Quantity | Description |
1 | iComfort® E30 smart thermostat which includes a Smart Hub and HD Display |
6 | Mounting screws (#6 X 1.25” pan head) – Display requires 4 and smart hub 2. |
6 | Wall anchors (alligator flanged solid wall anchors) |
1 | Installation and setup guide |
1 | User guide |
1 | Checklist |
1 | Warranty certificate |
IMPORTANT The iComfort E30 smart thermostat CAN NOT be connected as a communicating device to indoor or outdoor units. Only conventional 24VAC wiring to indoor and outdoor units is supported.
NOTE: Due to Lennox’ ongoing commitment to quality, features and options are subject to change without notice and without incurring liability.
Operating and Storage Environment, Electrical and Dimensions
Smart Hub External Components, Button, LEDs, Jumpers, Terminals and Wiring Specifications
Push Button Function
The smart hub push button switch has two primarily functions.
The push button has a LED associated with it that indicates the status of the smart hub commissioning state (see “Table 1. System and Commissioning LED Indicators” on page 4).
LED Indicators
When alarms are present, you may review alarm(s) listed either on the homeowner notification screen or the menu / settings > advanced settings > dealer control center > notifications screen.
Alert codes which require manual clearing can only be done under the dealer control center > notification screen.
Table 1. System and Commissioning LED Indicators
LED Color | Status | Description | |
If multiple errors are present, the system status LED will display each active condition for one second on and one second off. The system will continue to cycle through all active conditions. System status errors are displayed in the following priority: HVAC alerts, thermostats and then Wi-Fi. |
Table 2. Communication Error Troubleshooting (HD Display to Smart Hub)
Possible Connection Issues | E30 Smart Hub – System Status LED |
One communication wire at either the HD Display or smart hub A or B termi- nals is disconnected. | Flashing Magenta LED |
Both communication wires – at either the HD Display or smart hub A or B terminals are disconnected. | Flashing Magenta LED |
Power wires at either the smart hub or HD Display 12V+ and 12V- terminals are disconnected. | Flashing Magenta LED. |
If terminals are connected correctly, then check HD Display. HD Display not be secured correctly to subbase. | Flashing Magenta LED. HD Display screen may be either blank or a message indicating iComfort cannot communicate with the equipment. |
Unit Type Jumpers
Set the unit type jumper for the type of indoor unit being used (see “Figure 1. Smart Hub External Components” on page 3 and “Table 3. Unit Type Jumpers Positions”). The factory default setting is IFC. If jumper is missing from header, alarm 130 is activated.
Table 3. Unit Type Jumpers Positions
Jumper Position | Indoor Unit | Outdoor Unit |
HP | DO NOT USE | |
IFC | Conventional furnace, hydronic baseboard heating and hot water coils | Conventional heat pump or air conditioner |
AHC | Conventional Air Handler |
Heat Stage Jumper Positions
The heat staging Jumper must be set for the number of stages of electric heat (air handler) or the number of stage of gas heat (furnace) and stages of heat pump. Using the heat stages jumper (see figure 3 and table 8). The factory default setting is position 2. If jumper is missing from header, alarm 130 is activated.
Figure 3. Heat Stage Jumper Positions
Table 4. Heat Stage Jumpers
Label (Position) | Air Handler Heat Stages | Furnace Heat Stages | Heat Pump Stages | |||
Number of Electric Heat Stages | Stage Per- centage | Number of Gas Stages | Stage Per- centage | Number of Compressors Stages | Stage Per- centage | |
0 | No Elec- tric Heat | 0 | 1 | 100% | 1 | 100% |
1 | 1 | 100% | 1 | 100% | 1 | 100% |
2 (default) | 2 | 50%, 100% | 2 | 70%, 100% | 2 | 70%, 100% |
3 | 3 | 33.5%, 66.5%, 100% | 2 | 70%, 100% | 2 | 70%, 100% |
If jumper is missing, setting defaults to single-stage. Changing jumper position after power-up requires recommission for the change to be recognized. |
IMPORTANT If any jumpers were set incorrectly AFTER commissioning was completed, then reposition jumpers to correct configuration. Re-running the commissioning procedure will be required at the thermostat or with the mobile app.
The following is the wiring specification requirements for installation of this system.
Table 5. Terminal Designations and Wiring Recommendations
Terminal Designation | Description | Thermostat Wiring |
ACC1 | Accessory 1 and 2 (typically can be used for 1 or 2 speed ventilators and fresh air damper) |
18AWG unshielded |
ACC2 | ||
+ | 12VDC output | 18AWG unshielded |
– | 12VDC return | |
A | Communications bus A |
18 – 22AWG shielded (recommended) |
IMPORTANT Use 1-pair, 18AWG unshielded thermostat cable (field-provided) for power terminals (R, C, 12+ AND 12-). Highly recommend using 1-pair 22AWG shielded thermostat cable for communications terminals ( A and B) which will help eliminate any noise interference.
Table 6. Conventional Terminals (24VAC)
Label | Description | Function |
W1 | First-stage heat output (first-stage gas heat output when configured as furnace (IFC) and first-stage electric heat output when configured as air handler (AHC). | |
W2 | Second-stage heat output (second-stage gas heat output when configured as IFC and second-stage electric heat output when configured as AHC. | |
W3 | Third-stage heat output (third-stage electric heat output when configured as air handler) | |
G | Indoor blower control (continuous fan) (monitoring only). G input may be connected to IAQ devices such as humidifier, Lennox Ventilation Control System and Heat or Energy Recovery Ventilators to turn the indoor blower on and off. |
Table 6. Conventional Terminals (24VAC)
Label | Description | Function |
Y2 | Second-stage compressor output. | |
Y1 | First-stage compressor output. | |
DS | 24VAC dehumidification signal output. The DS terminal is powered when there is not a dehumidification call. | |
C | Class II, 24VAC transformer common | Both R and C terminals are used to receive power from the indoor unit and capable of providing the power to the Smart hub and all the associated loads. The R power input uses a 3A fuse (Lennox part number 25J49. |
R | Class II. 24VAC transformer power | |
H | 24VAC humidifier signal output. | |
O | Heat pump reversing valve (24VAC = cool) | Used as reversing valve output for heat pumps. The E30 uses a single-pole dual throw relay to generate O and B signals. Normally the O output is open and B output at 24VAC during heating calls. During cooling calls O is 24VAC and B open. With relay de-energized 24VAC is present on O terminal. When power off/ or control reset, 24VAC power shall not be present on the O terminal. |
B | Heat pump reversing valve (24 VAC = heat) |
The following diagrams in this section illustrates the basic Lennox control wiring for all compatible components.
Discharge Air Temperature Sensor (DATS)
Installation of discharge air temperature sensor (DATS) (88K38) must comply with the following requirements:
Outdoor Air Temperature Sensor (OATS)
The optional outdoor air (temperature) sensor (OATS) (X2658) wiring distance to the iComfort E30 should not exceed 150 feet (45 meters) when wired with minimum 22 #AWG (recommend 18 #AWG) dedicated 2-conductor thermostat cable. Installation of OATS must comply with the following requirements:
HD Display External Components
Reducing Electrical Noise
WARNING Improper installation, adjustment, alteration, ser vice or maintenance can cause property damage, personal injury or loss of life.
Installation and service must be performed by a li censed professional HVAC installer (or equivalent) or a service agency. Before beginning installation, note the type of equipment, number of stages, and any accessories being installed.
Do
Do Not
Smart Hub Installation
IMPORTANT Do not install smart hub in location where direct exposure to condensation or dripping water is possible.
DO NOT install smart hub on indoor unit.
Things to consider when installing the smart hub:
IMPORTANT Do not install smart hub in location were direct exposure to condensation or dripping water is possible.
Installation
Use the following procedure for installation of the HD Display where existing thermostat wiring does not exist:
Mounting Display to Subbase
Commissioning or Service (Using the Mobile Setup Application)
This application tool is used by dealers to commission a iComfort E30 smart thermostat using a Wi-Fi enabled mobile device.
A temporary smart hub local network provides a means for a mobile device using the iComfort Mobile Setup application to directly communicate with the smart hub.
NOTE: The iComfort Mobile Setup application running on a mobile cannot connect to the smart hub through the Internet or home Wi-Fi network.
To use the iComfort Mobile Setup app, the mobile device must be:
Mobile Device Operating System Requirements
The iComfort Mobile Setup application is available for both IOS 6.0 and higher (App Store) and Android 4.1 and higher (Google Play).
Establishing a Direct Wireless Connection to the Smart Hub
IMPORTANT If the connection between the iComfort Mobile Setup application and smart hub is idle for three (3) minutes, the smart hub will auto-disconnect from the mobile device. Repeat procedures to reconnect.
Service
To use iComfort Mobile Setup application as a service tool, the commissioning of the system must have already been completed.
Alternative Method
From the home screen, go to menu > settings > advanced settings > pair smart hub to iComfort dealer mobile application selection. It will auto connect to dealer application and start you at the dealer control center screen. The following screen will appear and show the status of the connection. Once connected the screen will automatically disappear.
