Peco

Peco T8168 Programable Thermostat Product Specifictions Guide

Peco T8168 Programable Thermostat

Precision Digital Outputs

The T8168 Thermostat delivers precision digital outputs for valves, dampers, relays, and fans. Easy single set point technology provides simple accurate control of temperature settings.

System Configurations
Designed to meet a variety of configuration needs.

Temperature

  • 2 Heat/2Cool ON/OFF
  • 1Heat/1Cool TWF
  • 1Heat/1Cool 0-10 VDC

Fan

  • One 0-10 VDC Fan
  • Up to Three 24 VAC Fan
  • Speeds

Applications
Highly versatile control for a variety of applications.

  • Fan Coil
  • Conventional HVAC
  • Proportional Control

The T8168 includes an easily configurable service menu to allow the fast system set up of requirements to limit operation, match user preferences or meet local codes. Controller Application Support Contact PECO to optimize the feature selection that meets your requirements at Controls@astronics.com

KEY BENEFITS

  • Remote, Local or Averaged Temperature Sensing
  • Control for Relays, Valves, and Dampers
  • Non-Programmable or Programmable Operation
  • Keypad Lockout with a PIN
  • Seasonal Summer-Winter Change Over for Fan Coils
  • Fan Coil 2-Pipe/4-Pipe Settings
  • Multiple Fault Notifications
  • Door Open Shut Down
  • Occupancy-based Fan Selection
  • Holiday Scheduling
  • NO/NC Heat W1 configuration
  • Models available with
  • Wi-Fi and BACnet

Wiring

Terminal Description
24 VAC-1 24 VAC 1 (UNSWITCHED)
24 VAC-2 24 VAC 2
24 VAC-2 24 VAC 2
Y1 COOL 1 COOL Open (TWF)
W1 HEAT 1 HEAT Open (TWF)
Y2 COOL 2 or FAN 3 (MED) COOL Close (TWF)
W2 HEAT 2 HEAT Close (TWF)
G FAN 1 (HI)
G1 FAN LO or DAMPER Configurable
YD 0-10VDC COOL (4-20mA)
WD 0-10VDC HEAT (4-20mA)
GD 0-10VDC FAN (4-20mA)
S1 REMOTE SENSOR, FAULT DETECTION
S2 PIPE SENSOR
SC DC /SENSOR COMMON
4A Unused
4B Unused
4C Unused

TWF = Three Wire Floating valve operation

PRODUCT SPECIFICATIONS

Output Ratings

  • Outputs: Y1, Y2, W1, W2, G, G1
  • 24 VAC (20-30 VAC); 50/60 Hz  10 VA
  • Outputs: WD, GD, YD
  • 0-10 VDC: Loads must be 1.2K ohms minimum
  • 4-20 mA: Loads must be 600 ohms maximum

Technical Data

  • Temperature Control Range: 50° to 90° F (10° to 32° C)
  • Differential: 1° F (0.5°C)
  • Input Power: 24 VAC (20-30 VAC) 50/60 Hz (+/- 10%)
  • Operating Temperature: 0° to 120°F (-18° to 49°C)
  • Operating Humidity: 5% to 95% RH, non-condensing
  • Physical Dimensions: 4.3” H x 5.7” W x 1.3”D
  • Terminal Connections: 14-24 AWG stranded or solid wire
  • Proportional Output Band Width: 2°F (1°C)
  • Proportional Stroke Time Default: 2 Minutes (Configurable)

The PECO® Performance PRO™ T8168 APPLICATIONS INCLUDE fan coil, PTAC, and Conventional system with a single, multi-speed, or 0-10 VDC Fan.

Get Started Today
For additional details, please contact PECO Control Systems. 11241 SE Highway 212 Clackamas, OR 97015 503-387-6410
Controls@astronics.com pecocontrolsystems.com
© Astronics PECO T8168 Data Sheet 2020.1

REFERENCE:

Download manuals:

Peco T8168 Programmable Thermostat Product Specification Guide

Other manuals:

Peco T8168 Programmable Thermostat Installation Guide

Peco T8168 Programmable Thermostat Product Specifications Guide

wpx_thermostats

Recent Posts

Johnson Controls T7000e LCD Digital Thermostat Installation Guide

Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide

1 year ago

Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’S GUIDE

Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE

1 year ago

Hetta HS01RF WIRELESS THERMOSTAT KIT USER MANUAL

Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…

1 year ago

HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat USER MANUAL

HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…

1 year ago

Honeywell RLV450 PROGRAMMABLE THERMOSTAT USER GUIDE

Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…

1 year ago

Honeywell RLV431 Programmable Thermostat User Guide

Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…

1 year ago