Neptronic

Neptronic TFCB24F3XYZ1 Fan Coil Thermostat Specification and Installation Instructions

Neptronic TFCB24F3XYZ1 Fan Coil Thermostat

Description

The TFCB24F3XYZ1 is a fully configurable controller designed specifically for 2 pipe and 4 pipe fan coil applications. No additional modules are required as the required inputs, outputs and control algorithms are built into the unit. The TFCB24F3XYZ1 also provides support for networked communications via the BACnet MS/TP protocol

Applications

  • Heating, cooling and reheat
  • 2 pipes or 4 pipes
  • Auxiliary heating sources, such as electric baseboards, can also be applied

Typical Application
Fan coil applications provide heating and cooling to a zone by circulating hot and cold air depending on the demand to maintain an optimum temperature in the selected space. A fan coil setup typically consists of fan coil units, source for hot and cold water, and a pipe system for distribution. When there is a demand for heating, the hot water is supplied to the unit through the source and passes over the heating coil, and the hot air is pushed into the zone by the fan. When there is a demand for cooling, the cold water is supplied to the unit through the source and passes over the cooling coil, and the cold air is pushed into the zone by the fan.

Features

  • Backlit LCD with simple icon and text driven menus
  • Configurable inputs and outputs
  • 2 Pipes with Analog, ON/OFF, or Floating option
  • 4 Pipes with Analog, ON/OFF, or with local reheat function
  • Precise temperature control with programmable PI function
  • Selectable Fahrenheit or Celsius scale
  • Independent cool and heat setpoint for No Occupancy
  • Lockable setpoint, control mode, and fan mode
  • Selectable internal or external temperature sensor
  • Changeover by contact or external temperature sensor
  • Selectable proportional control band and dead band
  • Anti-freeze protection
  • BACnet® MS/TP @ 9600, 19200, 38400, or 76800 bps
  • Selectable MAC address
  • Automatic or manual device instance assignment
  • Automatic baud rate detection
  • Copy and broadcast configuration to other networked TFCB24F3XYZ1 modules

Technical Specifications

Interface

Wiring

We strongly recommend that all Neptronic products be wired to a separate grounded transformer and that the transformer shall service only Neptronic products. This precaution will prevent interference with, and/or possible damage to incompatible equipment

Wiring – 2 Pipe Terminal Description Details – 2 Pipe

Terminals Analog On/Off Floating Step
1 Common Common Common Common
2 24 Vac 24 Vac 24 Vac 24 Vac
3 Common TRIAC Common TRIAC Common TRIAC Common TRIAC
4 TRIAC Output 1 (TO1) 2 pipe on/off 2 pipe floating (close) 9
5 TRIAC Output 2 (TO2) 2 pipe floating (open) 9
6 TRIAC Output 3 (TO3) Local reheat * Local reheat * Local reheat * 21
Fan 1 speed 2

speed

3

speed

Analog 1

speed

2

speed

3

speed

Analog 1

speed

2

speed

3

speed

Analog
7 Common Relay Common Relay Common Relay Common Relay
8 Digital Output 1 (DO1) High High High 33
9 Digital Output 2 (DO2) High Med High Med High Med 33
10 Digital Output 3 (DO3) Low Low Low AO4 Low Low Low AO4 Low Low Low AO4 33
11 Digital Input 1 (DI1) Occupancy Sensor * Occupancy Sensor * Occupancy Sensor *
12 Analog Input (AI1) External Temp Sensor * External Temp Sensor * External Temp Sensor * 38
13 Analog Input (AI2) External Changeover * External Changeover * External Changeover * 13
14 Analog Output 1 (AO1) 2 pipe analog 9
15 Analog Output 2 (AO2) 9
16 Analog Output 3 (AO3) Local reheat * Local reheat * Local reheat * 21
17 A+ BACnet communication BACnet communication BACnet communication
18 B- BACnet communication BACnet communication BACnet communication

