This digital thermostats are designed for application of 3-speed fan and valves in fan coil system.
Including:
Fan speed can be selected to automatic or manual 3-speed control mode. In ventilation mode, fan only support manual speed control.
Model | Horizontal/ Vertical | Backlight/ Color Ring | Time on/off | 2-pipe/ 4-pipe | Power supply (V) | Energy Saving | Ventilation | Manual/ Automatic Fan | Remote Sensor |
HTW-51-1000 | |||||||||
-H2BB | Horizontal | Blue | Y | 2/4 | 220 | Y | Y | Y | Y |
-V2BB | Vertical | Blue | Y | 2/4 | 220 | Y | Y | Y | Y |
-H2GG | Horizontal | Green | Y | 2/4 | 220 | Y | Y | Y | Y |
-V2GG | Vertical | Green | Y | 2/4 | 220 | Y | Y | Y | Y |
-H1BB | Horizontal | Blue | Y | 2/4 | 110 | Y | Y | Y | Y |
-V1BB | Vertical | Blue | Y | 2/4 | 110 | Y | Y | Y | Y |
-H1GG | Horizontal | Green | Y | 2/4 | 110 | Y | Y | Y | Y |
-V1GG | Vertical | Green | Y | 2/4 | 110 | Y | Y | Y | Y |
Note: Horizontal models are taken as samples for display, operation and installation pictures shown in below parts.
Thermostat appearnce
Valve control
Thermostat acquires the room temperature via its integrated sensor or external temperature sensor and maintains the setpoint by delivering on/off valve control commands output.
Fan Operation
Fan can be selected as manual or automatic 3-speed operation. In Manual mode, the fan is switched to the selected speed via control output Gh, Gm, Gl. While in automatic mode, fan speed depends on the difference between room temperature and setpoint. When room temperature reaches setpoint, valve will be closed and meanwhile, fan will be closed either.
System will have a fixed deadband set in ISU between heating and cooling setpoints for Automatic Change Over (ACO) configured thermostats.While the heating and cooling set points determine the dead band.
If the difference between heating and cooling set points is less than the dead band set in ISU, then the dead band set in ISU is enforced. When adjusting the cooling set point, conflicts will be resolved by moving the heating set point out of the way of the cooling set point (heating set point=cooling set point –dead band set in ISU). When adjusting the heating setpoint, conflicts will be resolved by moving the cooling set point out of the way of the heating set point (cooling set point=heating set point +dead band set in ISU). Heating and Cooling range stops will determine the maximum heating setpoint setting and minimum cooling setpoint setting.
The last system control mode used will determine the mode in ACO when in the deadband.
Temperature display
The displayed temperature can be set to acquired room temperature or setpoint. The setting can be made during Installer Set-Up process.
Room temperature and scetornt can be displayed simultaneously.
Cycle per hour (CPH)
In order to get a more accurate temperature control, CPH function may enable the thermostat to open the valve for several times per hour even the temperature is close to setpoint (difference less than ½ P-band). The default value is 4 for heating and 3 for cooling and can be changed in Installer Set-Up process.
Time on/off
If the thermostat is off, hold power button for 3 seconds, system will be time on mode. If the thermostat is on, hold power button for 3 seconds, system will be time off mode.
The setting range is from 0 to 12 hours. The step is 0.5 hour with the default time is 0.
Backlight
Any key press will activate the backlight. Backlights will timeout 8 seconds after last key press. When in Installer Set-up and Installer test mode, the backlight will timeout 60 seconds after last key press.
Remote temperature sensor
It provides control either depending on the acquired room temperature or depends on the return air temperature. The model of remote temperature sensor is (NTC20K).
Keypad lock
Keypad lock can be set in ISU with default status is all keys available. You may change into mode button locked out, Fan and mode buttons locked out and All buttons locked out by changing the ISU.
Operating modes
The following operating modes are available:
Comfort mode
In comfort mode, the setpoint can be changed by pressing up and down button. Different applications include cool only, heat only and manual heat/cool changeover.
Ventilation mode
Press mode button to enter ventilation mode. In ventilation mode, no output for valve while the fan will operate according to selected fan speed.
Energy saving mode
A potential-free dry contact (such as hotel key card) or button press (pressing mode button for continuous 3 seconds) can activate the energy saving mode with icon appearing on screen. The dry contact can be selected as normal open or normal close type in ISU.
If activated by dry contact, all buttons will be locked except the multi-key for ISU. If energy saving is activated by button press, then any following button press will stop energy saving mode.
For heating mode, if the energy saving function is enabled, the setpoint will change to remote setback heating setpoint. The range of remote setback heating setpoint is from 10oC to 21oC and default value is 18oC. The value may change in ISU with step of 0.5oC.
