Pro1 Technologies
Thermostat Application Guide
Description | |
Gas or Oil Heat | Yes |
Electric Furnace | Yes |
Heat Pump (No Aux. or Emergency Heat) | Yes |
Heat Pump (With Aux. or Emergency Heat) | Yes |
Multi-Stage Systems | Yes |
Heat Only Systems | Yes |
Heat Only Systems – Floor or Wall Furnace | Yes |
Cool Only Systems | Yes |
Millivolt Conventional Systems | Yes |
Two Transformer Systems | No |
Power Type
A trained, experienced
the technician must install this product. Carefully read these instructions. You could damage this product or cause a hazardous condition if you fail to follow these instructions.
Wall Locations
The thermostat should be installed approximately 4 to 5 feet above the floor. Select an area with average temperature and good air circulation.
Subbase Installation
Mount Thermostat
Align the 4 tabs on the subbase with corresponding slots on the back of the thermostat, then push gently until the thermostat snaps in place.
About The Badge
All of our thermostats use the same universal magnetic badge. Visit the company website to learn more about our free private label program.
Battery Installation
Battery installation is recommended even if the thermostat is hardwired (C terminal connected). When the thermostat is hardwired and batteries are installed, the thermostat will activate a compressor delay of 5 minutes when the thermostat detects a power outage from the hardwired power supply.
Important
The low battery icon is displayed when the AA battery power is low. Whenever the thermostat detects low battery voltage from the AA batteries, the low battery icon will begin flashing on the screen for 21 days (if the batteries are not changed). If the batteries are not changed 22 days after the thermostat detects low battery voltage, the thermostat screen will only show the flashing battery icon until the buttons are pressed. If the batteries are not changed 43 days after the thermostat detects low battery voltage, the thermostat screen will only show the flashing battery icon until buttons are pressed and the set points will offset to 85°F/29°C in cooling and 55°F/13°C in heating. At this stage, set point changes can be made temporarily but, the set points will change back to defaulted values after a 4-hour period. The thermostat will continue to perform this low battery flashing, temperature offset condition until the internal voltage threshold is reached. When the thermostat internal voltage threshold is reached, all relays will be opened and the thermostat will become inoperable until new batteries are installed.
Caution: Electrical Hazard Failure to disconnect the power before beginning to install this product can cause electrical shock or equipment damage.
Terminal Designations
Terminal | 2 Heat 2 Cool Conventional System | 2 Heat 1 Cool Heat Pump System | 4 Heat 2 Cool Heat Pump System | 5 Heat 3 Cool Heat Pump System |
RC | Transformer power (cooling) | Transformer power (cooling) | Transformer power (cooling) | Transformer power (cooling) |
RH | Transformer power (heating) | Transformer power (heating) | Transformer power (heating) | Transformer power (heating) |
C | Transformer common | Transformer common | Transformer common | Transformer common |
B | Reversing valve / configurable terminal | Reversing valve / configurable terminal | Reversing valve / configurable terminal | Reversing valve / 3rd stage of heat & cool |
O | Reversing valve / configurable terminal | Reversing valve / configurable terminal | Reversing valve / configurable terminal | Reversing valve / 3rd stage of heat & cool |
G | Fan relay | Fan relay | Fan relay | Fan relay |
W/E | First stage of heat | Emergency Heat | First stage of auxiliary heat | First stage of auxiliary heat (4th stage of heat) |
Y | First stage of cool | First stage of heat & cool | First stage of heat & cool | First stage of heat & cool |
Y2 | Second stage of cool | N/A | Second stage of heat & cool | Second stage of heat & cool |
W2 | Second stage of heat | Auxiliary heat | Second stage of auxiliary heat | Second stage of auxiliary heat (5th stage of heat) |
S1/S2 | Remote Sensor | Remote Sensor | Remote Sensor | Remote Sensor |
H | Humidify | Humidify | Humidify | Humidify |
D | Dehumidify | Dehumidify | Dehumidify | Dehumidify |
Technician Setup Menu
This table references different humidity levels the thermostat will conform to, based on the outdoor temperature measurements. When the Automatic Humidity Adjusting tech setting selection is ON1 or ON2, the thermostat humidity will stay adjusted to the humidity level that correspond to the outdoor temperature based on the chart index below.