Multiple Smart Hub(s) – Group ID
Multiple smart hubs in a home can be assigned to a group (up to nine groups with up to five (5) smart hubs in each group). All smart hubs in a group can communicate with other smart hubs in the same group over the home Wi-Fi network.
Default Group ID 1. Range is 1 to 9.
NOTE: If a smart hub is set to Group 0, then there is no connectivity with another smart hub.
Group IDs can be changed by going to menu > settings > advanced settings view > dealer control center > equipment > smart hub.
Restarting Smart Hub
Pressing the smart hub button for more than five seconds will reboot the smart hub.
The following procedures are written for commissioning the system using the HD display interface.
When power is applied the system will use the smart hub configured equipment settings and factory defaults. All non-communicating equipment must be added in the “add non-communication equipment” screen.
Boot-up Screen
When power is applied to the system, the HD Display will display a welcome screen.
If there is an issue with communication between any component attached to the thermostat, a critical alert message will appear on the screen. The alert message will provide detail information concerning the possible cause. Once the issue is corrected and power is restored to the system the first screen in the initial setup sequence will appear.
IMPORTANT Sometimes there is a communication delay between the HD Display and smart hub during initial boot-up which will result in the reference message being display. Please wait up to one minute to see if the communication delay is resolved.
Below is an example of a communication error message.
Apple HomeKit Wi-Fi Accessory Configuration
A pop-up screen will appears providing instructions on how to connect the thermostat to the home Wi-Fi network using an Apple IOS device. If you wish to use this method to configure the unit for Wi-Fi and Apple HomeKit, then refer to the provided user guide for additional instructions.
Otherwise, select cancel to proceed with the thermostat commissioning procedures. There is an option to perform this task later on at the homeowners convenience.
NOTE: This procedure can only be accomplished using the Apple mobile IOS device.
IMPORTANT
The thermostat is only accessible via the Dealer Dashboard after the dealership’s main phone number or company name is added during thermostat commissioning. See “LennoxPros Dealer Dashboard” on page 43 for further details. This screen in the commissioning sequence is the dealer information screen where the dealer ID and/or phone number can be added. Once the system is connected to the Internet, the remaining information will be populated automatically by the Lennox server based on the dealer name or phone number entered. All information can be entered manually if desired however.
Information that can be manually entered is name, email website, dealer address which includes address 1, address 2, city, state and zip/postal code. Once completed touch continue.
Dealer Info Notification Pop-Up Screen
If either the Dealer ID or phone number is NOT provided, a notification screen will appear. The notification screen will provide information on the limitation imposed on the system if this information is not provided. Touch no to return to the previous screen to complete the information requested or touch yes to continue.
General Information
On this screen general information needs to be verified or changed. Touch any item to change its contents. A pop-up screen will appear that will allow the information to be added or changed.
Information required:
Equipment Found Screen
This screen will display the smart hub equipment settings. Here is where 24VAC equipment will need to be added (air conditioner, heat pump, humidifiers, dehumidifiers and ventilation equipment), by selecting the add non-communicating equipment.
Depending on whether the smart hub is configured for air handler or furnace operations, the name of each option will appear as either EIM-Furnace or EIM-Air Handler.
Non-Communicating Equipment
When selecting the non-communicating (24VAC) equipment icon a screen will appear listing equipment that can be added. When selecting an applicable component, a green check will appear next to the item.
NOTE: A temporary dialog box will appear indicating: Updating – Wait while we check for dependencies.
NOTE: This is where an outdoor unit type only is selected. Selections are one or two-stage heat pumps or air conditioners. Outdoor unit capacity will also have to be set. Other equipment that can be added are humidifiers and dehumidifiers. Other non-communicating equipment that can be added are:
NOTE: Once completed touch done which will display the equipment found screen. There the additional non-communicating equipment will now be displayed along with the iComfort equipment.
Once completed touch continue.
Reminders
This screen allows you to set reminders as either disabled or 3, 6, 12 or 24 months and also custom by specific date. The other options on this screen is to trigger the reminder event either by calendar or actual system run-time.
Reminders may be set for Replace filter 1, Replace filter 2, Replace UV bulb, Replace humidifier pad, Ventilation maintenance and Ventilation filter.
Once a reminder is set for a specific item, touch done to return to the previous screen. An “expires on date” will appear next to the item just set.
Commissioning Completion
Once commissioning is completed, the system will leave you at the Dealer Control Center. You can either touch exit to go to the main screen or perform any function listed in the various categories displayed.
This menu provides access to the dealer for performing various functions as listed below:
Selections listed in this section are dependent on system hardware configuration. Not all options will be available.
NOTE: When changing the default settings for any parameter, there is a possibility that it will affect the settings for another parameter. If this happens, a pop-up message will be displayed listing the other affected parameters and their new automatically set values.
The following is a complete list of all possible parameters under System. Parameters actually available are dependent on the smart hub settings.
Table 7. Smart Hub Parameters
Parameter (In alphabetical order) | Description |
About | This screen provides information concerning language supported, equipment type name, control software revision, model, control mode number, control serial number, control hardware revision, protocol revision number, device product level, 24VAC average power consumption, 24VAC peak power consumption, compatible devices list, application code memory size and micro-controller part number. |
Auto Changeover – Humidif. Deadband | Prevents the Humidification and Dehumidification settings from being closer together than 5% or greater than 10% (Dead-band). Range is 5 to 10%. Default is 5%. Adjustments are in increments of 1%. |
Auto Changeover – Temp Deadband | Prevents the Heating and Cooling from being set closer together than 3ºF (1.67°C) or greater than 9ºF (5.0°C) (Dead- band). Range is 3 to 9°F (1.67 to 5.0°C). Default is 3°F (1.67°C). Adjustments are in increments of 1°F (0.56°C). |
Auto Dehumidification Overcooling Threshold | Range is 0 – 10%. Default is 4%. Adjustments are in increments of 1%. This value can automatically be affected by adjusting other parameters. One example would be when enabling Max Dehumidification Overcooling. |
Balance Point Control If system is set up as dual fuel or heat pump with electric heat and a outdoor temperature sensor connected to smart hub, the low and high balance point settings will appear. The balance points feature requires that a sensed outdoor temperature is provided to the thermostat. The outdoor ambient temperature can be read from a field-installed outdoor temperature sensor (X2658). When balance point control is ENABLED, the low and high balance point fields will be turned “ON” and show RED. A message will be displayed asking you to review the low and high balance point settings and save all RED settings. Highlighted fields in RED must be saved to allow exit from that screen. Options are enabled or disabled. Default is disabled. When enabled, both low and high balance points can be set. High Balance Point This setting is used to prevent the furnace or electric heat from heating the structure. (Alert 19 – Minor – Notification only – The outdoor temperature is higher than the level where the furnace or electric heat is programmed to heat the home.) Range is -17 to 75°F (-27.22 to 23.89°C). Default is 50°F (10.0°C). Adjustments are in increments of 1°F (0.56°C). Low Balance Point Setting used to prevent the heat pump from heating the structure. (Alert 18 – Minor – Notification only – The outdoor temperature is below the level where the heat pump is programmed to heat the home). Range is -20 to 72°F (-28.89 to 22.22°C). Default is 25°F (-3.89°C). Adjustments are in increments of 1°F (0.56°C). | |
Cooling Mode | Options are Normal and Comfort. Default is Normal. When changing to Comfort Mode, several parameters are automatically modified for optimal system operations. The changed parameters are listed on the screen when set to Comfort. Normal – This setting cools the home to the desired temperature setting. Once second-stage is activated by timer or differential, it will not stage down to first-stage until the next cooling cycle demand. Comfort – This is when the system could automatically stage up or down based on the current load demand. |
Cooling Discomfort Threshold | Default is ON. The purpose of this algorithm when set to ON is to detect systems with faults which are causing measurable loss of comfort and thus, need repair/service intervention. The algorithm monitors the duration in which the indoor temperature is above the cool set point or below the heat set point and does not approach the set-point. When an issue is detected alarm 901 is activated. |
Parameter (In alphabetical order) | Description |
Electric Heat Stages During Defrost | Can increase or decrease the number of electric elements to come on during a call for defrost. Thermostat will have a demand for heat.) Range is 0 to 5 electric heat stages. Default is 2. Adjustments are in increments of 1. |
Equipment Name | A unique name can be assigned to this component. Name can be up to 29 characters. Name can consist of letters, numbers, special characters and spaces. Default name is Subnet Controller. |
Group ID | Default Group ID is 1. Valid range is 0 to 9. Multiple smart hubs in a home can be assigned to a group (up to nine groups with up to eight smart hubs in each group). All smart hubs in a group can communicate with other smart hubs in the same group over the home Wi-Fi network. If a smart hub is set to Group ID 0, there is no connectivity with another smart hub. |