Wiring – 4 Pipe Terminal Description Details – 4 Pipe

Terminals Cool: Analog Heat: Analog Cool: On/Off Heat: On/Off Cool: Analog Heat: On/Off or Pulse Cool: On/Off Heat: Analog Step
1 Common Common Common Common Common
2 24 Vac 24 Vac 24 Vac 24 Vac 24 Vac
3 Common TRIAC Common TRIAC Common TRIAC Common TRIAC Common TRIAC
4 TRIAC Output 1 (TO1) 4 pipe cool (on/off) 4 pipe cool (on/off) 9
5 TRIAC Output 2 (TO2) 4 pipe heat (on/off or pulse) 4 pipe heat (on/off or pulse) 9
6 TRIAC Output 3 (TO3) Local reheat * Local reheat * Local reheat * Local reheat * 21
Fan 1

speed

2

speed

3

speed

Analog 1

speed

2

speed

3

speed

Analog 1

speed

2

speed

3

speed

Analog 1

speed

2

speed

3

speed

Analog
7 Common Relay Common Relay Common Relay Common Relay Common Relay
8 Digital Output 1 (DO1) High High High High 33
9 Digital Output 2 (DO2) High Med High Med High Med High Med 33
10 Digital Output 3 (DO3) Low Low Low AO4 Low Low Low AO4 Low Low Low AO4 Low Low Low AO4 33
11 Digital Input 1 (DI1) Occupancy Sensor * Occupancy Sensor * Occupancy Sensor * Occupancy Sensor *
12 Analog Input (AI1) External Temp Sensor * External Temp Sensor * External Temp Sensor * External Temp Sensor *
13 Analog Input (AI2) 13
14 Analog Output 1 (AO1) 4 pipe cool (analog) 4 pipe cool (analog) 18
15 Analog Output 2 (AO2) 4 pipe heat (analog) 4 pipe heat (analog) 15
16 Analog Output 3 (AO3) Local reheat (analog)* Local reheat (analog)* Local reheat (analog)* Local reheat (analog)* 21
17 A+ BACnet communication BACnet communication BACnet communication BACnet communication
18 B- BACnet communication BACnet communication BACnet communication BACnet communication

Jumpers

Jumpers Description
JP1 TRIAC Output Signal Selector A&B = Internal: All TRIAC output signals are linked to internal 24 Vac (same as thermostat).

B&C = External: All TRIAC output signals are linked to external 24 Vac (different than thermostat).

JP2 Digital Output Signal Selector A&B = Internal: All digital output signals are linked to internal 24 Vac (same as thermostat). B&C = External: All digital output signals is linked to external 24 Vac (different than thermostat).
JP3 Mode Selection A&B = RUN: Thermostat is in Operation Mode. (See Operation Mode, page 14)

B&C = PGM: Thermostat is in Programming Mode. (See Programming Mode, page 5)

JP4 Fan Output Signal Selection A&B: Pin 10 of TB1 is set to digital output signal (DO3). (See Step 33) B&C: Pin 10 of TB1 is set to analog output signal (AO4). (See Step 33)
JP6 End of Line A&B: No End of Line.

B&C: 120 Ohm End of Line (on the last TFCB24F3XYZ1 of the RS-485 communication bus).

Jumpers

Jumpers Description
JP1 TRIAC Output Signal Selector A&B = Internal: All TRIAC output signals are linked to internal 24 Vac (same as a thermostat).

B&C = External: All TRIAC output signals are linked to external 24 Vac (different than thermostat).

JP2 Digital Output Signal Selector A&B = Internal: All digital output signals are linked to internal 24 Vac (same as a thermostat). B&C = External: All digital output signals are linked to external 24 Vac (different than thermostat).
JP3 Mode Selection A&B = RUN: Thermostat is in Operation Mode. (See Operation Mode, page 14)

B&C = PGM: The thermostat is in Programming Mode. (See Programming Mode, page 5)

JP4 Fan Output Signal Selection A&B: Pin 10 of TB1 is set to digital output signal (DO3). (See Step 33) B&C: Pin 10 of TB1 is set to analog output signal (AO4). (See Step 33)
JP6 End of Line A&B: No End of Line.

B&C: 120 Ohm End of Line (on the last TFCB24F3XYZ1 of the RS-485 communication bus).

Mounting Instructions

  • Remove the captive screw that’s holding the base and the front cover of the unit together.
  • Lift the front cover of the unit to separate it from the base.
  • Pull all wires through the holes in the base.
  • Secure the base to the wall using wall anchors and screws (supplied). Make the appropriate connections.
  • Mount the control module on the base and secure using the screw

Programming Mode

Symbols used in this Manual

Setpoint and User Control

inside temper sensor offset”

  • Range: 10.0ºC to 40.0ºC [50ºF to 104.0ºF]
  • Offset: Max. ± 5ºC
  • Increment: 0.1ºC [0.2ºF]

Compare the displayed temperature reading with a known value from a thermometer. To offset or calibrate the sensor, use the arrows button to set the desired temperature reading. This is useful for thermostats installed in areas where the temperature read is slightly different than the room’s actual temperature. For example, a thermostat placed right under the air diffuser. If the thermostat is set to use an external temperature sensor, (t10.0 at Step 38), the thermostat displays “OFF”.

