ACCESS SERVICE MENUS
CONFIGURE SERVICE MENUS
The following Service Menus (SM) commonly require configuration. Please verify that these are set for your specific application. Additional configuration may be required. Refer to Table 2 for all available Service Menus.
WIRE TERMINAL DESIGNATIONS
Connect wires for the appropriate system type (Table 1).
WARNING: DISCONNECT POWER BEFORE BEGINNING INSTALLATION.
TABLE 1. TERMINAL BLOCK
C | 24 VAC, Unswitched side | C | 24 VAC, Unswitched side |
W1 | Stage 1 Heat | B/O | Reversing Valve |
W2 | Stage 2 Heat | AUX | Auxiliary Heat (Stage 2 or 3) |
G | FAN High | G | FAN High |
A | FAN Medium | A | FAN Medium |
E | FAN Low | E | FAN Low |
Y1 | Stage 1 Cool | Y1 | Compressor Stage 1 |
Y2 | Stage 2 Cool | Y2 | Compressor Stage 2 |
RH | 24 VAC Power for heating, switched side | RH | 24 VAC Power for heating, switched side |
RC | 24 VAC Power for cooling, switched side | RC | 24 VAC Power for cooling, switched side |
SC | Sensor Common | SC | Sensor Common |
S1 | Indoor Remote Sensor | S1 | Indoor Remote Sensor |
S2 | Occupancy Sensor | S2 | Occupancy Sensor |
S3 | Seasonal Changeover Switch OPEN=Cooling in Summer CLOSED=Heating in Winter | S3 | NA |
TYPICAL FAN COIL
WIRING DIAGRAM
FAN SPEED SELECTION
The T8532OCC Thermostat has an onboard occupancy sensor that will setback operation when a room becomes vacant. Service Menu 325 Occupied Sensor Operation is turned on to enable this operation.
Occupied Timer (SM 326) – Sets the amount of time that must pass without detection before the control goes to Setback and starts the Ramping process.
Setback Ramping (SM 327) – Determines how the control will ramp to setback
values. The economy set goes directly to setback values. Comfort 1 setting will allow a 1°F per hour setback of the control set point. Comfort 2 sets back at 2°F per hour until the selected setback value is reached.
Setback Values (SM 310 and SM 320) – Set the HEAT and COOL set points for the setback. Values can be set to OFF or 50-90F. Selection of OFF will result in a set point of OFF.
Night Lock ON Protection (SM 328) – When enabled the control holds the user set point between 10 PM and 8 AM, anytime occupancy is detected during that time period. Note: This control has Low/ High Temp Protection. Freeze protection on this control is set at 40°F (heat). Over-temp protection is set at 110°F (cool).
Occupancy Sensor Detection Performance
Specifications | |
Input Power: | 24 VAC (20-30 VAC) 50/60 Hz and/or 2 AA Batteries |
Output Rating | Terminal W,Y,A – 20-30 VAC 0.02-1.0 A Terminal G – 20-30 VAC 0.02-0.6 A Total Load not to Exceed 2.5 A |
Temperature Control Range: | 50° to 90°F (10° to 32°C) |
Operating Temperature Range: | 0° to 120°F (-18° to 49°C) |
Occupancy Sensor Type: | Passive Infra-Red |
Detection Distance: 16.4 Ft (5 meters) Detection Range: 94° Horizontal x 82° Vertical
TABLE 2. ADVANCED CONFIGURATION: SERVICE MENUS
Some Service Menus may not be available, depending on the system type (SM 110).