HUM Terminal
OPTIONS | HUM terminal energizes when the ambient humidity is… |
1 | Below the humidity setpoint and heat or fan is energized. |
2 | Below the humidity setpoint and heat is energized. |
3 | Below the humidity setpoint. It will also energize the fan during a call for humidity. |
4 | Below the humidity setpoint. |
DHM Terminal
OPTIONS | DUM terminal energizes when the ambient humidity is… |
1 | Above the humidity setpoint and cool or fan is energized. |
2 | Above the humidity setpoint. It will also energize the fan during a call for dehumidity. |
3 | Above the humidity setpoint. |
4 | Above the humidity setpoint and the compressor is not running. |
Temperature 50 | 20%-25% 50 | 26%-35% 50 | 36%-45% 50 | 46%-55% 50 | 56%-65% 50 | 66%-75% 50 | 76%-85% 50 | 86%-90% 50 |
51 | 50.6 | 50.7 | 50.7 | 50.9 | 51 | 51 | 51 | 51.2 |
52 | 51.2 | 51.5 | 51.5 | 51.7 | 52 | 52 | 52 | 52.5 |
53 | 52.3 | 52.5 | 52.5 | 52.8 | 53 | 53 | 53 | 53.5 |
54 | 52.9 | 53.3 | 53.3 | 53.6 | 54 | 54 | 54 | 54.8 |
55 | 53.5 | 54 | 54 | 54.5 | 55 | 55 | 55 | 56 |
56 | 54.1 | 54.6 | 54.7 | 55.3 | 56 | 56 | 56 | 57 |
57 | 54.7 | 55.2 | 55.4 | 56.2 | 56.9 | 56.9 | 56.9 | 57.9 |
58 | 55.8 | 56.3 | 56.6 | 57.3 | 58.1 | 58.1 | 58.1 | 59.1 |
59 | 56.4 | 56.9 | 57.3 | 58.2 | 59 | 59 | 59 | 60 |
60 | 57 | 57.5 | 58 | 59 | 60 | 60 | 60 | 61 |
61 | 58 | 58.5 | 59.1 | 60.1 | 60.9 | 60.9 | 61.1 | 61.9 |
62 | 58.9 | 59.4 | 60.1 | 61.1 | 61.9 | 61.9 | 62.1 | 62.9 |
63 | 60.1 | 60.6 | 61.4 | 62.4 | 63.1 | 63.1 | 63.4 | 64.1 |
64 | 61 | 61.6 | 62.4 | 63.4 | 64.1 | 64.1 | 64.4 | 65.1 |
65 | 62 | 62.5 | 63.5 | 64.5 | 65 | 65 | 65.5 | 66 |
66 | 62.7 | 63.3 | 64.3 | 65.3 | 65.9 | 65.9 | 66.5 | 66.9 |
67 | 63.4 | 64.1 | 65.1 | 66.1 | 66.8 | 66.8 | 67.6 | 67.8 |
68 | 64.6 | 65.4 | 66.4 | 67.4 | 68.2 | 68.2 | 68.9 | 69.2 |
69 | 65.3 | 66.2 | 67.2 | 68.2 | 69.1 | 69.1 | 70 | 70.1 |
70 | 66 | 67 | 68 | 69 | 70 | 70 | 71 | 71 |
71 | 67.2 | 68.2 | 69.1 | 70.1 | 71.1 | 71.4 | 72.4 | 72.6 |
72 | 68.3 | 69.3 | 70.3 | 71.3 | 72.3 | 72.8 | 73.8 | 74.3 |
73 | 69.7 | 70.7 | 71.7 | 72.7 | 73.7 | 74.2 | 75.2 | 75.8 |
74 | 70.8 | 71.9 | 72.9 | 73.9 | 74.9 | 75.6 | 76.6 | 77.4 |
75 | 72 | 73 | 74 | 75 | 76 | 77 | 78 | 79 |
76 | 72.9 | 73.9 | 74.9 | 76.1 | 77.1 | 78.6 | 79.6 | 80.6 |
77 | 73.8 | 74.7 | 75.7 | 77.2 | 78.2 | 80.2 | 81.2 | 82.7 |
78 | 75.2 | 76.3 | 77.3 | 78.8 | 79.8 | 81.8 | 82.8 | 84.3 |
79 | 76.1 | 77.1 | 78.1 | 79.9 | 80.9 | 83.4 | 84.4 | 86.2 |
80 | 77 | 78 | 79 | 81 | 82 | 85 | 86 | 88 |
81 | 77.9 | 79.1 | 80.3 | 82.3 | 83.6 | 86.6 | 88.3 | 91 |
82 | 78.7 | 80.2 | 81.7 | 83.7 | 85.1 | 88.1 | 90.6 | 94.1 |
83 | 80.3 | 81.8 | 83.3 | 85.3 | 86.9 | 89.9 | 92.4 | 96 |
84 | 81.1 | 82.9 | 84.7 | 86.7 | 88.4 | 91.4 | 94.7 | 99 |
85 | 82 | 84 | 86 | 88 | 90 | 93 | 97 | 102 |
86 | 82.8 | 85.1 | 87.3 | 89.5 | 92 | 95.8 | 100.5 | 106.4 |
87 | 83.7 | 86.1 | 88.6 | 91.1 | 94.1 | 98.5 | 104 | 110.9 |
88 | 85.3 | 87.9 | 90.4 | 92.9 | 96 | 100.5 | 106.1 | 113.1 |
89 | 86.2 | 88.9 | 91.7 | 94.5 | 98 | 103.2 | 109.5 | 117.6 |
90 | 87 | 90 | 93 | 96 | 100 | 106 | 113 | 122 |
Setting Target Humidity Setpoint
Ambient humidity will flash in the time field when Humidify or De-Humidify is set to ON. HON will also flash when the Humidity terminal is energized. dON will also flash when the De-Humidify terminal is energized.