“Adjust minimum user setpnt”

  • Default: 15.0ºC [59ºF]
  • Range: 10.0ºC to 40.0ºC [50ºF to 104ºF]
  • Increment: 0.5ºC [1ºF]

In Operation mode, you cannot decrease the setpoint to less than the value that is set as the minimum user point. The minimum value is restricted by the maximum value set at Step 3. In other words, the value that is set as the minimum cannot be greater than the maximum value.

“Adjust maximum user setpnt”

  • Default: 30.0ºC [86ºF]
  • Range: 10.0ºC to 40.0ºC [50ºF to 104ºF]
  • Increment: 0.5ºC [1ºF]

In Operation mode, you cannot increase the setpoint to more than the value that is set as the maximum user point. The maximum value is restricted by the minimum value set at Step 2. In other words, the value that is set as the maximum cannot be less than the minimum value.

“User setpoint locked”

  • Default: No (Unlocked)
  • Range: Yes (Locked)/No (Unlocked)

If set to No, the user setpoint option is not locked and the user can adjust the desired setpoint temperature. If set to Yes, the user setpoint option is locked and the user cannot set the desired setpoint temperature. A lock symbol appears indicating that the setpoint is locked.

“Adjust intern setpoint”

  • Default: 22.0ºC [72ºF]
  • Range: 10.0ºC to 40.0ºC [50ºF to 104ºF]
  • Increment: 0.5ºC [1ºF]

Set the desired temperature setpoint within the defined range. If the setpoint option was locked in Step 4, a lock symbol is displayed. The setpoint value is restricted by the minimum (Step 2) and maximum (Step 3) values. In other words, the setpoint should be within in the range of minimum and maximum setpoints.

“Adjust temper control mode”

  • Default: Auto (Automatic)
  • Range: Auto (Automatic Cooling and Heating), ON (Cooling or Heating), Heat (Heating Only), Cool (Cooling Only)

enable on off control mode”

  • Default: Yes (Enable)
  • Range: Yes (Enable)/No (Disable)

If you select Yes, the user can set the unit to “Off” via the Control Mode (see page 15). If you select No, the “Off” selection does not appear in the Control Mode.

Pipe System Selection

“select 2 pipe 4 pipe system”

  • Default: 2P (2 pipe)
  • Range: 2P (2 pipe)/4P (4 pipe)

“select 2 pipe signal”

  • Default: AnLG (Analog)
  • Range: AnLG (Analog), OnOf (On/Off), Flt (Floating)

Select the desired signal output for your 2 pipe system from the available options. The cooling and heating symbols are also displayed.

  • If you select analog signal, AO1 will be set to automatic heat/cool changeover.
  • If you select OnOf, TO1 will be set to automatic heat/cool changeover.
  • If you select Flt, TO1 will be set to close and TO2 will be set to open.

“set floating time in seconds”

  • Default: 100 seconds
  • Range: 15 to 250 seconds
  • Increment: 5 seconds

Outputs

“min vdc analog output”

  • Default: 0.0 Volt
  • Range: 0.0 to 10.0 Volt
  • Increment:0.1 Volt

Select the desired minimum voltage (zero value) for the analog ramp. The minimum value (Step 11) is restricted by the maximum value (Step 12). In other words, the minimum value should be less than the maximum value

“max vdc analog output”

  • Default: 10.0 Volt
  • Range: 0.0 to 10.0 Volt
  • Increment: 0.1 Volt

Select the desired maximum voltage (span value) for the analog ramp. The maximum value (Step 12) is restricted by the minimum value (Step 11). In other words, the maximum value should be greater than the minimum value.