Heat Cool Stages Locked In Heat Cool (H/C) Stages Lock in default is disabled (heat/cool stages are turned off separately). If changed to Enabled, heat/cool stages are turned off together. For non-variable speed systems only. |
Parameter (In alphabetical order) | Description |
Humiditrol Comfort Adjust | Options are Maximum Overcooling, Midpoint Overcooling and Minimum Overcooling. Default is Maximum Overcooling. Maximum Overcooling: Indoor temperature > (greater than) two degrees above heating setpoint. Midpoint Overcooling: Indoor temperature > (greater than) HEAT setpoint + COOL setpoint / 2. Minimum Overcooling: Indoor temperature > (greater than) two degrees below cooling setpoint. XP20 and XP25 is not compatible with Humiditrol (EDA). |
Humidity Reading Calibration | Range is -10.0 to 10.0%. Default is 0.0%. If it is determine that the actual humidity percentage being detected at the thermostat is off based on independent readings using other humidity reading devices, the display can be adjusted using this setting. |
Lock In 2nd Stage HP by Outdoor Temp (Lennox Two-Stage Heat Pumps Only) | This accessory allows the unit to lock in 2nd stage HP heating when the outdoor temperature goes below the jumper pin setting. Options are off, 40°F, 45°F, 50°F and 55°F (4°C, 7°C, 10°C and 13°C). Default is off. |
Max Heat Setpoint | The highest temperature setting that the heat set point can be set on the thermostat. Default is 90.0F (32.33°C). Range is 60.0 to 90.0°F (15.56 to 32.22°C). Adjustable in increments of 1°F (0.56°C). |
Max Humidification Setpoint | Maximum allowed set point for humidification. Range is 15 to 45%. Default is 45%. Adjustments are in increments of 1%. |
Min Cool Setpoint | The lowest temperature setting that the cool set point can be set on the thermostat. Range is Range is 60.0 to 90.0°F (15.56 to 32.22°C). Default is 60°F (15.56°C). Adjustments are in increments of 1°F (0.56°C). |
Min Dehumidification Setpoint | Adjustable minimum dehumidification setting. Range is 40 to 60%. Default is 40%. Adjustments are in increments of 1%. |
Outdoor Temperature Reading Calibration | Range is -10 to 10°F (-5.56 to 5.56°C). Default is 0°F (0.0°C). Adjustments are in increments of 1°F. (0.56°C) This will allow for adjustment to the outdoor temperature display when the display temperature is off. Outdoor sensor is required. |
Reset smart hub | Reset smart hub (erases smart hub settings and restarts installer setup). |
Severe Weather Protection Options are enabled or disabled. Default is disabled. When enabled either the heat or freezing alert temperature setting will automatically generate a email notification to the homeowner that the applicable condition exist and homeowner interaction is required. Notification is dependent on the thermostat having a active Wi-Fi connection and the user account has been setup and includes a valid email address. Heat Alert Temperature This will notified the homeowner when the indoor temperature reaches the setting defined for this parameter. Range is 80°F to 100°F (26.67 to 37.78°C) with a factory default of 90°F (32.22°C). Increments adjusted by 1.0°F (0.56°C). Freezing Alert Temperature This will notified the homeowner when the indoor temperature reaches the setting defined for this parameter. Range is 30°F to 50°F (-1.11 to 10.0°C) with a factory default of 40°F 4.4°C). Increments adjusted by 1.0°F (0.56°C). |
Parameter (In alphabetical order) | Description |
Single Setpoint Mode (SSP) On the user screens this is referred to as Perfect Temp (Temperature). Options are enabled or disabled. Default is disabled. The Single Set Point (SSP) algorithm allows the user the set only one temperature set point value rather than one value for heating and a different value for cooling. When zoning is present, the following SSP settings are not available. When enabled the following parameters are automatically configured for optimal settings. SSP Heating Cancel Coast Counter Increment Slope Range is 0 to 0.75°F (0.0 to 0.42°C). Default is 0.25°F (-0.14°C). Adjustments are in increments of 0.125°F (0.07°C). SSP Heating Cancel Coast Counter Decrement Slope Range is 0.25 to 2°F (0.14 to 1.11°C). Default is 0.5°F (0.28°C). Adjustments are in increments of 0.125°F (0.07°C). SSP Cooling Cancel Coast Counter Increment Slope Range is -0.75 to 0.0°F (-0.42 to 0.0°C). Default is -0.25°F (-0.14°C). Adjustments are in increments of 0.125°F (0.07°C). SSP Cooling Cancel Coast Counter Decrement Slope Range is -2.0 to -0.25°F (-1.11 to -0.14°C). Default is -0.5°F (-0.28°C). Adjustments are in increments of 0.125°F (0.07°C). SSP Heating Lockout Outdoor Temp When the outdoor temperature is above this setting, heating is not allowed if single set point is running. Range is 50 to 80°F (10.0 to 26.67°C). Default is 70°F (21.11°C). Adjustments are in increments of 1.0°F (0.56°C). SSP Cooling Lockout Outdoor Temp When the outdoor temperature is below this setting, cooling is not allowed if single set point is running. Range is 30 to 60°F (-1.11 to 15.56°C). Default is 40°F (4.44°C). Adjustments are in increments of 1.0°F. | |
Smart Alert Enable | Options are disabled, conservative, medium and aggressive. Default is disabled. Disable – There is no monitoring of Smart Alert Enable. Conservative – The system will wait longer to display any Smart Alert Enable alarms. This options allow for a minimum chance for false alarms being shown. Medium (default) – Extensive testing by the Lennox development team to minimize the number of false alarms. Aggressive – Will shorten time to display any Smart Alert Enable alarms. Smart Alert Enable function monitors: • Thermostat set point setting • Temperature reading • Determine whether the system moving towards the desired temperature setting or is unable to achieve the desire temperature setting. • Uses local climate design temperatures • System run times. • Depending on type of system (conventional heating/cooling or heat pump system) and optional equipment not all system settings will be displayed. |
Parameter (In alphabetical order) | Description |
Smooth Setback Recovery (SSR) | When enabled, smooth set back begins recovery up to two hours before the programmed time so that the programmed temperature is reached at the corresponding programmed event time. Assume 12°F (6.6°C) per hour for first-stage gas/electric heating and 6°F (3.3°C) per hour for first-stage compressor based heating or cooling. With Smooth Set Back disabled, the system will start a recovery at the programmed time. Options are enabled or disabled. Default is enabled. The SSR set point calculation is as follows: |
Rules for SSR: • SSR is enabled when both “Smooth Setback Recovery” is set to enabled (default) and the program schedule is turned on. • SSR does NOT turn off stage delay timers. • SSR will NOT change the dead band between heating and cooling modes. • SSR will not overshoot the target set point. • SSR will reset if the user updates the program schedule during the active SSR period | |
Stage Delay Timers (First) | Enabled (default) setting: When enabled all stage delay timers (stages 2 through 6) are enabled and will serve to bring on additional stage(s) of cooling or heating on a timed basis (default 20 minutes) Disabled setting: All stages delay timers are disabled. Heat/cool stages are changed based on temperature The second-stage delay timer (when stage timers is Enabled) is used for both HEATING and COOLING. |
Stage Delay Timers (2 through 6) | Second through Sixth Stage Delay timer (where applicable) – If staged delay timers are “Enabled”, the default is 20 minutes but can be programmed from 5 to 120 minutes in 5-minute increments. If the first stage fails to advance the ambient temperature toward the set point by 1.0°F (0.56°C) in the programmed delay time, then the second stage is activated. |
Stage Differentials (1 through 6) | Number of stages in thermostat is dependent on equipment that is installed. |
Temp Reading Calibration | Range is -5.0 to 5.0°F (-2.78 to -2.78°C). Default is 0.0°F (-0.0°C). If it is determine that the actual temperature being detected at the thermostat is off based on independent readings using other ambient temperature reading devices, the display can be adjusted using this setting. |
Temperature Control Mode | Options are Normal and Comfort. Default is Normal. The Feels-Like feature factors in the outdoor temperature and indoor humidity for a more accurate control of the temperature in the home. Either an outdoor temperature sensor is used or Internet Weather is enabled for this feature to operate. Modifying this setting here will also change the feature status on the user settings screen. Normal – This setting cools or heats the home to the desired temperature setting (feels-like) is OFF. Comfort – This setting cools or heats the home to the desired temperature setting (Feels Like) is ON. When set to ON, other parameters are modified to optimal settings for this feature. Those setting changes will be listed on-screen when Comfort is enabled. |
Parameter (In alphabetical order) | Description |
Ventilation Control Mode – timed (default) | |
Ventilation Minutes Per Hour | Parameter range is 0.0 – 60.0 minutes. Default is 20.0 minutes. Can be adjusted in increments of 1.0 minutes. • The system first tries to satisfy the ventilation time by only ventilating while conditioning is occurring. Continuous fan is not considered conditioning. • When the required time remaining to ventilate for the hour does not equals the amount of time remaining in that hour, the system begins ventilation and does not stop until the ventilation time requirement is satisfied. • When ventilating without a conditioning demand, the ventilation output is active as well as a continuous indoor fan demand. • When ventilating with a conditioning demand, the ventilation output is active with the conditioning demand outputs. |
Ventilation Rates Thermostat ventilation CFM parameters are to be adjusted only after the HRV/ERV set up is completed and the CFMs are known. Once the thermostat’s CFMs are adjusted they are used with the thermostat’s timer algorithm to determine how long to run the HRV/ERV and to change from low to high speed if a 2-stage HRV/ERVs. | |
Ventilation Rate (Only listed for 1-speed ERV or HRV | Parameter range is 20 – 500 CFM. Default is 130 CFM. Can be adjusted in increments of 1.0 CFM. |
Ventilation Rate for Low Speed (Only listed for 2-speed ERV or HRV | Parameter range is 10 – 200 CFM. Default is 50 CFM. Can be adjusted in increments of 1.0 CFM. |
Ventilation Rate for High Speed (Only listed for 2-speed ERV or HRV | Parameter range is 20 – 500 CFM. Default is 130 CFM. Can be adjusted in increments of 1.0 CFM. |
