IMPORTANT!
Thank you for your confidence in our product. To obtain the best results from your investment, please read and follow the installation procedures carefully, and one step at a time. This will save you time and minimize the chance of damaging either the thermostat or possibly your heating and cooling system. These instructions may contain information beyond that which may be required for your particular installation.
WARNING: Use Energizer® or DURACELL® Alkaline Batteries Only. Energizer® is a registered trademark of Eveready Battery Company, Inc. DURACELL® is a registered trademark of The Procter & Gamble Company
CAUTIONS AND WARNINGS
The electrical rating for this thermostat is 1.5 Amps per terminal, with a maximum total combined load of 2.0A for all terminals combined.
COMPATIBLE WITH
NOT COMPATIBLE WITH
TOOLS YOU MAY NEED
MOUNTING LOCATION
On replacement installations, mount the new thermostat in place of the old one unless the conditions listed below suggest otherwise. On new installations, please follow these general guidelines:
WARNING
All wiring must conform to the local codes and ordinances that are in your particular location.
REMOVE OLD THERMOSTAT
INSTALL THERMOSTAT BASE
CONNECTING THE WIRES
When attaching the wires to the thermostat, please ensure that the bare wire ends are held ALL the way into the terminal block while the screw is being tightened.
WIRING BASE PLATE NOTICE
This thermostat model is part of a family of similar models that have the same general visual appearance. Even though this base plate may look the same as base plates from other models, the wiring connections may have different terminal letters for different purposes. Please do not interchange the back plates and/or thermostat front halves of other similar-looking models. Doing so may cause undesired heating and/or cooling operations to occur.
WIRING DIAGRAM NOTES
(Important, please read all notes before connecting wires)
2 / 3 / 4 WIRES
CONVENTIONAL, NON-HEAT PUMP
1-STAGE, HEAT ONLY (INCLUDING MILLIVOLT)
NOTE: THE BLACK TERMINAL LETTERS ARE TYPICAL, GRAY TERMINAL LETTERS ARE BRAND SPECIFIC
3 / 4 WIRES
CONVENTIONAL, NON-HEAT PUMP 1-STAGE, COOL ONLY
NOTE: THE BLACK TERMINAL LETTERS ARE TYPICAL, GRAY TERMINAL LETTERS ARE BRAND SPECIFIC
4 / 5 WIRES
CONVENTIONAL, NON-HEAT PUMP 1-STAGE HEAT AND 1-STAGE COOL
NOTE: THE BLACK TERMINAL LETTERS ARE TYPICAL, GRAY TERMINAL LETTERS ARE BRAND SPECIFIC
5 / 6 WIRES
CONVENTIONAL, NON-HEAT PUMP 1-HEAT / 1-COOL, WITH TWO-TRANSFORMERS
NOTE: THE BLACK TERMINAL LETTERS ARE TYPICAL, GRAY TERMINAL LETTERS ARE BRAND SPECIFIC
4 / 5 WIRES
HEAT PUMP SYSTEMS
1-HEAT / 1-COOL, WITH NO AUXILIARY / EMERG. HEAT
NOTE: THE BLACK TERMINAL LETTERS ARE TYPICAL, GRAY TERMINAL LETTERS ARE BRAND SPECIFIC
INSTALL BATTERIES INTO THERMOSTAT: Install two brand new Energizer® or DURACELL® “AA” size alkaline (only) batteries, into the thermostat’s battery compartment. Ensure the batteries are installed in the proper direction.
GAS / ELEC CIRCUIT BOARD OPTION (“G” TERMINAL FAN OPERATION)
This setting is a plastic shorting cap called a jumper. This jumper must remain installed, and set to either GAS or ELECTRIC for your system to work properly. This setting changes how your system’s blower fan (if applicable) is controlled while the thermostat is in HEAT mode when the Fan switch in the AUTO position. This setting does not affect the fan operation while in COOL mode. When set to “GAS”, the blower fan is controlled solely by the heating system itself. Systems that would typically use the “GAS” setting would be: natural gas, propane, oil furnaces, and boilers. When set to “ELEC”, the blower fan is controlled directly by the thermostat. This setting is required for heating systems that do not control their own fan, such as HEAT PUMPS, and units that only have an electric-resistive heating element as the heat source.