MENU | FEATURE | OPTIONS | STD. DEFAULT | DESCRIPTION / COMMENTS |
100 | Schedule Format | 0-3 | 0 | Select the schedule format on the T8000 Series. (Menu not available on non-programmable thermostats.) NOTE: Set the clock before changing to non-progammable. 0 = nonprogrammable 1 = programmable 2 = 5-1-1 schedule 3 = 5-2 schedule |
101 | Daylight-Saving Time | 0,1 | 1 | Select daylight-saving time as it follows standard format in U.S.: It begins second Sunday of March at 2:00 AM and ends on the first Sunday of November at 2:00 AM. 0 = Disabled 1 = Enabled (2007 U.S. Format) |
110 | System Type | 1-13 | 1 | Select the appropriate system configuration (determines available Service Menus). 1 = 1 Heat/1 Cool conventional 2 = 1 Heat/1 Cool heat pump 3 = Heat only without fan (2-wire systems) 4 = Heat only with fan 5 = Cool only 6 = 2 Heat/1 Cool heat pump (with auxiliary heat) and Emergency (Em) heat 7 = 2 Heat/2 Cool multistage conventional 8 = 2 Heat/ 1 Cool multistage conventional 9 = 1 Heat/ 2 Cool multistage conventional 10 = 2 Heat/ 2 Cool heat pump (no auxiliary heat) 11 = 3 Heat/ 2 Cool heat pump (with auxiliary heat) and Emergency (Em) heat 12 = NA 13 = NA |
120 | Fan Control (heating) | 0,1 | 1 | 0 = Fossil Fuel; Gas/Oil/Propane heat (equipment controls heating fan) 1 = Electric Furnace (thermostat controls heating fan) |
121 | Fan Speeds | 1, 2, 3, 4 | 3 | Allows selection of multiple fan speeds. 1 = Single speed Fan (G terminal) 2 = 2-speed Fan (G and E Terminals) 3 = 3-speed Fan (G,A and E Terminals) 4 = 3-speed Staged Fan |
130 | O/B Reversing valve | 0,1 | 0 | When 0, output is active for cooling. When 1, output is active for heating. 0 = (O) Active with cooling 1 = (B) Active with heating |
135 | W1 Output Configuration | 0,1 | 0 | Changes operation of W1 for Active to Open (NC Normally Closed) to Active to Close (NO Normally Open). Must be 0 for heat pump operation. 0 = NC Operation 1 = NO Operation |
150 | Backlight | 0,1 | 0 | 0 = Backlight temporarily on 1 = Backlight always on (low intensity, 24V only) |
MENU | FEATURE | OPTIONS | STD. DEFAULT | DESCRIPTION / COMMENTS |
170 | Remote Sensor | 0-8 | 0 | Select sensor if used. Contact PECO for information on the T8000 Series Indoor Remote Zone Sensor. 0 = No Remote Sensors 1 = Remote Indoor Sensor Only 2 = Not Used 3 = Not Used 4 = Not Used 5 = Not Used 6 = S3 Input with Aquastat Only 7 = S3 Input with Aquastat and S1 with Remote Indoor Sensor 8 = Not Used |
171 | Sensor Average Remote & Local | 0 – Local/Remote 1 – Average Local/Remote | 0 | This feature allows both local and remote sensing. SM 170 must be set to either 01 or 07. |
240 | Number of Program Periods | 2; 4 events | 4 | 2 = 2 events per day (Selections OCC1 and UnOcc1) 4 = 4 events per day (Selections Occ1-UnOcc1-Occ2- UnOcc2) |
250 | Clock Format | 12 or 24 Hours | 12 | 12 = 12-hour clock mode 24 = 24-hour clock mode |
260 | Temperature Format (°F or °C) | 0,1 | 1 | 0 = Celsius 1 = Fahrenheit |
265 | Single/Dual Setpoint | 0,1 | 1 | Determines if single user override setpoint is used, or if user sets heat and cool setpoints independently. 0 = Dual Setpoint (Heat and Cool) 1 = Single Override Setpoint (Single Setpoint with auto changeover algorithm) |
290 | Range Low | 50-90°F or 10-32°C | 50°F | Choose the lowest selectable temperature setpoint value. |
300 | Range High | 50-90°F or 10-32°C | 90°F | Choose the highest selectable temperature setpoint value. |
310 | Setback Low | Off; 50-82°F | 67°F | Temperature setpoint thermostat will Heat to when in Setback mode (Off sets Heating to ~45F Setback). 0 = Off ; 50-82°F (11-27°C) |
320 | Setback High | Off; 58-90°F | 78°F | Temperature setpoint thermostat will Cool to when in Setback mode. (Off sets Cooling to ~150F in Setback). 0 = Off (disabled) 58-90°F (11-32°C) |
325 | Occupied Sensor Operation | 0-1 | 1 | 0 = Disabled 1 = Occupancy Operation ON |
326 | Occupied Timer Duration | 30 min; 1, 2 ,4, 6 8,16,20, 24 hrs | 2 hrs | Sets the time required to go into setback after last detection. |
327 | Setback Ramping | 0, 1, 2 | 1 | Determines how fast the control will setback. 0 = Economy (No delay) 1 = Comfort 1° (1°F per hour) 2 = Comfort 2° (2°F per hour) |
328 | Nighttime Lock On | 0-1 | 1 | Locks the thermostat to Occupied mode after 10:00pm. Thermostat resets at 08:00am. NOTE: This feature requires the clock time to be set. 0 = Disabled (For Schools and Commercial Applications) 1 = ON (For Hospitality and Dorms) |
330 | Zone Temp Offset | +/-9°F or +/-4.5°C | 0°F | Adjusts the sensed Zone Temperature displayed, allowing calibration in the field. |