Ventilation High Outdoor Temperature Limit | Parameter range is 60 to 115ºF. Default is 100ºF. Can be adjusted in increments of 5ºF. While the outdoor temperature is equal to or higher than the setting for Ventilation High Outdoor Temperature Limit, ventilation does not run. When locked out due to high outdoor temperature, it will become unlocked when either the outdoor temperature is missing, or when the temperature reported is 1°F less than the Ventilation High Outdoor Temperature Limit setting when display units are in Fahrenheit, or is reported as 0.5°C less than lock out setting when the display units are Celsius. |
Ventilation Low Outdoor Temperature Limit | Parameter range is -20 to 55ºF. Default is 0ºF. Can be adjusted in increments of 5ºF. While the outdoor temperature is lower than the setting for the Ventilation Low Outdoor Temperature Limit, ventilation does not run. When locked out due to low outdoor temperature, it will become unlocked when the outdoor temperature is missing, or when the temperature reported is 1°F higher than the Ventilation Low Outdoor Temperature Limit setting when display units are Fahrenheit, or is reported as 0.5°C higher than lock out setting when the display units are Celsius |
Ventilation High Outdoor Dew Point Limit | Parameter range is 45 to 80ºF. Default is 55ºF. Can be adjusted in increments of 5ºF. While the outdoor dew point is higher than the setting for the high outdoor dew point limit, ventilation does not run. When locked out due to high outdoor dew point limit, it will become unlocked when the outdoor dew point is missing, or when the dew point temperature reported is 1°F less than the lock out setting when display units are Fahrenheit, or is reported as 0.5°C less than lock out setting when the display units are Celsius. |
Parameter (In alphabetical order) | Description |
Ventilation Control Mode – ASHRAE | |
• In this mode the thermostat can assist the installer by validating the ventilation CFMs are capable of meeting the ASHRAE required ventilation volumes, but the thermostat has no ability to control CFM from the HRV/ERV. • The system first tries to satisfy the ventilation volume by only ventilating while conditioning is occurring. Continuous fan is not considered conditioning. • The total volume of ventilation air is accumulated and stored to compare against the target hourly ventilation volume Vhr. The accumulated value resets each hour. • When the remaining required volume of ventilation air for the hour divided by the fan only ventilation rate is equal to or greater than the time remaining to ventilate for the hour and no conditioning is occurring, the system begins ventilation using continuous fan and does not stop until the target hourly ventilation volume requirement is satisfied. • When ventilating without a conditioning demand, the ventilation output is active as well a continuous indoor fan demand. • When ventilating with a conditioning demand, the ventilation output is active with the conditioning demand outputs. • When the system is ventilating, the user interface can indicate as such by showing “ventilating” to the user on the home screen. | |
Ventilation Rates Thermostat ventilation CFM parameters are to be adjusted only after the HRV/ERV set up is completed and the CFMs are known. Once the thermostat’s CFMs are adjusted they are used with the thermostat’s timer algorithm to determine how long to run the HRV/ERV and to change from low to high speed if a 2-stage HRV/ERVs. | |
Ventilation Rate (Only listed for 1-speed ERV or HRV | Parameter range is 20 – 500 CFM. Default is 130 CFM. Can be adjusted in increments of 1.0 CFM. |
Ventilation Rate for Low Speed (Only listed for 2-speed ERV or HRV | Parameter range is 10 – 200 CFM. Default is 50 CFM. Can be adjusted in increments of 1.0 CFM. |
Ventilation Rate for High Speed (Only listed for 2-speed ERV or HRV | Parameter range is 20 – 500 CFM. Default is 130 CFM. Can be adjusted in increments of 1.0 CFM. |
Ventilation Outdoor Condition Override | Options are Disabled (default) or Enabled. |
ASHRAE Compliance Check | = NO (Ventilation CFM too low to comply with ASHRAE 62.2) or YES (Current settings comply with ASHRAE 62.2) |
ASHRAE Infiltration Credit | Parameter range is 0.0 – 200.0 CFM. Default is 2500 square feet. Can be adjusted in increments of 1.0 CFM. |
ASHRAE House Floor Area Serviced by This Ventilator | Parameter range is 500.0 – 5000.0 square feet. Default is 2500.0 CFM. Can be adjusted in increments of 100.0 square feet. The formula for calculating how much ventilation is required is: (total square footage of the home/100) + ((number of bedrooms+1) x 7.5 cfm) |
ASHRAE Number of Bedrooms | Parameter range is 1.0 – 10.0. Default is 3.0. Can be adjusted in increments of 1.0. |
Ventilation High Outdoor Temperature Limit | Parameter range is 60 to 115ºF. Default is 100ºF. Can be adjusted in increments of 5ºF. While the outdoor temperature is equal to or higher than the setting for Ventilation High Outdoor Temperature Limit, ventilation does not run. When locked out due to high outdoor temperature, it will become unlocked when either the outdoor temperature is missing, or when the temperature reported is 1°F less than the Ventilation High Outdoor Temperature Limit setting when display units are in Fahrenheit, or is reported as 0.5°C less than lock out setting when the display units are Celsius. |
Parameter (In alphabetical order) | Description |
Ventilation Low Outdoor Temperature Limit | Parameter range is -20 to 55ºF. Default is 0ºF. Can be adjusted in increments of 5ºF. While the outdoor temperature is lower than the setting for the Ventilation Low Outdoor Temperature Limit, ventilation does not run. When locked out due to low outdoor temperature, it will become unlocked when the outdoor temperature is missing, or when the temperature reported is 1°F higher than the Ventilation Low Outdoor Temperature Limit setting when display units are Fahrenheit, or is reported as 0.5°C higher than lock out setting when the display units are Celsius |
Ventilation High Outdoor Dew Point Limit | Parameter range is 45 to 80ºF. Default is 55ºF. Can be adjusted in increments of 5ºF. While the outdoor dew point is higher than the setting for the high outdoor dew point limit, ventilation does not run. When locked out due to high outdoor dew point limit, it will become unlocked when the outdoor dew point is missing, or when the dew point temperature reported is 1°F less than the lock out setting when display units are Fahrenheit, or is reported as 0.5°C less than lock out setting when the display units are Celsius. |
Wall Insulation | Options are poor, average and good. Default is average. |
Table 8. Air Handler Parameters
Parameter | Description |
About | Provides information concerning unit code, language support, equipment type name, unit model number, unit serial number, unit nominal capacity, number of heating states, heating capacity by stage, indoor blower CFM range, control software revision, control model number, control serial number, control hardware revision, discharge air temp sensor, outdoor air temp sensor, protocol revision number, device product level, factory installed transformer, 24VAC average power consumption, 24VAC peak power consumption, line voltage average power consumption, line voltage peak power consumption, compatible devices list, applicable code memory size, and micro- controller part number.. |
Reset Air Handler | Any installer modifications under the air handler tab will be reset back to the factory defaults if the reset air handler option is used. |
Table 9. Furnace Parameters
Parameter | Description |
About | This screen provides information on unit code, language supported, equipment type name, unit model number, unit serial number, unit nominal capacity, number of heating stages, heating capacity by stage, indoor blower CFM range, control software revision, control model number, control serial number, control hardware revision, discharge air temp sensor, outdoor air temp sensor, protocol revision number, device product level, factory installed transformer, 24VAC average power consumption, 24VAC peak power consumption, line voltage average power consumption, line voltage peak power consumption, compatible devices list, application code memory size and micro-controller part number. |
Reset Furnace | Any installer modifications under the furnace tab will be reset back to the factory defaults if the reset furnace option is used. |
Table 10. Thermostat (HD Display) Parameters
Parameter | Description |
About | This screen provides information concerning model number, serial number, hardware revision, software revision, language support and equipment type name. |
Auto Brightness | Options are on and off. Default is off. |
Brightness Value | The brightness range is 0 – 100. Default 80. Touch either the + or – button to increase or decrease the setting. |
Display Air Quality | Options are on and off. Default is off. Air Quality is displayed under the weather display. Touch the Weather icon on the home page to see the current air quality. |
Display Indoor Humidity | Options are on and off. Default is off. |
Display Outdoor Weather | Options are on and off. Default is off. |
Parameter | Description |
Outdoor Temperature Source | Options are off, Internet (AccuWeather) or sensor. Default is Internet (AccuWeather). |
Proximity Control | Options are ON and OFF. Default is OFF. Is used to wake-up the display from screen saver mode when motion near the HD Display is detected. |
Reset thermostat | Resets the thermostat settings to factory default. |
Screen Locked | Options are unlocked, partially locked and locked. Default is unlocked. |
Screen Saver | Options are off, weather, power save and logo. Default is off. |
Wide Setpoint | Options are ON and OFF. Default is OFF. This allows a wider low and high temperature. Normal range is 60 to 90°F (15.5 to 32.0°C). When this parameter is set to ON, the range is 40 to 100°F (0.0 to 40°C). This feature can also be set through the user interface setting screen. From the home screen go to menu > settings > heat & cool > wider set-point range. |
Table 11. Utilities
Parameter | Description |
Restart smart hub | Restarts the smart hub. |
Re-configure System | Re-configure HVAC system. |
Reset HVAC Equipment | Resets all HVAC equipment. |
Factory Reset Thermostat | Resets thermostat to factory default settings. |
Factory Reset Smart Hub | Resets smart hub parameters back to factory default. |
Verify Airflow Per Zone is the first screen to appear under this selection. If no zoning is installed, zone airflow settings will be for zone 1 only. If zoning equipment is detected by the system then zones 1 through 4 will be listed. These screens allow for verification and modification of CFMs for blower, heating and cooling circulation. Touch continue to proceed to the next screen.
