IEC’s line of commercial programmable low-voltage fan coil thermostats maintains room temperatures by controlling the operation of 2- or 4-pipe fan coil systems. These thermostats have separate heating and cooling set points with auto-changeover as standard features. The thermostat has a 3-speed fan operation capability and the option to show single or dual set points. Programming of up to 3 occupied and 1 unoccupied time/temperature settings is allowed. Batteries are not required. During power interruption, the internal memory stores schedule for an unlimited time while the clock will continue to run for at least 48 hours. .
Year-round comfort is assured
One-degree control accuracy precisely monitors the desired space temperature to within 1 degree of user set point by using a solid-state, laser-trimmed sensor. Heating and cooling LED operation glows red when unit is in the Heating mode and green when unit is in the Cooling mode. Neverlost™ memory protection on the thermostat eliminates the need to reconfigure the thermostat after power outages so your configurations will remain intact indefinitely. IEC’s warranty ensures peace of mind.
Easy programming for quick operation:
The backlit Thermoglow™ display is large and easy to read. The backlight feature can be configured for either button activation or continuous lighting. Also simple adjustments will display room temperatures in either Celsius or Fahrenheit, time of day, or temperature and set points. Four time periods per day allow flexibility to create schedules for every application. Start and stop times along with heating and cooling set points are easily entered into the schedule.
Recommended Wiring | 22 AWG (36 ft max) 18 AWG (100 ft max) |
Operating Temperature F (C) | 41 to 104 (5 to 40) |
Storage Temperature F (C) | -40 to 135 (-40 to 57) |
Operating Relative Humidity | 0 to 95% (non- condensing) |
Dimensions (In.) | 3.13 x 3.13 x 1.13 |
Power | 5 va at 24 vac, 60 Hz |
Agency Approvals: Complies with FCC Part 15 rules. Thermostat does not cause harmful interference and accepts all interference received. UL and UL, Canada approval. These thermostats are considered low voltage devices by UL and do not require UL approval. As an added assurance to the quality of the thermostats, these thermostats are UL listed. Title 24 compliance. Meets specified requirements of programming capability for all California commercial installations.
System Description:
24 V programmable, 2- or 4-pipe (or electric heat), room fan coil unit controller with digital display
Quality Assurance: Unit shall be tested and certified in accordance with FCC Part 15 for RF interference, is UL and UL Canada certified, meets European Community standards and meets specified programming capability requirements for all California commercial installations.
Delivery, Storage and Handling: Each unit shall be individually packaged from point of manufacture and shall be handled and stored in accordance with the manufacturer’s instructions.
General: The low-voltage, 7-day programmable digital thermostat shall be capable of maintaining room temperature by controlling the operation of an HVAC system.
Mounting: The thermostat shall be wall-mounted, surface-mounted, or unit-mounted.
Standard Features: The thermostat shall allow separate heating and cooling set points and auto-changeover as standard.
Configurations: The thermostat shall accept several different equipment configurations/applications including single-stage heating and cooling, two stages of heating and cooling, or electric heating and hydronic systems.
Power: Batteries shall not be required. During power interruption, the internal memory shall store user-defined default settings as well as the user’s comfort programming and configuration. Clock and day of the week settings shall be retained for a minimum of 48 hours.
Display: The backlit thermostat display shall be large and easy to read with a single adjustment to show the temperature in Celsius or Fahrenheit.
Settings: The thermostat shall have a solid-state, laser-trimmed sensor with one-degree control accuracy to precisely control the desired space temperature to within 1 degree of the user set point.
The thermostat shall have an auto-changeover with an adjustable headband to enable the user to choose separate heating and cooling set points (35°F to 99°F). This adjustable deadband shall be configurable to the user’s specifications (from 1° to 6°F) and in cycles per hour (2 to 6).
Other Features: For safety purposes, the front panel buttons shall be capable of being disabled to prevent unauthorized use of the thermostat.
Optional Features: Exact Fit® locking cover installed with optional standard or special tools to prevent unauthorized users from accessing the front panel buttons.
Mounting plate and cover plate to allow the thermostat to be mounted directly to the wall or to standard 2” x 4” or 4” x 4” junction box.
Schedules:
Four-Pipe Operation
The Mode button selects the operating mode of the thermostat. If Off is selected, the thermostat will not enter Heating or Cooling mode. If Heat is selected, the thermostat will only enter Heating mode (if the room temperature is below the heating set point). If Cool is selected, the thermostat will only enter Cooling mode (if the room temperature is above the cooling set point). If Auto is selected, the thermostat will enter Heating or Cooling mode based on the room’s temperature and the heating and cooling set points.
Two-Pipe Operation:
Total or Auxiliary Electric Heat:
The Mode button selects the operating mode of the thermostat. If Off is selected, the thermostat will not enter Heating or Cooling mode. If Heat is selected, the thermostat will only enter Heating mode (if room temperature is below the heating set point). For total electric heat, a call for heat will enable the electric heater. For auxiliary electric heat, a call for heat will either enable the electric heater (if chilled water is in the coil), or open the coil valve (if hot water is in the coil). If Cool is selected, the thermostat will only enter Cooling mode (if room temperature is above the cooling set point and chilled water is in the coil). If Auto is selected, the thermostat will enter Heating or Cooling mode based on the room’s temperature and the heating and cooling set points.
Auto Changeover: When the thermostat mode is set to Auto, the thermostat will provide automatic changeover from Heating or Cooling mode and Cooling to Heating mode when required. The thermostat will automatically switch to maintain the desired temperature setting. The thermostat does not need to be manually changed from heating to cooling or cooling to heating operation.
Fan Operation: When only the Fan is in “Auto” mode, it will run continuously (unless thermostat mode is set to Off or thermostat is in unoccupied mode and heating or cooling are not active). The thermostat will increase or decrease the fan speed based on load conditions. Fan operation may also be set to always run at Low, Medium, or High speeds.
Dry Contact Switch/External Control:
Outside Sensor: The thermostat shall display the outside temperature (if the optional outdoor sensor is wired to a thermostat
Download Manual:
Iec E055-71520317 Programmable Fan Coil Thermostat Product Specifications Guide
OTHER MANUALS
IEC E055-71520317 Programmable Fan Coil Thermostat Installational Instruction
IEC E055-71520317 Programmable Fan Coil Thermostat Owners Manual
IEC E055-71520317 Programmable Fan Coil Thermostat Product Specifications Guide
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…