Ch over temper sensor”

  • Default: SENs (External Changeover Sensor)
  • Range: SENs, NoCl, NoHt

If SENs is selected: heating mode activates when the temperature read by the external sensor is above the Changeover Setpoint and cooling mode activates when the temperature read by the external sensor is below the Changeover Setpoint. (see Step 14)

“Ch over setpnt temper”

  • Default: 24.0ºC [75ºF]
  • Range: 10.0ºC to 40.0ºC [50ºF to 104ºF]
  • Increment: 0.5ºC [1ºF]

This option appears if you have set one of the analog inputs to SENs (External Changeover Sensor) at Step 13. Set the desired changeover temperature setpoint. Note that the heating mode activates when the temperature read by the external sensor is above the changeover setpoint and cooling mode activates when the temperature read by the external sensor is below the changeover setpoint.

select 4 pipe heating signal”

  • Default: AnLG (Analog)
  • Range: AnLG (Analog), OnOf (On/Off), PULs (Pulse)

This option appears if you have selected 4P at Step 8. Select the heating signal for your 4 pipe system.

  • If you select AnLG (Analog), AO2 will be set to heating.
  • If you select OnOf (On/Off), or PULs (Pulse), TO2 will be set to heating.

“min vdc analog output heating”

  • Default: 0.0 Volt
  • Range: 0.0 to 10.0 Volt
  • Increment: 0.1 Volt

Select the desired minimum voltage (zero value) for heating ramp. The minimum value (Step 16) is restricted by the maximum value (Step 17). In other words, the minimum value must be less than the maximum value

“max vdc analog output heating”

  • Default: 10.0 Volt
  • Range: 0.0 to 10.0 Volt
  • Increment: 0.1 Volt

Select the desired maximum voltage (span value) for heating ramp. The maximum value (Step 17) is restricted by the minimum value (Step 16). In other words, the maximum value must be greater than the minimum value.

“select 4 pipe cooling signal”

  • Default: AnLG (Analog)
  • Range: AnLG (Analog), OnOf (On/Off)

This option appears if you have selected 4P at Step 8. Select the desired cooling signal output for your 4 pipe system.

  • If you select the AnLG (analog) signal, AO1 will be set to cooling.
  • If you select the OnOf (on/off) signal, TO1 will be set to cooling

min vdc analog output cooling

  • Default: 0.0 Volt
  • Range: 0.0 to 10.0 Volt
  • Increment:0.1 Volt

Select the desired minimum voltage (zero value) for cooling ramp. The minimum value (Step 19) is restricted by the maximum value (Step 20). In other words, the minimum value must be less than the maximum value

“max vdc analog output cooling ”

  • Default: 10.0 Volt
  • Range: 0.0 to 10.0 Volt
  • Increment: 0.1 Volt

Select the desired maximum voltage (span value) for cooling ramp. The maximum value (Step 20) is restricted by the minimum value (Step 19). In other words, the maximum value should be greater than the minimum value

“set local reheat signal”

  • Default: OFF (no signal selected
  • Range: OFF, AnLG, AnLG, On/Of, On/Of, PuLS, PuLS

Select the desired signal output for reheat.

  • If you select AnLG (Analog, heating and fan), AO3 will be set to reheat.
  • If you select On/Of (On/Off heating and fan) or PuLS (Pulse heating and fan), TO3 will be set to reheat

If you selected On/Of (On/Off heating and fan), or or PuLS (Pulse heating and fan), go to Step 24.

“min vdc analog output reheat”

  • Default: 0.0 Volt
  • Range: 0.0 to 10.0 Volt
  • Increment: 0.1 Volt

Select the desired minimum voltage (zero value) of reheat ramp. The minimum value (Step 22) is restricted by the maximum value (Step 23). In other words, the minimum value must be less than the maximum value

“max vdc analog output reheat”

  • Default: 0.0 Volt
  • Range: 0.0 to 10.0 Volt
  • Increment: 0.1 Volt

Control Ramps

“control ramp reheat”

  • Default:  2.0ºC [4ºF]
  • Range: 0.5ºC to 5.0ºC[1ºF to 10ºF]
  • Increment: 0.5ºC [1ºF]

“control dead band reheat”

  • Default: 0.3ºC [0.6ºF]
  • Range: 0.3ºC to 5.0ºC[0.6ºF to 10.0ºF]
  • Increment: 0.1ºC [0.2ºF]

“control ramp HEATing”

  • Default: 2.0ºC [4ºF]
  • Range: 0.5ºC to 5.0ºC[1ºF to 10ºF]
  • Increment: 0.5ºC [1ºF]

“control ramp cooling”

