Note! More information about the product can be found in the manual, which is available for download from www.regincontrols.com
Caution! Read and understand the instruction before using the product.
Caution! Ensure that the installation complies with local safety regulations.
Warning! Before installation or maintenance, the power supply must first be disconnected in order to prevent potentially lethal electric shocks! Installation or maintenance of this unit should only be carried out by qualified personnel. The manufacturer is not responsible for any eventual damage or injury caused by inadequate skills during installation, or through removal of or deactivation of any security devices.
| Supply voltage | 230 V ~ (207…253 V ~ 50/60 Hz) |
| Power consumption | < 2 VA |
| Protection class | IP30 |
| Ambient humidity | 10…90 %RH (non-condensing) |
| Ambient temperature | 0…50 °C |
| Measuring range, temperature | 0…50 °C |
| Sensor element, temperature | NTC |
| Accuracy, temperature | ±0.5 K |
| Display | Built-in |
| Display type | LED-backlit LCD |
| Output signal, temperature | NTC |
| Setpoint adjustment | 5…35 °C |
| Mounting | Room (flush-mounted with screw distance cc 60 mm) |
| Installation | Fan-coils, 2- or 4-pipe |
| Digital inputs (DI) | 1 x Closing potential-free contact |
| Digital outputs (DO) | 3 x Relay outputs for 3-step fan control, 230 V AC, Max. 5 A 2 x Relay outputs for On/Off valve ac- tutors, 230 V AC, Max. 5 A |
| Analog inputs (AI) | 1 x PT1000 |
| Change-over function | Automatic |
| Communication port | 1 |
| Internal serial port, type | RS485 |
| Internal serial port, built-in protocol | Modbus (RTU) |
| Internal serial port, communication speed | 9600 bps (4800…38400 bps) |
| Internal serial port, parity | Even (Even, Odd, None) |
| Internal serial port, stop bit | 1 (1 or 2) |
| Cable connection | Screw terminals max. 1.5 mm2 (AWG 16) |
| Dimensions, external (WxHxD) | 95 x 95 x 50.5 mm |
| Terminal | Description |
| L | Supply voltage |
| N | Supply voltage |
| FAN1 | 230 V AC Relay 1 |
| FAN2 | 230 V AC Relay 2 |
| FAN3 | 230 V AC Relay 3 |
| Heat | 230 V AC Relay 4 |
| Cool | 230 V AC Relay 5 |
| GND | GND (for DI) |
| DI | Digital input for presence detection, hotel key card etc |
| Temp | Analogue input for external PT1000 sensor, change-over |
| GND | Agnd for terminal Temp Serial communication port, Com N |
| A | Serial communication port, Com A |
| B | Serial communication port, Com B |
The thermostat settings can be controlled in one of the following ways:
Table 1 Buttons available in the display
Handling
The display behaves differently depending on the mode and the state that the thermostat is currently operating in. The thermostat can be in one of the following states:
The thermostat can be in three different modes when in Standby or Occupied state:
CE-mark
This product carries the CE-mark. More information is available at www.regincontrols.com.
Contact
DOWNLOAD MANUALS:
REGIN RCFD-230C FAN COIL Room Thermostat Instruction Manual
OTHER MANUALS:
REGIN RCFD-230C FAN COIL Room Thermostat DATA Sheet
Bad Ragaz Casino No Deposit Bonus Codes For Free Spins 2026 Details pertaining to the…
Online Slot Games For Money Playing online casinos UK on a mobile device Spin the…
Prime Fortune Casino No Deposit Bonus Codes For Free Spins 2026 Fantasy sports became a…
Online Casino Real Money Uk No Deposit Get ready to play the most realistic card…
Sin88 Casino No Deposit Bonus Codes For Free Spins 2026 This can be part of…
How To Always Win Blackjack Casino offer terms and conditions in UK Here is how…