Select Test Mode is the next screen to appear. Your options are automated tests or manual tests. Select the desired option and select apply.
Automated Tests:
Select this options and the next screen will allow you to select the specific tests available for your hardware configuration. The test are automatic and no installer / service technician’s attendance is required. When the automatic testing is complete the system returns to the consumer home screen. A updated installation report is generated and available in Lennox Pros under the Homeowners account.
Manual Test:
Depending on hardware present, various tests are available. By default all items to be tested are enabled. Selecting a specific test will un-check the item. When a specific set of tests are completed the results will be displayed on the screen next to the tested item. Touch continue to proceed to the next set of test items. Once all tests are completed press done to return to the touch tests to run screen. Touch the left arrow at the top left side of screen to return to the Dealer Control Center
Diagnostics
This screen allows the installer to verify the current operational state of the air handler or furnace. Diagnostics results are for active various inputs, voltage, delays and relays.
Touch the left arrow at the top left side of screen to return to the Dealer Control Center.
Results of both manual and automatic tests will be displayed under this section.
The dealer information screen will appear. The next screen will be for dealer information. Here either the dealer ID or phone number can be added. Once the system is connected to the Internet, the remaining information is automatically populated. Not all information for this screen will be viewable. Touch and hold and then swipe up to access the remaining information on the screen.
Information Required: Dealer ID and / or dealer phone number. Information that can be manually entered is name, email website, dealer address which includes address 1, address 2, city state and zip/postal code. Once completed, touch the left arrow at the top left side of screen to return to the Dealer Control Center.
IMPORTANT
Adding dealer information will ensure the thermostat is associated with your LennoxPros.com account when connecting to the Lennox server.
Information Pop-Up Screen:
If the dealer ID or phone number is not provided, a warning screen will appear. The warning screen will provided information on the limitation imposed on the system if this information is missing. Touch no to return to the above screen to complete the information requested or press yes to continue.
General Information
On this screen general information needs to be verified or changed. Touch any item to change its contents. A pop-up screen will appear that will allow the information to be added or changed.
Information Required:
Home Address
On this screen general information needs to be verified or changed. Touch any line item to change its contents. Information to be added is address 1, address 2, state, city and zip/postal code. Complete the requested information and press the continue button.
For firmware version 3.15 and later, all controls for dehumidification are listed at menu > settings > humidity. Under Humidity Control, select dehumidify to enable dehumidification. By default it is disabled.
When dehumidify is enabled, the options are as follows and are dependent on equipment type and accessory installed.
Dehumidification Setting Options
Slide bar adjust with a range of 0°F to 4°F (-17.8 to -15.5°C). Only available when Max is selected.
Dehumidification Set Point
Slide bar adjust with a range of 40% to 60%.
Advanced Dehumidification Descriptions
See table 1 for detail information concerning system operations when using Normal or Max settings.
Table 12. Dehumidification Control Modes of Operations
Mode of Operation | Option | Description |
Dehumidification Only | Normal | Staged Outdoor Units: Dehumidifies while servicing a cooling demand and will not over-cool. The over-cool slider is hidden from the user. |
Max | Staged Outdoor Unit: If at the start or during a cooling call, the humidity is above the relative humidity set point then the unit dehumidifies during the cooling demand. If at the time the cooling call terminates, the humidity demand is not satisfied, over-cooling will occur up to the over-cooling slider setting in an attempt to satisfy the dehumidification demand. Once the room temperature reaches the over-cooling set point. If the system still has a dehumidification demand, the system keeps using the over-cooling set point as its operating cooling set point (will not wait for the temperature to rise to the normal cooling set point to run again) until the dehumidification demand is satisfied | |
(ERV, HRV and Fresh Air Damper)
This equipment is designed to provide fresh air while exhausting an equal amount of stale air.
Ventilation Rates
The E30 ventilation function is only a turn on – turn off feature. All CFMs must be adjusted from the HRV/ERV unit. The ventilation function can be controlled by outdoor temperatures and by timers in the thermostat. The ventilation feature can also control 1 and 2 stages of ventilation operation.
Thermostat ventilation CFM parameters are to be adjusted only after the HRV/ERV set up is completed and the CFMs are known. Once the thermostat’s CFMs are adjusted they are used with the thermostat’s timer algorithm to determine how long to run the HRV/ERV and to change from low to high speed if a 2-stage HRV/ERVs.
Energy Recovery Ventilator (ERV)
The ERV unit is equipped with an enthalpic core. This device is designed for use in warm, humid climates with heavy air conditioning loads. The ERV unit transfers both sensible (temperature) and latent (moisture) heat from incoming fresh air to the stale air as it is being exhausted; thus, reducing the air conditioning load.
Heat Recovery Ventilator (HRV)
The HRV unit is equipped with an aluminum core. The device uses the stale air that is being exhausted to condition the fresh air as it is being brought in.
Lennox models are all non-communicating equipment and can be added during the commissioning procedure (see “Commissioning (Using the HD Display)” on page 15).
Fresh Air Damper
This option is used to control a damper connecting outside air to the return plenum of the system. When a fresh air damper style of ventilation is added to the system, and ventilation is required, the ventilation demand is serviced by energizing 1 relay to close or open the relay contacts connected to the fresh air damper and commanding the blower to run at a rate of at least the continuous fan speed.
The parameter Fresh Air Damper Ventilation CFM represents the CFM of the air drawn through the fresh air damper while the system runs the indoor blower at the continuous fan speed for non-zoned systems, and the lowest zone CFM (continuous fan, heating, or cooling) for zoned applications. All calculations used to determine the ventilation volume requirement and the amount of ventilation air delivered use this number regardless of the actual fan speed.
Zoning Application
Operation of Fresh Air Dampers with Environmental Overrides
Parameter settings and descriptions are listed in “Table 7. Smart Hub Parameters” on page 18. The table below list which parameters are available for the Fresh Air Damper, ERV and HRV equipment.
Wiring connections are listed in “Figure 15. iComfort E30 to either ERV or HRV” on page 10 and “Figure 16. iComfort E30 to Fresh Air Damper” on page 10.
Ventilation Control Modes
Thermostat ventilation CFM parameters are to be adjusted only after the HRV/ERV set up is completed and the CFMs are known. Once the thermostat’s CFMs are adjusted they are used with the thermostat’s timer algorithm to determine how long to run the HRV/ERV and to change from low to high speed if a 2-stage HRV/ERVs.
Table 13. Ventilation Control Modes
Ventilation Minutes Per Hour (0 to 60 min., default is 20 min.) | X | X | X | X | X |
Ventilation Rate (20 to 500 cfm, default is 130 cfm) (Shown only for single speed ERV or HRV) | X | X | X | ||
Ventilation Rate for Low Speed (10 to 200 cfm, default is 50 cfm) (Shown only for two speed ERV or HRV) | X | X | |||
Ventilation Rate for High Speed (20 to 500 cfm, default is 130 cfm) (Shown only for two speed ERV or HRV) | X | X | |||
Ventilation High Outdoor Temperature Limit (60 to 115°F, default is 100°F) | X | X | X | X | X |
Ventilation Low Outdoor Temperature Limit (–20 to 55°F, default is 0°F) | X | X | X | X | X |
Ventilation High Outdoor Dew Point Limit (45 to 80°F, default is 55°F) | X | X | X | X | X |
NOTE: In this mode the thermostat can assist the installer by validating the ventilation CFMs are capable of meeting the ASHRAE required ventilation volumes, but the thermostat has no ability to control CFM from the HRV/ERV.
