HTW-FT03 series Smart Wifi fan coil thermostat is widely used in these environment like Homes, Residential buildings, Schools, Hotels, Hospitals, Offices and etc. to main an ideal room temperature purpose
Ordering Guide
Ordering Guide | |||||
HTW-FT03** | -2 | 2 pipe(tube) system | -W | Wifi Application | |
Smart Wifi Fan Coil Thermostat | -4 | 4 pipe(tube) system | –T | Clock | |
-M | Modulating output | –P | Programmable | ||
-N | Modbus RTU communication | –E | External Temperature Sensor | ||
–K | Key Card occupancy input | –24v | Power Supply with 24Vac | ||
e.g. HTW-WF06-FC-2KP refers to application: 2 pipe(tube) system, 3 fan speed + 1 H/C valve, with key card and weekly programmable | |||||
Specification | |||||
Power Supply | 95~240Vac, 50/60Hz | Sensor | NTC3950, 10K | ||
Current Load | Fan Relay 5A(3A-inductive) | Temperature Accuracy | 0.5°C or 1 | ||
Valve Relay 3A(1A-inductive) | Set-Point Range | 5~35°C | |||
Storage Temp. | -5 ~ 45 °C | Display Temp. Range | 5 ~ 99°C | ||
Power Consumption | < 1.5W | Timing Error | < 1% | ||
Housing Material | PC +ABS ( Fireproof) | Installation Box | EU or Standard Electric Box | ||
Wires on Terminals | Wire 2 x 1.5 mm2 or 1 x 2.5 mm2 | ||||
Protection Class | IP20 | Operating Buttons | Capacitive Touch Buttons | ||
Dimensions and Display
Installer Set-UP Process (ISU)
Parameter | Function | Configurable Value | Default | ||
1 | Temperature calibration | -7°C to +9°C (internal sensor) | -1 | ||
2 | Fan Control Type | 00:When room temp. reaches set point, the fan turns off 01:When room temp. reaches set point, the fan turns to low | 00 | ||
3 | Keypad Lock type | 00: = All buttons will lock except the Power button 01: = All buttons will lock | 01 | ||
4 | Heating/Cooling | 00: Cool only 01:Heating and Cooling | 01 | ||
5 | Min. set-point limit | 5°C – 15°C | 05 | ||
6 | Max. set-point limit | 15°C – 45°C | 35 | ||
7 | 12/24 hours format | 00:12h 01:24h | 01 | ||
8 | Temperature Display | 00:display both set-point and room temp. 01:display set-point only | 00 | ||
9 | Economy Mode | 00:Normal mode 01:Energy Saving mode | 00 | ||
A | Heating Economy Temperature | 10°C – 30°C | 20 | ||
B | Cooling Economy Temperature | 10°C – 30°C | 26 | ||
C | Dead Zone | 1°C to 5°C (Switching differential) | 1 | ||
Warranty |
The installation personnel with non-professional training shall not perform this operation! During thermostat power off, Press these 2 buttons M &
Step 1- Download and Install APP
Use your smart phone or tablet PC to scan the QR code below or Search “SMART LIFE” in the app store /Google play to download and install APP
Step 2- Register your account
Step 3- Connect App with Thermostat
On the thermostat
During power off status, press and hold the arrow icon for
On the App
***If the thermostat has already been connected under above steps, please ignore this process.***
This SMART LIFE App is only supported on 2.4GHz Wi-Fi channels. If the router does not be supported, or the wi-fi signal is weak or thermostat can not be connected as above steps, please try this AP mode connection process.
On the thermostat
On the App
Programmable Schedule Setting
When thermostat runs in programmable mode, click the “schedule setting” to switch to the schedule page, where you can simply configure the weekly programmable 5+2 schedule up to 6 period each day. (Workdays=Monday~Friday, Weekend=Saturday and Sunday) Click “Complete” to save the configuration
Group Control and Info. Modify
Share Thermostat with Others
Work with 3rd party Echo Control
Click “Profile”>”Integration”>Select amazon echo/Google Home/IFTTT>”Use Now” Details
Customize Scene
Trouble Shooting | ||||
No. | If. | Then. | ||
1 | The power is on but without display. | ■ Check if the terminals between LCD panel and The relay/Power Module is loosened. | ||
2 | Without output but display works. | ■ Use a new LCD panel or new Relay/Power Module for Replacement | ||
3 | Room Temp. on display is not correct | ■ Do temperature calibration in parameter in ISU | ||
4 | Heating system does not respond | ■ Set the mode to heating by pressing the M button. ■ Make sure the temperature is set above the room temperature. ■ Make sure “heat on” icon shows on the display. ■ Wait 5 minutes for the system to respond. | ||
5 | The M or Increase/Decrease button doesn’t work | Make sure keypad is unlocked. Check that thermostat is on. |
DOWNLOAD MANUALS:
hotowell HTW-FT03 Smart Wifi Fan Coil Thermostat User Manual
hotowell HTW-FT03 Smart Wifi Fan Coil Thermostat User Manual
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…