IEC-LOGO

IEC E055-71520317 Programmable Fan Coil Thermostat 

IEC-E055-71520317-Programmable-Fan-Coil-Thermostat-Installational-Instruction-PRODUCT

Auto-Changeover is available in 4-pipe systems, in 2-pipe systems with Electric Heat, or when used with a G100-71520306 accessory, auto-changeover sensor.

CAUTION
Follow Installation Instructions carefully. Disconnect the Power to the Heater/Air Conditioner before removing the old thermostat and installing the new thermostat.

PREPARATION

IEC-E055-71520317-Programmable-Fan-Coil-Thermostat-Installational-Instruction-FIG-1Proper installation of the thermostat will be accomplished by following these step-by-step instructions. If you are unsure about any of these steps, call a qualified technician for assistance.

Assemble tools

REMOVE & REPLACE THE OLD THERMOSTAT

Note: This thermostat is strictly a low-voltage control. One or two E025-71481103 (10a 125vac) or E025-71481104 (20a 125vac) relay boards must be installed to operate the fan coil unit.

MOUNT THE THERMOSTAT

WIRE CONNECTIONS

IEC-E055-71520317-Programmable-Fan-Coil-Thermostat-Installational-Instruction-FIG-1If the terminal designations on your old thermostat do not match those on the new thermostat, refer to the chart below, or the wiring diagrams that follow.

IEC-E055-71520317-Programmable-Fan-Coil-Thermostat-Installational-Instruction-FIG-10

Note: Be sure to seal any opening through the wall behind the thermostat to prevent improper temperature sensing of the conditioned space.

IEC-E055-71520317-Programmable-Fan-Coil-Thermostat-Installational-Instruction-FIG-1If the terminal designations on your old thermostat do not match those on the new thermostat, refer to the chart below, or the wiring diagrams that follow.

IEC-E055-71520317-Programmable-Fan-Coil-Thermostat-Installational-Instruction-FIG-11

Note: Be sure to seal any opening through the wall behind the thermostat to prevent improper temperature sensing of the conditioned space.

Sample Wiring Diagram
4-Pipe, 2 Relay Boards, Line Voltage Water Valves

4-Pipe, Low Voltage Valves, Remote Temperature Sensor & Dry Contact

2-Pipe, Low Voltage Valve, Heat Only or Cool Only

2-Pipe, Low Voltage Valve, H2O Changeover Sensor

Important Note: If a Duct sensor is conn-ected to this thermostat it is suggested that the fan be programmed for continuous operation [step #5,(non-programmable) or step #7 (programmable) in the
Owner’s Manual].

2-Pipe, Low Voltage Valve, Chilled Water with Electric Strip Heat

TEST OPERATION

IEC-E055-71520317-Programmable-Fan-Coil-Thermostat-Installational-Instruction-FIG-1Turn the power on to the Fan Coil Unit.
IEC-E055-71520317-Programmable-Fan-Coil-Thermostat-Installational-Instruction-FIG-1Press the MODE button repeatedly until the HEAT icon appears on the display. Press the UP or DOWN buttons until the set temperature is 10 degrees above room temperature. The hot water valve will open and the fan will be run.
IEC-E055-71520317-Programmable-Fan-Coil-Thermostat-Installational-Instruction-FIG-1Press the MODE button repeatedly until the COOL icon appears on the display. Press the UP or DOWN buttons until the set temperature is 10 degrees below room temperature. The cold water valve will open and the fan will be run.
IEC-E055-71520317-Programmable-Fan-Coil-Thermostat-Installational-Instruction-FIG-1Press the UP button until the setpoint is equal to the room temperature. Press the Fan button repeatedly until a single bar appears next to the Fan icon. Confirm the fan is running on low speed. Press the Fan button again, confirm the fan is running on medium speed. Again, press the Fan button, confirm the fan is running at high speed. Press the Fan button once more, the bars next to the Fan icon should disappear.
IEC-E055-71520317-Programmable-Fan-Coil-Thermostat-Installational-Instruction-FIG-1Press the MODE button repeatedly until the OFF icon appears on the display. Both valves will be closed and the fan will be off.