Ventilation Rate (20 to 500 cfm, default is 130 cfm) | X | X | X | ||
Ventilation Rate for Low Speed (10 to 200 cfm, default is 50 cfm) | X | X | |||
Ventilation Rate for High Speed (20 to 500 cfm, default is 130 cfm) | X | X | |||
ASHRAE Compliance Check | NO | YES | YES | YES | YES |
ASHRAE Infiltration Credit (0 to 200 cfm, default is 0 cfm) | X | X | X | X | X |
ASHRAE House Floor Area Serviced by this Ventilator | X | X | X | X | X |
ASHRAE Number of Bedrooms | X | X | X | X | X |
Ventilation Outdoor Condition Override – Enabled
Ventilation High Outdoor Temperature Limit (60 to 115°F, default is 100°F) | X | X | X | X | X |
Ventilation Low Outdoor Temperature Limit (–20 to 55°F, default is 0°F) | X | X | X | X | X |
Table 13. Ventilation Control Modes
Ventilation Control Mode | Fresh Air Damper | 1 Speed HRV | 2 Speed HRV | 1 Speed ERV | 2 Speed ERV |
Ventilation High Outdoor Dew Point Limit (45 to 80°F, default is 55°F) | X | X | X | X | X |
This is for connecting the thermostat to a secure home wireless network.
NOTE: A router with Apple Bonjour® capabilities is required for this function. Check the router functions if the smart hub does not connect. Apple Bonjour is an implementation of zero-configuration networking (Zeroconf), a group of technologies that includes service discovery, address assignment, and host name resolution.
NOTE: Never use a home guest account. Never use an open router connection (non-secure). Always use a secure connection physically located in the home where the thermostat is located.
Home Wi-Fi Access Point is Visible
Home Wi-Fi Access Point is Hidden
The following terminology is used in this troubleshooting section:
Electromagnetic Interference Causing Poor Connectivity:
Locate the smart hub and router away from other devices that could possibility interfere with wireless communications. Some examples of other devices that could interfere are:
To eliminate a possible source of interference, temporally disable any devices and see if Wi-Fi performance has improved.
Received Signal Strength Indication (RSSI)
The ideal signal strength range for the thermostat is -1 to -69 RSSI. The signal strength can be viewed from the thermostat interface.
Performance reports are only available through either the consumer or dealer web portals.
More information concerning Performance Reports is available in the user guide.
The following thermostat component parts can be ordered:
Table 14. Replacement Parts
Catalog # | Component | Remarks |
17H17 | HD display | Thermostat interface |
15S64 | Smart hub | Control base |
iComfort Thermostat App (Homeowner)
The free iComfort® Thermostat app is available for use on iPhone®, iPad® and Android™ devices.
Control cooling/heating temperatures, fan operation, set programs and set Away mode for multiple locations.
iComfort Mobile Setup App (Installer)
Allows the installer to commission the system and remotely turn the system on and off during setup on any iPhone®, iPad® and Android™ device. Apple, the Apple logo, iPhone and iPad are trademarks of Apple Inc. registered in the US and other countries.
Android is a trademark of Google Inc. Use of this trademark is subject to Google permission.
These screens provide information on active notifications and previously cleared notifications. When selecting either a cleared or active notification a brief description and alert code will be displayed. Notifications are categorized by system, indoor unit (air handler or furnace), outdoor unit (air conditioner or heat pump), zoning control (if installed) and thermostat.
Alert Code Types
To expand a specification notification to access a more detail description of the alert code, press the down arrow to expand the description.
Communication System: When communication controls are operating in a communication system, all jumper and link setting on controls are ignored. Jumpers and link setting are treated as defaults and would only be active if the system was converted to a non-communicating system.
Soft disabling is when the Lennox communicating thermostat finds an unknown control on the E30 system communication bus. The thermostat sends the unknown control a message to go into soft disable mode until the component is properly configured or removed.
The Lennox communicating thermostat will not show any code for a soft disabled control. When soft disabling occurs only the control that has been disabled will display the blinking LED status. Refer to the device’s installation and setup guide for further guidance.
Use the following procedure when a soft disable code is present:
The following are service notification alert codes.
Table 15. Service Alert Notification Codes
Service Alert Code | Function |
3000 | Filter 1 |
3001 | Filter 2 |
3002 | Humidifier pad |
3003 | UV Light |
3004 | Maintenance |
3005 | PureAir Maintenance |
4000 | User Wi-Fi state change, disabled |
4001 | Firmware download failed |
4002 | Image file download failed |
Table 16. Alert Codes and Troubleshooting | |||||
GF= Gas Furnace, AH=Air Handler, ID=Indoor unit (GF or AH), HP=Heat Pump, AC=Air Conditioner, OD=Outdoor Unit (AC or HP), PA=Pure Air S, ZA=Zone system and TS=Thermostat | |||||
Alert Code | Inverter Flash Code | Priority Condition | Actual Displayed Alert Text Under dealer control center > Notifications |
Component or System Operational State and Troubleshooting Tip |
How to clear alert code |
10 |
Service Urgent |
Unknown Device Detected | The thermostat when NOT in configuration mode has detected an unknown device. Typically the thermostat will send a command to the unknown device and place the device into a soft disable state. The soft disable control will indicate so as follows: • On air handler, furnace and outdoor controls, the soft-disabled state is displayed by double horizontal lines on seven-segment display. • On the damper control module, the green LED will flash 3 seconds on and 1 second off. • On the equipment interface module, the green LED will flash 3 seconds on and 1 second off. • A new communicating device has been added to the system since the original configuration setup was completed. • Go to menu > settings > advanced settings > view dealer control center > equipment and press reset all equipment. This will allow the system to auto-detect any Lennox communicating devices attached. |
Clear alert code by reconfiguring the system. | |
12 |
Service Urgent |
Indoor Unit Not Detected | Thermostat did not find an indoor unit. Make sure there is an Lennox communicating indoor unit on the system. • Check for voltage and missing component. • Check R, i+, i- and C connections at mag-mount or subbase, smart hub and all attached communicating components. • Ohm wires for electrical continuity. • Cycle power to both indoor unit first and then thermostat. • Verify that equipment interface module (if applicable) is configured as either an air handler or furnace when used with a non-communicating indoor unit. • Go to menu > settings > advanced settings > view dealer control center > equipment and press reset all equipment. This will allow the system to auto-detect any Lennox communicating components attached. • Replace indoor unit control if there is no response. |
Automatically clears when the system detects that the issue no longer exists. | |
14 |
Service Urgent | Too Many Devices of the Same Type | The thermostat found more than one thermostat, indoor or outdoor unit on the system. • Check wiring and remove duplicate equipment. • Go to menu > settings > advanced settings > view dealer control center > equipment and press reset all equipment. This will allow the system to auto-detect any Lennox communicating components attached. | Automatically clears when the system detects that the issue no longer exists. |
Table 16. Alert Codes and Troubleshooting | |||||
GF= Gas Furnace, AH=Air Handler, ID=Indoor unit (GF or AH), HP=Heat Pump, AC=Air Conditioner, OD=Outdoor Unit (AC or HP), PA=Pure Air S, ZA=Zone system and TS=Thermostat | |||||
Alert Code | Inverter Flash Code | Priority Condition | Actual Displayed Alert Text Under dealer control center > Notifications |
Component or System Operational State and Troubleshooting Tip |
How to clear alert code |
105 |
Service Urgent |
Communication Problem | One of the system components has lost communication with the system. The system component (device) is unable to communicate. • S30 – Access dealer control center, select notifications icon, review alert code details to determine which device or unit has the communication problem. Review both active and cleared alerts. • Wi-Fi – Press and hold the Lennox logo on the bottom right of stat for 5 seconds to access the dealer control center. Follow the prompts to access the dealer / installer screen and select the “Alerts” tab. Review alert code details to determine which device or unit has the communication problem. Review both active and cleared alerts. • Zoning – Remove wire from smart hub to iHarmony control and just have wiring from furnace. Troubleshooting: • Check each control for additional codes • In most cases issues are related to electrical noise. Verify that high voltage power is separated from the low voltage communication wires. • Check for proper grounding on line voltage and low voltage wiring, transformer and equipment. • Check for incorrectly wired or loose or spliced connections between system components (devices or units). • Make sure all unused wires are tied together and taken back to the C terminal on the indoor control board as shown in the installation and setup guide. • Disconnect all wiring to other system components (except thermostat to indoor unit) and reconnect one device at a time and recommission system each time a device is reconnected until the issue is located. • Zoning: If zoning is installed and is wired directly from smart hub to iHarmony control then disconnect that wiring. Run control wiring from the iHarmony control directly to the indoor unit control. Wiring diagrams are provided in the iHarmony Installation and Setup Guide. • Float Switch: When using a float switch, use isolation relay to break common wire to outdoor unit. For testing purposes, remove float switch from the circuit. • Firmware and Accessories: Make sure that smart hub has correct firmware version for added accessory. (Example: Pure Air S and/or Apple Home Kit must have software version 3.4 or higher before it will connect to system properly. (If software is not updated in system it will cause system operation issues). • Inductive voltage from surrounding sources. Check each wire in AC mode to C on circuit board. > Good voltage is .03-.3VAC inductive voltage is not an issue. > Acceptable can be up to .7VAC with moderate success. > Some units have worked with up to 1.2VAC with occasional success. > Voltage over 1.2VAC needs to be addressed. |
