Recommended locations for your thermostat.
To ensure that your thermostat provides accurate readings and controls effectively, it must be installed approximately 1.5 m above floor level on an inside wall, away from direct sunshine and any other sources of heat or cold such as radiators, cold draughts, etc.
All electrical installation work should be carried out by a suitably qualified Electrician or another competent person. If you are not sure how to install this thermostat consult either with a qualified electrician or heating Engineer. Do not remove or refit the appliance onto the backplate without the mains supply to the system is isolated. All wiring must be in accordance with IEE regulations. This product is for fixed wiring only.
All wiring must be in accordance with IEE regulations. This product is for fixed wiring only.
Access
Move the mode slider to
Set °C/°F temperature
Set 12/24 hours clock
The pre-set value is 12 hours clock.
Set calibration
Important: This operation is reserved for professional installers only; any wrong8 changes would result in control anomalies. Change should only be made if the temperature measured (measured by a reliable ther- mometer) is different by at least 1’C compared to the setpoint temperature of the room thermostat. The calibration adjusts the temperature measured by the ambient temperature sensor to compensate for a deviation from+3C to- 3C in increments of 0.1’C.
IMPORTANT: Before carrying out the calibration it is recommended to wait for 4h af ter a setpoint temperature modification to insure that the ambient temperature is stabilized.
The pre-set calibration value is 0.
Program lock
The product is unlocked by default, OFF is displayed.
When the program lock function is turned on then following functions will be disabled:
Select 2 points/TPI
The pre-set control algorithm is TPI.
Display disappears on thermostat.
The heating does not come on or does not go off.
You want to change the operating mode but when you move the mode slider nothing happens.
The thermostat is in Auto Mode but programs are not being executed by the boiler:
The thermostat does not control properly.
Note: It is recommended to replace annually as part of the normal system service and before leaving the property empty for a prolonged period.
Environment:
UKCA declaration of conformity: We, Neomitis Ltd, hereby declare under our sole responsibility that the products described in these instructions comply with statutory instruments 2016 No.1101 (Electrical Equipment safety Regulations), ), 2016 No.1091 (Electromagnetic Compatibility Regulations) , 2012 n°3032 (ROHS) and following designated standards:
Neomitis Ltd: 16 Great Queen Street, Covent Garden, London, WC2B 5AH UNITED KINGDOM – contactuk@neomitis.com
EU declaration of conformity
We, Imhotep Creation, hereby declare under our sole responsibility that the products described in these instructions comply with the provisions of Directives and harmonized standards listed below: –
Control class and energy contribution, according to ERP 2009/125/EC and related regulations
Class IV – PID Room Thermostat, for use with on/off heating devices. Electronic room thermostat that controls both the cycle time of the thermostat and the ratio between on and off periods during the same cycle of the heating device, depending on the room temperature. PID control reduces the average water temperature, improves the accuracy of room temperature control, and increases system efficiency. The symbol , affixed on the product indicates that you must dispose of it at the end of its useful life at a special recycling point, in accordance with European Directive WEEE 2012/19/EU. If you are replacing it, you can also return it to the retailer from which you buy the replacement equipment. Thus, it is not ordinary household waste. Recycling products enables us to protect the environment and to use less natural resources.
NEOMITIS
DOWNLOAD MANUAL
NEOMITIS RTE1A PROGRAMMABLE ROOM THERMOSTAT INSTALLATION INSTRUCTION
OTHER MANUALS:
NEOMITIS RTE1A PROGRAMMABLE ROOM THERMOSTAT OPERATING Instruction
NEOMITIS RTE1A PROGRAMMABLE ROOM THERMOSTAT INSTALLATION INSTRUCTION
Please select text to grab.
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…