Recommended Heating Settings
Increasing Humidity The table below shows recommended indoor humidity levels in relation to outdoor temperatures during heating (adding humidity).
Recommended Cooling Settings
Consult your professional HVAC technician for recommended settings for your climate.
Set Time
All our programmable thermostats are shipped with an energy saving default program. You can customize this default program by following the instructions in the set program schedule section starting on page 24. Your thermostat can be programmed to have each day of the week programmed uniquely (7 days) or non-programmable. For the 7-day programming modes, there are three time period options.
Custom Program
Day of the Week | Events | Time | Setpoint Temperature (HEAT) | Setpoint Temperature (COOL) |
Weekday | Wake/OCC1 | |||
Leave/UNOCC1 | ||||
Return/OCC2 | ||||
Sleep/UNOCC2 | ||||
Occupied | ||||
Unoccupied | ||||
Saturday | Wake/OCC1 | |||
Leave/UNOCC1 | ||||
Return/OCC2 | ||||
Sleep/UNOCC2 | ||||
Occupied | ||||
Unoccupied | ||||
Sunday | Wake/OCC1 | |||
LeaveUNOCC1 | ||||
Return/OCC2 | ||||
Sleep/UNOCC2 | ||||
Occupied | ||||
Unoccupied |
To customize your 7 day 4 time period Program schedule, follow these steps
Monday:
Default Programming
Day of the Week | Events | Time | Setpoint Temperature (HEAT) | Setpoint Temperature (COOL) |
Weekday | Wake/OCC1 | 6 AM | 70˚F (21˚C) | 78˚F (24˚C) |
Leave/UNOCC1 | 8 AM | 62˚F (17˚C) | 85˚F (28˚C) | |
Return/OCC2 | 6 PM | 70˚F (21˚C) | 78˚F (24˚C) | |
Sleep/UNOCC2 | 10 PM | 62˚F (17˚C) | 82˚F (26˚C) | |
Saturday | Wake/OCC1 | 6 AM | 70˚F (21˚C) | 78˚F (24˚C) |
Leave/UNOCC1 | 8 AM | 62˚F (17˚C) | 85˚F (28˚C) | |
Return/OCC2 | 6 PM | 70˚F (21˚C) | 78˚F (24˚C) | |
Sleep/UNOCC2 | 10 PM | 62˚F (17˚C) | 82˚F (26˚C) | |
Sunday | Wake/OCC1 | 6 AM | 70˚F (21˚C) | 78˚F (24˚C) |
LeaveUNOCC1 | 8 AM | 62˚F (17˚C) | 85˚F (28˚C) | |
Return/OCC2 | 6 PM | 70˚F (21˚C) | 78˚F (24˚C) | |
Sleep/UNOCC2 | 10 PM | 62˚F (17˚C) | 82˚F (26˚C) |
Day of the Week | Events | Time | Setpoint Temperature (HEAT) | Setpoint Temperature (COOL) |
Weekday | Wake/OCC1 | 6 AM | 70˚F (21˚C) | 78˚F (24˚C) |
Leave/UNOCC1 | 8 AM | 62˚F (17˚C) | 85˚F (28˚C) | |
Return/OCC2 | 6 PM | 70˚F (21˚C) | 78˚F (24˚C) | |
Sleep/UNOCC2 | 10 PM | 62˚F (17˚C) | 82˚F (26˚C) | |
Saturday | Wake/OCC1 | 6 AM | 70˚F (21˚C) | 78˚F (24˚C) |
Leave/UNOCC1 | 8 AM | 62˚F (17˚C) | 85˚F (28˚C) | |
Return/OCC2 | 6 PM | 70˚F (21˚C) | 78˚F (24˚C) | |
Sleep/UNOCC2 | 10 PM | 62˚F (17˚C) | 82˚F (26˚C) | |
Sunday | Wake/OCC1 | 6 AM | 70˚F (21˚C) | 78˚F (24˚C) |
LeaveUNOCC1 | 8 AM | 62˚F (17˚C) | 85˚F (28˚C) | |
Return/OCC2 | 6 PM | 70˚F (21˚C) | 78˚F (24˚C) | |
Sleep/UNOCC2 | 10 PM | 62˚F (17˚C) | 82˚F (26˚C) |
Filter Change & Other Reminders
If the filter change reminder is enabled, you will see a reminder in the display when your air filter needs changed. The reminder will be shown in the display after your system has run long enough to require an air filter change
Resetting The Filter Change Reminder
When the reminder is displayed, you should change your air filter and reset the reminder by holding down the 3rd button from the left side of the thermostat for 3 seconds
Download Manual:
Pro1 Technologies T855iSH Non-Programmable Thermostat Installational Manual
OTHER MANUALS
Pro1 Technologies T855iSH Non-Programmable Thermostat Operational Manual
Pro1 Technologies T855iSH Non-Programmable Thermostat Product Specifications Guide
Pro1 Technologies T855iSH Non-Programmable Thermostat User Guide
Pro1 Technologies T855iSH Non-Programmable Thermostat Installational Manual
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…