Automatically clears when the system detects the issue no longer exists. |
Table 16. Alert Codes and Troubleshooting | |||||
GF= Gas Furnace, AH=Air Handler, ID=Indoor unit (GF or AH), HP=Heat Pump, AC=Air Conditioner, OD=Outdoor Unit (AC or HP), PA=Pure Air S, ZA=Zone system and TS=Thermostat | |||||
Alert Code | Inverter Flash Code | Priority Condition | Actual Displayed Alert Text Under dealer control center > Notifications |
Component or System Operational State and Troubleshooting Tip |
How to clear alert code |
110 | Service Urgent | GF Low AC Line Voltage | The component AC line voltage is too low. This alert code may appear during a brownout. • It may also occur when line voltage is below its designed operating value. • Check and correct the power line voltage. | Automatically clears when the system detects the issue no longer exists. | |
115 |
Service Soon/Service Urgent |
Low Secondary (24VAC) Voltage | 24VAC power to a system component control is lower than the required range of 18 to 30VAC. • Check and correct voltage. • Check for additional power-robbing system components (devices) connected to system. • This alert code may require the installation of an additional or larger VA transformer. • Damper control module will operate in non-zone mode until proper voltage is restored. |
Automatically clears when the system detects the issue no longer exists. | |
120 |
Service Soon/Service Urgent |
Unresponsive Device | There is a delay in the system component responding to the system. Typically this alert code does not cause any operational issues and will clear on its own. • This alert code is usually caused by a delay in the outdoor unit responding to the thermostat. • Leaking voltage from strands within the bundle. > Land only the R wire on the R terminal to load the bundle with 24VAC. ► Typically only the R wire needs to be landed to identify if voltage is leaking. ► If voltage is present checking the other wires is informational only but not needed. ► If voltage is not present checking the other wires one at a time would be needed. > Check each loose wire in AC mode to C on circuit board. ► Good voltage is .03 -.3VAC leaking voltage is not the issue. ► Acceptable can be up to .7VAC with moderate success. ► Some units have worked with up to 1.2VAC with occasional success. ► Voltage over 1.2VAC needs to be addressed. |
Automatically clears after an unresponsive system component (device) responds to any inquiry. |
Table 16. Alert Codes and Troubleshooting | |||||
GF= Gas Furnace, AH=Air Handler, ID=Indoor unit (GF or AH), HP=Heat Pump, AC=Air Conditioner, OD=Outdoor Unit (AC or HP), PA=Pure Air S, ZA=Zone system and TS=Thermostat | |||||
Alert Code | Inverter Flash Code | Priority Condition | Actual Displayed Alert Text Under dealer control center > Notifications |
Component or System Operational State and Troubleshooting Tip |
How to clear alert code |
124 |
Service Urgent |
Tstat Lost Communication To Smarthub | The thermostat has lost communication with a system component for more than three minutes. System component has lost communication with the thermostat. • Check the wiring connections between components. • Ohm wires. • Cycle power. • Any component that is miss-wired may cause a false component code to be shown on system component. • Disconnect all wiring to other system components and check communication one at a time. NOTE: When using a float switch, use isolation relay to break common wire to outdoor unit. For testing purposes, remove float switch from the circuit This alert code stops all associated system operations and waits for a heartbeat message from the system component that is not communicating. |
Automatically clears after communication is re-established with applicable system component (device). | |
125 |
Service Urgent |
Control Hardware Problem | There is a hardware problem on a system component control. There is a control hardware problem. • In system using iHarmony zoning, the system will remain in non-zone mode (all dampers open) for five minutes after priority condition no longer exist. • In systems using a Equipment Interface Module, remove jumper if present on indoor unit between R and W2. • In systems using a PureAir S, the pure air control board jumper selector is missing. If none of the above tips are applicable, then replace the control if the problem prevents operation and is persistent. |
Automatically clears five minutes after the issue no longer exists. | |
126 |
Service Urgent | Control Internal Communication Prob | There is an internal hardware problem on the system component control. In addition, if you have zoning the alert code is triggered when your zone temperature is deviating away from set point persistently. • Typically the system component control will reset itself. • Replace the system component (device) control if the problem prevents operation and is persistent. |
Automatically clears 300 seconds after the issue no longer exists. | |
130 |
Service Urgent |
Configuration Jumper Missing | • Configuration jumper missing on equipment interface module. • Install the missing jumper. • Set as heat pump, furnace control or air handler control. NOTE: This is applicable in non-communicating applications only. | Automatically clears after the missing or incorrectly installed jumper is installed or corrected. |
Table 16. Alert Codes and Troubleshooting | |||||
GF= Gas Furnace, AH=Air Handler, ID=Indoor unit (GF or AH), HP=Heat Pump, AC=Air Conditioner, OD=Outdoor Unit (AC or HP), PA=Pure Air S, ZA=Zone system and TS=Thermostat | |||||
Alert Code | Inverter Flash Code | Priority Condition | Actual Displayed Alert Text Under dealer control center > Notifications |
Component or System Operational State and Troubleshooting Tip |
How to clear alert code |
132 | Service Urgent | Device Control Software Fault | System component control software is corrupted. • Recycle power. • If failure re-occurs, replace the system component control. | Manual system power reset is required to recover from this alert code. | |
180 |
Service Soon |
Outdoor Temperature Sensor Problem | The thermostat has found a problem with the outdoor temperature sensor. In normal operation after system component control recognizes sensors, the alert code will be sent if valid temperature reading is lost. • Compare outdoor sensor resistance to temperature / resistance charts in unit installation instructions. Replace sensors pack if necessary. • At the beginning of (any) configuration, furnace, air-handler control or equipment interface module will detect the presence of the sensor(s). • If detected (reading in range), appropriate feature will be set as ‘installed’ and shown in the ‘About’ screen. |
Automatically clears upon configuration, or sensing normal values. | |
310 |
Service Soon |
Discharge Air Temp Sensor Problem | There is a discharge air temperature sensor issue. • Confirm there is no short or open circuits in the Lennox communicating thermostat connections to any of the other components in the communication system. • Compare discharge air temperature sensor (DATS) resistance to temperature / resistance charts in system component installation instruction. • Replace discharge air sensor if necessary. NOTE: Issues with a DATS connected to a damper control module or equipment interface model will not generate an alert code. |
Automatically clears 30 seconds after condition is detected as recovered or after system restart. | |
344 | Service Urgent | GF IFC Relay Y1 Stuck | Link Relay Problem. Issue could be with possible Y1 relay failure. NOTE: Relay is located on the IFC (Integrated Furnace Control). If issue continues replace IFC. | Automatically clears five minutes after Y1 input sensed OFF. | |
345 |
Service Urgent |
Relay O Failure | The O relay on the system component has failed. Either the pilot relay contacts did not close or the relay coil did not energize. • Possible O relay / stage 1 failure. • Pilot relay contacts did not close or the relay coil did not energize. • Replace system component (device) control. If error is applicable to the XC20, XC25, XP20 or XP25, the outdoor control will need to be replaced. |
Automatically clears after the fault recovered following reset. |
Table 16. Alert Codes and Troubleshooting | |||||
GF= Gas Furnace, AH=Air Handler, ID=Indoor unit (GF or AH), HP=Heat Pump, AC=Air Conditioner, OD=Outdoor Unit (AC or HP), PA=Pure Air S, ZA=Zone system and TS=Thermostat | |||||
Alert Code | Inverter Flash Code | Priority Condition | Actual Displayed Alert Text Under dealer control center > Notifications |
Component or System Operational State and Troubleshooting Tip |
How to clear alert code |
346 |
Service Urgent |
HP Jumper Not Removed | The heat pump configuration link is not cut on the air handler control. • Configuration link not cut on air handler control. • Cut O to R. NOTE: This is only applicable when matching non-communicating heat pump with Lennox communicating indoor unit. |
Automatically clears when the system detects that the issue no longer exists. | |
347 |
Service Urgent |
ID or EIM Relay Y1 Fault | • Lennox communicating thermostat sends a Y1 compressor demand to the indoor control requesting it to relay the demand to the outdoor unit. • The indoor unit communicating control will verify the presences of 24VAC between the Y1 and C on its terminals. If it does not detects the presences 24VAC, it will trigger alert code 347. Possible cause for alert code 347 is Y1 relay on the applicable system component has failed. Either the furnace pilot relay contacts did not close or the relay coil did not energize. • System operation will stop. • Possible Y1 relay / stage 1 failure. • Furnace pilot relay contacts did not close or the relay coil did not energize. NOTE: There is no input back to the applicable system component control. |