2-PIPE, CHANGEOVER SENSOR, NO STRIP HEAT
IEC-E055-71520317-Programmable-Fan-Coil-Thermostat-Installational-Instruction-FIG-1Turn the power on to the Fan Coil Unit and confirm that the thermostat is programmed correctly in setup. Steps #3 & #4 (non-programmable) or Steps #5 & #6 (programmable) in the Owner’s Manual.
IEC-E055-71520317-Programmable-Fan-Coil-Thermostat-Installational-Instruction-FIG-1If hot water is available, press the MODE button repeatedly until the HEAT icon appears on the display. Press the UP or DOWN buttons until the set temperature is 10 degrees above room temperature. The hot water valve will open and the fan will be running.
IEC-E055-71520317-Programmable-Fan-Coil-Thermostat-Installational-Instruction-FIG-1If cold water is available, press the MODE button repeatedly until the COOL icon appears on the display. Press the UP or DOWN buttons until the set temperature is 10 degrees below room temperature. The cold water valve will open and the fan will be running.
IEC-E055-71520317-Programmable-Fan-Coil-Thermostat-Installational-Instruction-FIG-1Press the UP button until the setpoint is equal to the room temperature. Press the Fan button repeatedly until a single bar appears next to the Fan icon. Confirm the fan is running on low speed. Press the Fan button again, and confirm the fan is running on medium speed. Again, press the Fan button, confirm the fan is running at high speed. Press the Fan button once more, the bars next to the Fan icon should disappear.
IEC-E055-71520317-Programmable-Fan-Coil-Thermostat-Installational-Instruction-FIG-1Press the MODE button repeatedly until the OFF icon appears on the display. Both valves will be closed and the fan will be off.

2-PIPE, NO CHANGEOVER SENSOR
IEC-E055-71520317-Programmable-Fan-Coil-Thermostat-Installational-Instruction-FIG-1Turn the power on to the Fan Coil Unit and confirm that the thermostat is programmed correctly in setup. Steps #3 & #4 (non-programmable) or Steps #5 & #6 (programmable) in the Owner’s Manual.
IEC-E055-71520317-Programmable-Fan-Coil-Thermostat-Installational-Instruction-FIG-1If hot water is available, press the MODE button repeatedly until the HEAT icon appears on the display. Press the UP or DOWN buttons until the set temperature is 10 degrees above room temperature. The hot water valve will open and the fan will be running.
IEC-E055-71520317-Programmable-Fan-Coil-Thermostat-Installational-Instruction-FIG-1If cold water is available, press the MODE button repeatedly until the COOL icon appears on the display. Press the UP or DOWN buttons until the set temperature is 10 degrees below room temperature. The cold water valve will open and the fan will be running.
IEC-E055-71520317-Programmable-Fan-Coil-Thermostat-Installational-Instruction-FIG-1Press the UP button until the setpoint is equal to the room temperature. Press the Fan button repeatedly until a single bar appears next to the Fan icon. Confirm the fan is running on low speed. Press the Fan button again, confirm the fan is running on medium speed. Again, press the Fan button, confirm the fan is running at high speed. Press the Fan button once more, the bars next to the Fan icon should disappear.
IEC-E055-71520317-Programmable-Fan-Coil-Thermostat-Installational-Instruction-FIG-1Press the MODE button repeatedly until the OFF icon appears on the display. Both valves will be closed and the fan will be off.

IEC-E055-71520317-Programmable-Fan-Coil-Thermostat-Installational-Instruction-FIG-1Turn the power on to the Fan Coil Unit and confirm that the thermostat is programmed correctly in setup. Steps #3 & #4 (non-programmable) or Steps #5 & #6 (programmable) in the Owner’s Manual.
IEC-E055-71520317-Programmable-Fan-Coil-Thermostat-Installational-Instruction-FIG-1If hot water is available, press the MODE button repeatedly until the HEAT icon appears on the display. Press the UP or DOWN buttons until the set temperature is 10 degrees above room temperature. The hot water valve will open and the fan will be running. The strip heat will be locked out if hot water is available.
IEC-E055-71520317-Programmable-Fan-Coil-Thermostat-Installational-Instruction-FIG-1If hot water is not available, but your unit is equipped with a strip heat system, press the UP or DOWN buttons until the set temperature is 10 degrees below room temperature. The unit should energize the strip heaters and the fan will be running.
IEC-E055-71520317-Programmable-Fan-Coil-Thermostat-Installational-Instruction-FIG-1If cold water is available, press the MODE button repeatedly until the COOL icon appears on the display. Press the UP or DOWN buttons until the set temperature is 10 degrees below room temperature. The cold water valve will open and the fan will be running.

IEC-E055-71520317-Programmable-Fan-Coil-Thermostat-Installational-Instruction-FIG-1Press the UP button until the setpoint is equal to the room temperature. Press the Fan button repeatedly until a single bar appears next to the Fan icon. Confirm the fan is running on low speed. Press the Fan button again, confirm the fan is running on medium speed. Again, press the Fan button, confirm the fan is running at high speed. Press the Fan button once more, the bars next to the Fan icon should disappear.
IEC-E055-71520317-Programmable-Fan-Coil-Thermostat-Installational-Instruction-FIG-1Press the MODE button repeatedly until the OFF icon appears on the display. Both valves will be closed and the fan will be off.