  • Default: 2.0ºC [4ºF]
  • Range: 0.5ºC to 5.0ºC[1ºF to 10ºF]
  • Increment: 0.5ºC [1ºF]

“control dead band heating”

  • Default: 0.3ºC [0.6ºF]
  • Range: 0.3ºC to 5.0ºC[0.6ºF to 10.0ºF]
  • Increment: 0.1ºC [0.2ºF]

“control dead band cooling”

  • Default: 0.3ºC [0.6ºF]
  • Range: 0.3ºC to 5.0ºC[0.6ºF to 10.0
  • Increment: 0.1ºC [0.2ºF]

Other Settings

“cooling anti cycle minutes”

  • Default: 2 minutes
  • Range: 0 to 15 minutes
  • Increment: 1 minute

adjust intgral time in seconds”

  • Default: 0 secon
  • Range: 0 to 250 seconds
  • Increment: 5 seconds

“adjust damping factor seconds”

  • Default: 0 second
  • Range: 0 to 10 seconds
  • Increment: 1 second

“select fan speed signal”

  • Default: 3 (speed fan contact)
  • Range: (speed fan contact), 2 (speed fan contact), 3 (speed fan contact), AnLG (Analog)

“min vdc analog output fan”

Select the desired minimum voltage (zero value) for fan ramp. The minimum value (Step 34) is restricted by the maximum value (Step 35). In other words, the minimum value should be less than the maximum value. The fan symbol is also displayed

  • Default: 0.0 Volt
  • Range: 0.0 to 10.0 Volt
  • Increment: 0.1 Volt

“max vdc analog output fan”

Select the desired maximum voltage (span value) for fan ramp. The maximum value (Step 35) is restricted by the minimum value (Step 34). In other words, the maximum value must be more than the minimum value. The fan symbol is also displayed.

  • Default: 10.0 Volt
  • Range: 0.0 to 10.0 Volt
  • Increment: 0.1 Volt

“enable fan auto mode”

Select the Enable or Disable option to allow the user to adjust the Automatic mode. The fan symbol is also displayed.

  • Default: Yes (Enable)
  • Range: Yes (Enable)/No (Disable)

“fan auto timeout minutes”

  • Default: 2 minutes
  • Range: 0 to 15 minutes
  • Increment: 1 minute

External Temperature Sensor

External Temperature Sensor

  • Default: OFF (input none rewired
  • Range: OFF (input none rewired), t10.0 (external temperature sensor 10.0 KΩ)

Select the sensor that should be rewired to the analog output.

  • If you select OFF, the thermostat will be controlled by its internal temperature sensor.
  • If you select t10.0, the thermostat will be controlled by an external temperature sensor

“extern temper sensor offset”

  • Offset: Max. ± 5ºC
  • Range: 0.0ºC to 50.0ºC [41.0ºF to 122.0ºF]
  • Increment: 0.1ºC [0.2ºF]

This option appears if you have set one of the analog inputs to t10.0 (External temperature sensor 10.0 KΩ) at step 38. When the thermostat is connected to the appropriate analog input (AI1 or AI2), the display shows the temperature read by the external temperature sensor. Adjust the offset by comparing it with a known value (e.g. thermometer). If the sensor is not connected or short circuited, the display is blank “Error“, and the error symbol is displayed.

No Occupancy

“Select occ contact”

  • Default: NO (Normally Open
  • Range: NO (Normally Open)/NC (Normally Close)

“no occ delay overide minutes”

Select the desired heating setpoint temperature during the no occupancy period. The maximum value is restricted by the cooling setpoint in the no occupancy period (Step 43). In other words, the maximum value must be greater than the no occupancy cooling setpoint value. The moon and heating symbols are also displayed.

  • Default: 2 minutes
  • Range: 0 to 15 minutes
  • Increment: 1 minute

“no occ heating setpnt”

  • Default: 2 minutes
  • Range: 0 to 15 minutes
  • Increment: 1 minute

“no occ cooling setpnt”

Select the desired cooling setpoint temperature during the no occupancy period. The minimum value is restricted by the heating setpoint in the no occupancy period (Step 42). In other words, the minimum value must be less than the no occupancy heating setpoint value. The moon and cooling symbols are also displayed

  • Default: 28.0ºC [82ºF]
  • Range: 10.0ºC to 40.0ºC [50ºF to 104ºF]
  • Increment: 0.5ºC [1ºF]

Anti-Freeze

“enable anti freeze protect”

If this option is enabled, heating starts automatically when the temperature drops to 4ºC [39ºF], even if the thermostat is in OFF mode. Once the temperature reaches 5ºC [41ºF], the heating stops

  • Default: No (Disable)
  • Range: No(Disable)/Yes (Enable)

BACnet Settings

“auto BAUDS RATE”
Enable or disable Auto Baud Rate Detection. If you enable this option, the controller configures its baud rate automatically by detecting the network speed upon connection to the network (go to Step 46). If you disable this option, you must select the baud rate manually (go to Step 47).