NOTE: If your blower fan does not operate properly after installation, move the Gas / Electric option to the setting.
B/O CIRCUIT BOARD OPTION (FOR HEAT PUMP APPLICATIONS)
This setting is a plastic shorting cap (called a jumper) which determines the operation of the shared B/O wire terminal connection. This jumper must remain installed for a Heat Pump system to be able to provide heating and cooling as needed, and the majority of heat pumps today use the default “O” setting. The symptoms that will occur if this setting is not correct will be: heating while in cool mode, and cooling while in heat mode. When this is set to “O” (factory default), the shared B/O terminal will be turned on while in COOL mode, and off in HEAT mode. When this is set to “B” (which is needed for some Rheem, Ruud, and Bard heat pumps), the shared B/O terminal will be turned on in HEAT mode, and off in the COOL mode
HEAT / OFF / COOL, SYSTEM MODE SWITCH: Set this switch to HEAT to control your heating system, and COOL to control your cooling system. The OFF position will disable both the heating and cooling units.
AUTO / ON, FAN MODE SWITCH: When this switch is in AUTO, the blower fan (if present in your system) will automatically cycle on and off by itself while heating or cooling is running. When in the ON position, the blower fan will run constantly with or without a demand for heating or cooling, even when the System Mode switch is in the OFF position.
NOTE: The Fan Mode switch only works if your system provides a wire for the thermostat’s “G” wire terminal, to control a blower fan. The Fan Mode switch has no effect in systems that do not have a blower fan (such as a hot water radiator system).
SET BUTTON: This button is used to access the setup options menu and other additional features.
UP / DOWN BUTTONS: The UP and DOWN buttons are used to control the set temperature, or adjust any other on-screen items. Typically, an item that is flashing can currently be adjusted.
Setup options for how the thermostat will function, along with choosing your particular system type, are performed using a menu on the display screen. TO ACCESS THE SETUP MENU: Move the System Mode switch into the OFF position, and then hold down the SET button for approximately 5 seconds until
the screen changes. The menu will always start with item #01 and is advanced to each following item by a single press of the SET button. The options for each
item are changed using the UP or DOWN buttons.
ITEM #01 (TEMPERATURE SCALE)
ITEM #02 (NOT USED)
ITEM #03 (NOT USED)
ITEM #04 (MAXIMUM HEAT SET TEMP LIMIT)
ITEM #05 (MINIMUM COOL SET TEMP LIMIT)
ITEM #06 (SYSTEM / EQUIPMENT TYPE)
ITEM #07 (DELAY TIME)
ITEM #08 (TEMPERATURE SWING)
ITEM #09 (TEMPERATURE CALIBRATION)
[0 (zero)] (default) At zero, there are no changes made to the base room temperature measurement. The adjustment is from as low as subtracting -5F (-3C) degrees from the room temperature, to as high as adding +5F (+3C) degrees to the room temperature. The internal temperature sensor is accurately calibrated at the factory, and in most cases, this setting should not need to be altered.
HEATING AND COOLING: Basic operation of your heating or cooling system can be obtained by choosing either HEAT or COOL with the System Mode switch. The temperature can be adjusted using the UP and DOWN buttons.
LCD DISPLAY BACKLIGHT: The display screen is lighted to assist viewing at nighttime, or in locations with low light levels. A press of any button on the front panel will light the display for approximately 10 seconds. Any button presses that occur while the light is on will reset the 10-second timer, causing the screen to remain illuminated for an additional 10 seconds.
STATIC NOTICE: This thermostat is protected against normal static electric discharges, however, to minimize the risk of damaging the unit in extremely dry
weather, please touch a grounded metal object before touching your thermostat.
ADVANCED FEATURES KEYPAD LOCKOUT
You can lock the front panel buttons to prevent unauthorized tampering of your thermostat settings.
TO LOCK THE KEYPAD: Start with the thermostat at rest, and the display backlight
NOT illuminated. Press the SET button one time to illuminate the display screen, then press and hold the SET button for at least five seconds until a padlock icon appears in the display screen.
TO UNLOCK THE KEYPAD: Start with the thermostat at rest, and the display backlight NOT illuminated. Press the SET button one time to illuminate the
display screen, then press and hold the SET button for at least five seconds until the padlock icon disappears from the display screen.