IEC-E055-71520317-Programmable-Fan-Coil-Thermostat-Installational-Instruction-FIG-1SYMPTOM: The fan will not run in all three speeds or switches speeds in an improper order. CAUSE: Incorrect wiring between the thermostat and the relay board, or between the relay board and the fan wires.
REMEDY: Recheck the wiring (G=low speed, G2=medium speed, G3=high speed).
IEC-E055-71520317-Programmable-Fan-Coil-Thermostat-Installational-Instruction-FIG-1SYMPTOM: Cold water valve opens for either a cool or a heat demand in a 4-pipe system. CAUSE: The thermostat has been programmed for the incorrect type of fan coil.
REMEDY: Confirm that you have entered the correct programming for your type of fan coil system. Steps #3 & #4 (non-programmable) or Steps #5 & #6 (programmable) in the Owner’s Manual.
IEC-E055-71520317-Programmable-Fan-Coil-Thermostat-Installational-Instruction-FIG-1SYMPTOM: The water valve does not open at all in 2-pipe configurations.
CAUSE: The thermostat has been programmed for the incorrect type of fan coil system or the fan coil is not wired to the thermostat correctly. REMEDY: Program the thermostat for a 2-pipe fan coil. Step #3, (non-programmable) or Step #5 (programmable) in the Owner’s Manual. Also, make certain that the water valve is wired to the Y1 terminal.
IEC-E055-71520317-Programmable-Fan-Coil-Thermostat-Installational-Instruction-FIG-1SYMPTOM: Parts of the thermostat display are missing.
CAUSE: The thermostat has been programmed for a minimal display.
REMEDY: Program the thermostat for Full Display. Step #1, (non-programmable) or Step #3 (programmable) in the Owner’s Manual.
IEC-E055-71520317-Programmable-Fan-Coil-Thermostat-Installational-Instruction-FIG-1SYMPTOM: The thermostat displays large set-point digits instead of the room temperature. CAUSE: The thermostat has been programmed to display Single Setpoint.
REMEDY: Program the thermostat to display Dual Setpoint. Step #2 (non-programmable) or Step #4 (programmable) in the Owner’s Manual.
IEC-E055-71520317-Programmable-Fan-Coil-Thermostat-Installational-Instruction-FIG-1SYMPTOM: The thermostat display is stuck in Unoccupied.
CAUSE: The sensor connected to the Dry Contact terminals of the thermostat, is active, forcing the unit into ‘Unoccupied.’
REMEDY: Verify proper wiring between the thermostat and the occupancy sensor and verify that the wiring is not shorted.
If no sensor is connected, program the Dry Contact polarity for Normally Open. Step #11
(non-programmable) or Step #14 (programmable) in the Owner’s Manual.

TROUBLESHOOTING

IEC-E055-71520317-Programmable-Fan-Coil-Thermostat-Installational-Instruction-FIG-1SYMPTOM: The thermostat will only allow Heat or Off in 2-pipe installations, even though chilled water is available.
CAUSE: Faulty, improperly wired, or improperly installed H2O changeover sensor.
REMEDY: Confirm proper wiring of the change-over sensor (between R and H2O). Confirm proper placement of the sensor (good mechanical coupling for temperature transfer).
Test the changeover sensor as follows:

  1. Remove power from the fan coil system.
  2. Disconnect the wire between the sensor and the H2O terminal.
  3. Place an ohmmeter between R and the wire just disconnected from the sensor.
  4. A good sensor will show continuity whenever the water temperature is confirmed to be at or below 65 degrees. If the sensor is open when the water temperature is confirmed to be at or below 65, replace the sensor.

5000 W I-40 Service Road Oklahoma City, OK 73128 405.605.5000 [phone]  405.605.5001 www.iec-okc.com 008 – 2019 International Environmental Corporation (IEC).

Reference

Download Manual:

IEC E055-71520317 Programmable Fan Coil Thermostat Installational Instruction

OTHER MANUALS

IEC E055-71520317 Programmable Fan Coil Thermostat Owners Manual

Iec E055-71520317 Programmable Fan Coil Thermostat Product Specifications Guide

IEC-LOGO

IEC E055-71520317 Programmable Fan Coil Thermostat Installational Instruction

Leave a Reply

Your email address will not be published. Required fields are marked *

To respond on your own website, enter the URL of your response which should contain a link to this post's permalink URL. Your response will then appear (possibly after moderation) on this page. Want to update or remove your response? Update or delete your post and re-enter your post's URL again. (Find out more about Webmentions.)