Automatically clears after reset and Y1 input sensed. | |
380 |
Service Urgent |
EIM Interlock Relay Fault | Interlock relay failure (furnace or air handler modes only). • Interlock relay is energized, but input is not sensed after three seconds. • There will be no heating or cooling due to this alert code – moderate condition. • De-energize interlock relay and energize after five minutes if demand is still present – critical condition. |
Automatically clears after fault recovered. | |
381 | Service Urgent | EIM Interlock Relay Stuck | Interlock relay stuck (furnace or air handler modes only). • Interlock relay continuously sensed (with relay off). • There is no heating and cooling operation – moderation condition. • After 10 minutes if event still exist it will be escalated to priority condition service urgent. | Automatically clears 30 seconds after fault clears. | |
382 | Service Urgent | EIM Relay W1 Fault | Relay W1 failure (furnace or air handler modes only). W1 relay is energized but input is not sensed after three seconds. | Automatically clears when W1 relay input is sensed. |
Table 16. Alert Codes and Troubleshooting | |||||
GF= Gas Furnace, AH=Air Handler, ID=Indoor unit (GF or AH), HP=Heat Pump, AC=Air Conditioner, OD=Outdoor Unit (AC or HP), PA=Pure Air S, ZA=Zone system and TS=Thermostat | |||||
Alert Code | Inverter Flash Code | Priority Condition | Actual Displayed Alert Text Under dealer control center > Notifications |
Component or System Operational State and Troubleshooting Tip |
How to clear alert code |
418 |
Service Soon |
OD EIM W Output Hardware Fault | There is a faulty W output circuit. • W terminal is energized while in cooling mode. • Possible cause may be a stuck closed relay on the control, or something external to the control that is energizing W terminal when it should not be energized. • Disconnect any wiring from the W terminal. • If 24VAC is still present on the terminal, then it is a stuck relay. • If 24VAC disappears, then there is a need to check any of the wires hooked up to the W terminal. |
Automatically clears after fault signal is removed. | |
419 |
Service Urgent | OD EIM W Output Hardware Fault Lockout | The W output has reported more than five errors. • The system will shut down the outdoor unit. • The W output (alert code 418) on the outdoor unit has reported more than five strikes. • Disconnect thermostat wire from W and verify there is no 24VAC on the W. • If 24VAC is present, replace the outdoor control. |
Automatically clears after power recycled. | |
420 |
Service Soon | AH EIM Defrost Out Of Cycle | The heat pump defrost cycle has taken more than 20 minutes to complete. • Defrost cycle lasts longer than 20 minutes. • Check heat pump operation. • This is applicable only in communicating indoor unit with non-communicating heat pump. | Automatically clears when W1 signal is removed. | |
421 | Service Urgent | OD EIM W External Miswire Fault | The W output terminal on the outdoor unit is not wired correctly. Voltage sensed on W output terminal when Y1 out is deactivated. | Automatically clears once voltage is not sensed on output or power is cycled. | |
610 |
Service Urgent |
Low Room Temperature Detected | This alert will automatically notified the user that a low room temperature condition exist. A notification is displayed on the HD display and email notification sent to homeowner and dealer. The freeze alert protection parameter range is 30°F to 50°F (-1.11 to 10.0°C). Default is 40°F (4.44°C). NOTE: Notification is dependent on the thermostat having a active Wi-Fi connection and the user account has been setup and includes a valid email address. |
Automatically clears when condition is resolved. | |
611 |
Service Urgent |
High Room Temperature Detected | This alert will automatically notified the user that a high room temperature condition exist. A notification is displayed on the HD display and email notification sent to homeowner and dealer. The heat alert protection parameter range is 80°F to 100°F (26.67 to 37.78°C). Default is 90°F (32.22°C). NOTE: Notification is dependent on the thermostat having a active Wi-Fi connection and the user account has been setup and includes a valid email address. |
Automatically clears when condition is resolved. |
Table 16. Alert Codes and Troubleshooting | |||||
GF= Gas Furnace, AH=Air Handler, ID=Indoor unit (GF or AH), HP=Heat Pump, AC=Air Conditioner, OD=Outdoor Unit (AC or HP), PA=Pure Air S, ZA=Zone system and TS=Thermostat | |||||
Alert Code | Inverter Flash Code | Priority Condition | Actual Displayed Alert Text Under dealer control center > Notifications |
Component or System Operational State and Troubleshooting Tip |
How to clear alert code |
700 |
Service Urgent |
Thermostat Temp Sensor Problem | The HD display’s internal temperature sensor is not operating correctly. To resolve this issue, try the following: • Remove HD display from mag-mount and reattaching. • Seal hole in wall behind mag-mount to minimize exposure to unconditioned air from inside the wall. • Run “reset all” under dealer control center. • If issue persist, then replace the HD display. |
Automatically clears when the system detects that the issue no longer exists. | |
701 |
Service Urgent |
Thermostat Temp Above Limit | The thermostat is reading indoor temperatures above the pre-programmed limit. The thermostat has a built-in non-adjustable high limit of 99°F. • Cool thermostat. • Adjust set point. • Run reset all under dealer control center. • Replace HD display or mag-mount, if needed. |
Automatically clears when the system detects that the issue no longer exists. | |
703 |
Service Soon | Thermostat Humid Sensor Problem |
Thermostat Humid Sensor Problem. Sensor is damaged or data is corrupted possibly.. | First try a system reset, then if persists the thermostat would need replacement. | |
— |
Service Soon |
— | Possible loose or mis-wired connections or two zone sensors are assigned the same zone number. Two dashes will be displayed on the S30 thermostat for indoor temperature and/ or zone sensor. The system will go into central mode. Individual zone functions is disabled. Anytime the zone sensor loses communication with the damper control module, the entire system will go into central mode. If two sensors are assigned the same zone number, this could result in the double dashes to appear as well. | If two zone sensors are assigned the same zone number, this could cause the double dashes to appear. If loose or mis-wired connection was confirmed, correct the issue and run the re-configuration procedure. |
Smart Hub Checks: | YES | NO | |
1 | Is the smart hub properly mounted to either a wall stud or wall? NOTE: Do not mount on equipment or ductwork. | ||
2 | Is communication status LED (green) visible when hinged cover is closed? NOTE: When LED is active it indicates that 24VAC is present at the smart hub. It also indicates communication is active between smart hub and HD Display. | ||
3 | Is blinking communicating green LED seen (located in center of smart hub) when cover is open? | ||
4 | Are all terminal wiring properly connected and tight? | ||
5 | Are jumpers set to proper equipment type and number of stages? | ||
6 | When required, is either or both the discharge (DATS) and outdoor air temperature (OATS) sensors properly connected and isolated when used? | ||
HD Display Subbase Checks: | YES | NO | |
1 | Are all terminal wiring properly connected and tight? | ||
HD Display Checks: | YES | NO | |
1 | Is the HD Display properly placed and connected to subbase? | ||
2 | Are all terminal wiring properly connected and tight on subbase? | ||
3 | Is the screen blank after initial power-up? NOTE: The HD Display may take up to three minutes before anything appears on the screen due to a HD Display low battery condition. HD Display battery charging only occurs when connected to the subbase. | ||
System Checks | YES | NO | |
1 | Is the Wi-Fi connected? | ||
2 | Can the homeowner access the consumer portal (www.myicomfort.com) from either a PC or tablet? | ||
3 | Has the homeowner downloaded the Lennox Thermostat application from either Google Play or IOS App Store to their mobile devices? | ||
4 | Is the Lennox Dealer account number or your main shop phone number been added to the dealer information screen? | ||
5 | Has a complete system test been run? If not, from the HD Display home screen go to settings > advanced settings > view dealer control center > and select tests. |
The dealer dashboard displays Dealer’s iComfort® thermostat installations in one convenient location. It is accessible through the Service Dashboard at www.LennoxPros.com.
The thermostat can be accessible via the Dealer Dashboard only after the dealership’s main phone number or company name is added during thermostat commissioning. See “Dealer Info” on page 16 for further details for adding your dealer information.
Service Dashboard Search Screen
Customer Results Screen
Displays a list of customers with installed iComfort® thermostats, and their locations:
Map displays the following:
NOTE: Click on a customer’s pin to view information about their system.
NOTE: Selecting a customer from the list or map pin displays the detailed System Overview Screen including owner information, system components, system history, status and any alerts.
Home Systems
System History
This section provides a list of alerts over the past 12 months
Remote In Button
Alerts & Reminders: System
Tabs for Alerts – Critical, Moderate, Cleared and Reminders
NOTE: Clicking on a card with an alert expands to display the Remote In control (if enabled by the homeowner) and Troubleshoot (access to the Lennox Troubleshooting Center which includes error code lookups and any available documentation).
Equipment & Reports
Download manual:
Lennox E30 Smart Thermostat Installation Guide
Other manuals:
Lennox S30 Smart Thermostat User Guide
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…