340 | Keypad Lockout | 0-3 | 0 | Restricts access to certain features of device; Service Menu still available if keypad lockout is enabled. 0 = No key pad lockout (Default) 1 = Disables Schedule and System keys 2 = Disables Schedule, System, and Fan keys 3 = Disables all keys |
341 | Enable Pin Access | 0,1 | 0 | Applies a 3 digit access code to enter Service Menu 342 0 = Disable 1 = Enable |
342 | Set PIN | 000-999 | 000 | Choose a 3-digit PIN access code. |
350 | Fan Mode | 1-3 | 3 | 1 = ON: Fan is always on, regardless of demand 2 = Auto: Fan is only on with heating or cooling demand 3 = ON or Auto: Occupant can choose either selection |
360 | System Mode | 0-3 | 0 | Allows ability to determine which system modes the occupant can select. 0 = OFF, Auto 1 = OFF, Heat, Cool, Auto 2 = OFF, Heat, Cool 3 = Heat, Cool, Auto |
MENU | FEATURE | OPTIONS | STD. DEFAULT | DESCRIPTION / COMMENTS |
375 | Purge Enable | 0-3 | 0 | 0 = No Purge ▲! WARNING: Service Menu 375 may disable fan operation during valve 1 = W1 purge. This feature should be set to 0 (zero) unless outputs are connected 2 = Y1 Purge to hydronic heating or cooling valves. Failure to follow this instruction can 3 = W1 & Y1 purge result in damage to equipment and/or property. |
376 | Purge Duration | 1-3 | 1 | Defines how long to open the valve to perform the purge function. 1 to 3 minutes |
377 | Purge Frequency | 0-2 | 0 | Defines how long to open the valve to perform the purge function. 0 = Every 24 Hours 1 = Every 12 Hours 2 = Every 6 Hours |
380 | Minimum Deadband Adjustment | 1-10°F, 0.5-5°C | 3°F | A changeover deadband value prevents short cycling between heating and cooling modes. The value is adjustable to meet various HVAC system requirements. |
395 | Temporary Occupied Duration Limit | 0-4 hours | 0 | The temporary User Override is limited by the time defined in this service menu. 0 = Remainder of time until the next scheduled event. 1 = 1 Hour 2 = 2 Hours 3 = 3 Hours 4 = 4 Hours |
480 | Minimum Off Time | Range: 0-10 Minutes | 4 | Sets the minimum off time for both the heat and cool output. |
500 | Programmable/ Intermittent Fan | 0-2 | 0 | In programmable mode, fan will operate continuously during occupied periods or with demand during unoccupied periods. In intermittent mode, fan will operate based on the on and off times set in menus 501 and 502 whenever there is no call for fan. 0 = Disable 1 = Programmable Fan: Fan operates continuously in occupied periods or with demand in unoccupied periods. 2 = Intermittent Fan: Fan operates based on the on and off times set in menus 501 and 502. |
501 | Intermittent Fan On Time | 1-60 minutes | 5 minutes | Defines the duration in which fan low will be on. Fan On will be activated after Fan Off time has passed. |
502 | Intermittent Fan Off Time | 0-60 minutes | 25 minutes | Defines the duration in which fan low will be off. Fan Off will be activated after Fan On time has passed. A selection of 0 will result in continuous Fan. |
520 | Default Display Icons | 0-4 | 3 | Select icons that will be displayed in the Default Display screen. 0 = Time, Temp, SP 1 = Time, Temp 2 = Time only 3 = Temp only 4 = No Display |
530 | Revision | — | — | Upon menu selection the firmware revision, firmware checksum, and configuration checksum is displayed. |
540 | Factory Default Reset | 0,1 | 0 | When Enable is selected the device will return to factory default settings. 0 = Disable 1 = Enable Note: Press the “Done” key to complete the process. |
600 | System Test Main Output (Cool) | 0-2 | 0 | If either stage is enabled it will activate the associated output for 10 minutes. The Fan output will automatically turn on. If a different service menu is selected the output will be disabled. 0 = Disable 1= Cool Stage 1 2 = Cool Stage 2 |
610 | System Test Main Output (Heat) | 0-3 | 0 | If either stage is enabled it will activate the associated output for 10 minutes. The Fan output will automatically turn on if configured to do so. If a different service menu is selected the output will be disabled. (Note: Aux heat could be stage 2 or stage 3 based on configuration) 0 = Disable (Default) 1 = Heat Stage 1 2 = Heat Stage 2 3 = Heat Stage 3 |
620 | System Fan Test Output | 0-3 | 0 | 0 = Disabled 1 = Low Speed 2 = Medium Speed 3 = High Speed |
900 | Factory Use Only | — | — | Factory Use Only |
901 | Factory Use Only | — | — | Factory Use Only |
902 | Factory Use Only | — | — | Factory Use Only |
COPYRIGHT 2016 PECO, INC. ALL RIGHTS RESERVED P/N 71969 3220-2345 REV 02
DOWNLOAD MANUALS:
PECO T8532OCC-001 MULTI-FAN OCCUPANCY THERMOSTAT Quick Start Guide
OTHER MANUALS:
PECO T8532OCC-001 MULTI-FAN OCCUPANCY THERMOSTAT Product Specifications Guide
PECO T8532OCC-001 MULTI-FAN OCCUPANCY THERMOSTAT Quick Start Guide
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…