SOFTWARE RESET: A Software Reset is used to erase ALL heating and cooling temperature programs, and to return all user-adjustable software settings back to their original factory default values. To perform a Software Reset, first ensure that the thermostat’s Keypad Lockout is not enabled and then move the System Mode switch to the OFF position. Start with the thermostat at rest, and the display backlight NOT illuminated. Press the SET button one time to illuminate the display screen, then press and hold the SET button for at least five seconds until the backlight goes out and the display screen becomes fully populated with all segments visible.
COMPRESSOR PROTECTION BYPASS: This optional feature permits the installer or service technician to temporarily disable the built-in compressor protection delays. This is most useful for diagnosing and testing the heating and cooling systems after installation is complete, and should not be used during normal operation. To activate this feature, first ensure that the thermostat’s Keypad Lockout is not enabled and then move the System Mode switch to the OFF
position. Start with the thermostat at rest, and the display backlight NOT illuminated. Press any button one time to illuminate the display screen, then press and hold both the UP and DOWN buttons together at the same time for at least five seconds.
NOTE: there will be no visual confirmation on the display screen when this feature becomes activated, however, you should be able to turn the cooling system on and off without any protection delays being imposed. All compressor protection delays (in all modes of operation) will be disabled for 5 minutes. After the 5-minute duration has expired, the thermostat will return to normal operation automatically
BATTERY REPLACEMENT
This thermostat is powered by two “AA” Alkaline batteries. The batteries should be replaced AT LEAST once per year to ensure reliable operation (or sooner if the battery icon or “LO BATT” appears in the display screen). The batteries are located on the back of the thermostat’s circuit board. The front portion of the
thermostat can be removed from the back half by using the housing release tabs on the bottom edge of the thermostat housing. When installing new batteries, we recommend using only brand new Energizer® or DURACELL®, “AA” size alkaline batteries. Please observe the polarity markings shown in the battery compartment to ensure proper installation. When finished, line up the front of the thermostat to the base, and firmly press together to securely latch the front and back halves together properly.
If you have any problems installing or using this thermostat, please carefully and thoroughly review the instruction manual. If you require assistance, please contact our Technical Assistance department at 856-234-8803 during regular business hours between 8:00 AM and 4:30 PM Eastern Standard Time, Monday through Friday. You can also receive technical assistance online anytime day or night at www.luxproproducts.com. Our website offers you troubleshooting guides and answers to the most common technical questions, and also permits you to email your questions to our technical support staff at your convenience.
If this unit fails because of defects in materials or workmanship within three years of the date of original purchase, LUX will, at its option, repair or replace it. This warranty does not cover damage by accident, misuse, or failure to follow installation instructions. Implied warranties are limited in duration to three years from the date of the original purchase. Some states do not allow limitations on how long an implied warranty lasts, so the above limitation may not apply to you. Please return malfunctioning or defective units to the location from which the purchase was made, along with proof of purchase. Please refer to “TECHNICAL ASSISTANCE” before returning the thermostat. Purchaser assumes all risks and liability for incidental and consequential damage resulting from the installation and use of this unit. Some states do not allow the exclusion of incidental or consequential damages, so the above exclusion may not apply to you. This warranty gives you specific legal rights and you may also have other rights, which vary from state to state. Applicable in the U.S.A. and Canada only.
MERCURY WARNING AND RECYCLING NOTICE
Mercury is a hazardous substance. Many states have laws requiring the proper disposal of mercury thermostats. If your new thermostat is replacing an older thermostat that might contain mercury, please visit www.thermostat-recycle.org to learn how and where to dispose of your old thermostat. On the website, you can enter your ZIP code to locate the nearest local drop-off point to recycle your old thermostat. If you are not sure whether your old thermostat contains mercury, the website also provides information and guidelines to help you determine whether it does. If you are unable to access the website, you may call the Thermostat Recycling Corporation at 1-888-266-0550 for guidance regarding the proper handling and disposal of your old mercury thermostat.www.luxproproducts.com 856-234-8803
Download Manual
LUXPRO P111 NON-PROGRAMMABLE THERMOSTAT Installation Manual
Other manuals
LUXPRO P111 NON-PROGRAMMABLE THERMOSTAT Product Specifications
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…