  • Default: Yes (Enable)
  • Range: Yes (Enable)/No (Disable)

“auto comport BAUDS RATE”

  • Default: No default (information display only)
  • Range: 9600, 19200, 38400, 76800

“adjust comport bauds rate”

  • Default: 9.6 kBps
  • Range: 9.6k, 192.k, 38.4k, 76.8k

“adjust MSTP Mac address”

  • Default: 1
  • Range: 0 TO 254
  • Increment: 1

“copy config”
Select Yes to copy the configuration of the existing device to other devices of the same type on the network. If you select No, go to Step 53.

  • Default: No
  • Range: Yes/No

“Select begin address”
Select the first address you want to copy to. For example, if you select MAC address 1 as the begin address and 54 as the end address, all the devices from 1 to 54 will receive the configuration of the current device.

  • Default: 0
  • Range: 0-254
  • Increment: 1

“Select end address”
Select the last address you want to copy to. You cannot copy more than 64 addresses at once.

  • Default: “begin address
  • Range: “begin address + 63”
  • Increment: 1

“Copy config result”
Displays “Succeed” if the addresses have been copied successfully. Otherwise, an error message appears with the associated MAC address. You can scroll through the addresses and see the error message associated with each address. The following is a complete list of error messages

Range: Copy Config” followed by one of these results: “Succeed”, “Progerr”, “Typeerr”, “Modlerr”, “Memerr”, “Slave”, “Commerr”

  • copy config succeed”
    • Copy config was successful.
  • “copy config progerr”
    • Copy config failed because the target device is in Program Mode.
  • “copy config typeerr”
    • Copy config failed because the target device is not the same as the source device. For example, copying a TRO configuration to a TFC device.

  • copy config modlerr”
    • Copy config failed because the model number of the source device and the target device is not the same. For example, copying a TFCB24F3XYZ1 configuration to a TFC24F3YZ1.
  • “copy config mem err”
    • Copy config failed because the software/application version of the source device and the target device is not the same.
  • “copy config Slave”
    • The target device has a slave address and it cannot respond to the master. Manually verify that the configuration was copied correctly or avoid using a slave address (128 – 254).
  • “copy config commerr”
    • Copy config failed because the target device did not respond after 3 attempts. Either the address does not exist or there is a problem with the wiring or with noise.

“adjust device instanc 0153000”
To change the device instance, select Yes and continue to the next step. If you select No, the device instance will be modified automatically according to the MAC address (the menu starts over at Step 1).

  • Default: No
  • Range: No/Yes

“0153000”

  • Default:”current value”
  • Range: 0 to 4194302
  • Increment: 1

Use the arrow buttons to change the value and press to move to the next digit on the right or press to move to the digit on the left. Ensure that you provide a unique device instance. Set the Jumper (JP3) to “RUN” mode (Operation Mode) to save the changes

BACnet Setup Operation Mode

The BACnet Setup mode is accessible through the normal Operation mode.

  • The Mode Selector Jumper (JP3) must be set to the “RUN” mode (Operation Mode). Refer to Wiring on page 2.
  • Press the buttons for 5 seconds. The “Enter Password” screen appears.
  • Enter the password (637) within 1 minute. Use the arrow buttons to increase or decrease the value and theor , to advance and return to the digits respectively. If you enter the wrong password, the thermostat displays “Eror” and returns to Operation Mode.
  • If you enter the password correctly, you will be taken to the BACnet program mode. The symbol is displayed indicating that the BACnet mode is active. In the BACnet mode, press the button to advance to the next program function and to return to the previous program function. Use the buttons to adjust the values

“auto BAUDS RATE” to “adjust device instance”
These BACnet setup steps are exactly the same as those in the Programming Mode. Please refer to Steps 45 to 54 starting on page 11. When complete continue to the following step.

