators loading 5: x 5 actuators loading | 1 |
When the thermostat is set on Cooling Disabled (d19–>1) it will block the cooling function for single rooms until the device will receive the heating command. During the periods of cooling blocked no special indicator will be displayed on the LCD screen. Ice flake will also be turned off.
Note: d19 will be available only if d18 is set on 1 (Heat/Cool Mode selection Connected).
Note: Vacation Modes ends when it reaches day 0. After that the device goes back to Auto Mode.
| Model: | BTRP230 |
| Voltage | 230 V AC, +-10%, 50/60 Hz |
| Operating performance | 230 V: 1,8 W / 0.5A Max load |
| Temperature setback | Adjustable |
| Temperature range | 5°C – 35°C |
| Span | +/- 0,5°C |
| Storage temperature | -20°C to +60°C |
| Ambient temperature | 0 °C up to 45 °C |
| Degree of protection | IP 30 |
| CE conformity according to | Class II ( EN60730 ) |
| Housing material | PC, V2 |
| Color | RAL 9010 pure white |
| Connection | Screw terminal |
| Weight | 130g net / 175g gross |
| Puls-wide-modulation (PWM) | Yes |
| Clock, Timer | Yes, programmable |
| Profile Modes | 3 ( Sun, Moon, Automatic) |
| Heating and Cooling | Yes, on CO contact Input (0V= Heatmode ; 230V Cooling mode) |
| Parameter adjustment | Yes, in Installer Mode |
| Dimensions | front : 55 x 55 x 17mm Back: dia.: 55mm x 30mm |
SALUS Controls warrants that this product (BTRP230) will be free from any defect in materials or workmanship, and shall perform in accordance with its specification, for a period of five years from the date of installation. SALUS Controls sole liability for breach of this warranty will be (at its option) to repair or replace the defective product.
SALUS Controls plc
SALUS House Dodworth Business Park South, Whinby Road, Dodworth, Barnsley S75 3SP, UK.
Sales: T: +44 (0) 1226 323961
E: sales@salus-tech.com
Technical: T: +44 (0) 1226 323961
E: technical@salus-tech.com
www.salus-controls.com
SALUS Controls is a member of the Computime Group
Issue Date: Feb 2016 00188
For a PDF Installation guide please go to www.salus-manuals.com
Maintaining a policy of continuous product development SALUS Controls plc reserves the right to change the specification, design, and materials of products listed in this brochure without prior notice.
Download Manual:
SALUS BTRP230 Pure White Room Thermostat UP Electronic Digital Installation Manual
OTHER MANUALS:
SALUS BTRP230 Pure White Room Thermostat UP Electronic Digital User Guide
SALUS BTRP230 Pure White Room Thermostat UP Electronic Digital Installation Manual
Bad Ragaz Casino No Deposit Bonus Codes For Free Spins 2026 Details pertaining to the…
Online Slot Games For Money Playing online casinos UK on a mobile device Spin the…
Prime Fortune Casino No Deposit Bonus Codes For Free Spins 2026 Fantasy sports became a…
Online Casino Real Money Uk No Deposit Get ready to play the most realistic card…
Sin88 Casino No Deposit Bonus Codes For Free Spins 2026 This can be part of…
How To Always Win Blackjack Casino offer terms and conditions in UK Here is how…