  • Range: Steps 45 to 54
  • Page: Page 11 and 13

“INSIDE TEMPER SENSOR OFFSET”
Compare the displayed temperature reading with a known value from a thermometer. To offset or calibrate the sensor, use the arrows button to set the desired temperature reading. This is useful for thermostats installed in areas where the temperature read is slightly different than the room’s actual temperature. For example, a thermostat placed right under the air diffuser

  • Offset: Max. ± 5 ºC
  • Range: 10.0ºC to 40.0ºC [50.0ºF to 104.0ºF]
  • Increment: 0.1ºC [0.2ºF]

“extern temper sensor offset”
This option appears if you have set one of the analog inputs to t10.0 (External temperature sensor 10.0 KΩ) at step 38. When the thermostat is connected to input (AI1), the display shows the temperature read by the external temperature sensor. Adjust the offset by comparing it with a known value (e.g. thermometer). If the sensor is not connected or short circuited, the display is blank “Error“, and the error symbol is displayed.

  • Offset: Max. ± 5ºC
  • Range: 0.0ºC to 50.0ºC [41.0ºF to 122.0ºF]
  • Increment: 0.1ºC [0.2ºF]

Operation Mode

The Mode Selector Jumper (JP3) must be set to the “RUN” mode (Operation Mode). Refer to Wiring on page 2. To exit, set the Jumper (JP3) back to the “PGM” mode (Programming Mode). All changes will be saved

Power Up
Upon power up, the LCD illuminates and all segments appear for 2 seconds. The thermostat then displays its current version for 2
seconds.

LCD Backlight
Pressing any button on the thermostat illuminates the LCD for 4 seconds.

Temperature
The thermostat always displays the temperature reading. If the sensor is disconnected or short circuited then “OFF”, “- – -”, (alarm symbol) are displayed. To toggle the temperature scale between ºC and ºF, press both the buttons for 3 seconds.

Setpoint
To display the setpoint, press the button twice. The setpoint appears for 3 seconds. To adjust the setpoint, press the buttons while the temperature is displayed. If the setpoint adjustment has been locked (Step 4 on page 6), the lock symbol appears.

No Occupancy Mode

This function is only available if you have selected the derogation time at Step 41 on page 11. If the no occupancy is triggered, the thermostat enters the No Occupancy Mode (the symbol appears) and uses the heating and cooling setpoints defined at Step 42 and 43 on page 11. The user can press any button to override the duration of No Occupancy. The symbol flashes to indicate that the derogation period is on. If the symbol does not flash, it means that the derogation period is complete or that the No Occupancy Mode derogation option has been locked

Control Mode
To access the Control Mode, press the button. The Control Mode appears for 5 seconds. These options can vary depending on the options selected at Steps 6 and 7 on page 6.

  • Auto (Automatic Cooling or Heating)
  • Cooling only (on)
  • Heating only (on)
  • OFF

Fan Speed Selection Mode
To access the Fan Speed selection mode, press the button. The mode appears for 5 seconds. These options can vary depending on the fan speed signal and auto mode settings at Step 33 and Step 36 on page 10.

  • Automatic speed. This option is available if you have selected Yes (Enable) at Step 36 in Programming Mode.
  • Low speed
  • Medium speed
  • High speed
  • Off

Neptronic

  • 400 Lebeau blvd, Montreal, Qc, H4N 1R6, Canada
  • www.neptronic.com
  • Toll free in North America: 1-800-361-2308
  • Tel.: (514) 333-1433
  • Fax: (514) 333-3163
  • Customer service fax: (514) 333-1091
  • Monday to Friday: 8:00 am to 5:00 pm (Eastern time)

REFERENCE:

DOWNLOAD MANUALS:

Neptronic TFCB24F3XYZ1 Fan Coil Thermostat Specification and Installation Instructions

Neptronic TFCB24F3XYZ1 Fan Coil Thermostat Specification and Installation Instructions

wpx_thermostats

Recent Posts

Johnson Controls T7000e LCD Digital Thermostat Installation Guide

Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide

1 year ago

Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’S GUIDE

Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE

1 year ago

Hetta HS01RF WIRELESS THERMOSTAT KIT USER MANUAL

Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…

1 year ago

HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat USER MANUAL

HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…

1 year ago

Honeywell RLV450 PROGRAMMABLE THERMOSTAT USER GUIDE

Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…

1 year ago

Honeywell RLV431 Programmable Thermostat User Guide

Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…

1 year ago