For cooling mode, if the energy saving function is enabled, the setpoint will change to remote setback cooling setpoint. The range of remote setback cooling setpoint is from 22oC to 32oC and default value is 26oC. The value may change in ISU with step of 0.5oC.
Freezing protection mode
Freezing protection can be selected as disabled (default) or enabled. In freezing protection mode (no such mode in cool only application), when thermostat is in OFF mode while the acquired temperature is below 6oC, the thermostat will start heat mode until the temperature rises to 8oC or the thermostat is turned on.
On/off mode
Pressing power button can switch between on and off mode.
Item | Terminal | Description |
1 | Cc | Cooling close |
2 | Y | Cooling open |
3 | L | AC Power |
4 | Ch/Cc | Heating close/Cooling close |
5 | W/Y | Heating open/Cooling open |
6 | N | AC Ground |
7 | Gh | High speed fan relay |
8 | Gm | Medium speed fan relay |
9 | Gl | Low speed fan relay |
10 | Sc | Ground for remote sensor and remote setback |
11 | RSB | Remote set back |
12 | Rs | Remote sensor |
Application 1: 2 pipes heat only wiring diagram
Application 2: 2 pipes Cool only wiring diagram
Application 3: 2 pipes 1 stage Heat or 1 stage Cool MCO wiring diagram
Application 4: 4 pipes 1stage Heat and 1 stage Cool MCO/ACO wiring diagram
Install the thermostat about 5 feet (1.5m) above the floor in an area with good air circulation at average temperature.
Do not install in locations where the thermostat can be affected by:
After completing the installer setup above, press the button again to begin a system test Follow the procedure below to test the heating and cooling and fan system.
System Test System Status
Press
Number | Description | Possible Options |
1 |
System type | 0 Heat only |
1 Cool only | ||
2 two pipes 1H1C manual (Default) | ||
4 four pipes manual | ||
5 four pipes auto | ||
5 | Remote sensor | 0 Onboard Sensor (Default) |
1 Remote (NTC20K) | ||
9 | Temperature scale | 0 ºF |
1 ºC(Default) | ||
10 |
Fan control type | 0 Cycle only |
1 Constant only (3 speed: Low->Med->High-> Low) | ||
2 User can choose Cycle or Constant (3 speed: Low->Med->High->Auto-> Low) (Default) | ||
12 |
Sequence Dead band for four pipes | 1 ºC (2 ºF) |
1.5 ºC (3 ºF)(Default) | ||
2 ºC (4 ºF) | ||
3 ºC (5 ºF) | ||
3.5 ºC (6 ºF) | ||
4 ºC (7 ºF) | ||
4.5 ºC (8 ºF) | ||
5 ºC (9 ºF) | ||
13 |
CPH value For Heat | 1 |
2 | ||
3 | ||
4 (default) | ||
5 | ||
6 | ||
7 | ||
8 | ||
9 | ||
10 | ||
11 | ||
12 | ||
14 |
CPH value For Cool | 1 |
2 | ||
3(default) | ||
4 | ||
5 | ||
6 | ||
18 |
Display Temperature adjustment | -2 ºC(-4 ºF) |
-1.5 ºC(-3 ºF) | ||
-1 ºC(-2 ºF) | ||
-0.5 ºC(-1 ºF) | ||
0 ºC(0 ºF) (default) | ||
0.5 ºC(1 ºF) | ||
1 ºC(2 ºF) | ||
1.5 ºC(3 ºF) | ||
2 ºC(4 ºF) | ||
19 | Temperature Display mode | 0 display Room Temperature |
1 display Setpoint | ||
2 display both (default) | ||
20 | Heating Range Stops | 10-32 ºC default 32 ºC (50-90 ºF default 90 ºF) |
21 | Cooling Range Stops | 10-32 ºC default 10 ºC (50-90 ºF default 50 ºF) |
22 |
Keypad Lockout | 0 All keys available(default) |
1 System button Locked out | ||
2 Fan and System button Locked out | ||
3 All buttons locked out | ||
23 | Remote setback enable method | 0 Hotel card NO |
1 Hotel Card NC | ||
2 Button (Default) | ||
24 | Remote setback heating setpoint | Range 10-21ºC Default : 18 ºC (Range 50-70ºF Default : 64) |
25 | Remote setback cooling setpoint | Range 22-32ºC Default : 26 ºC (Range 72-90 ºF Default : 79 ºF) |
27 | Freeze Protection | 0 Disabled (default) |
1 Enabled |
If… | Then… |
Heating system does not turn on. | ♦ Set the mode to Heat by pressing the Mode button. ♦ Check that the heat temperature setting is set above the room temperature and “Heat On” shows solidly in the display. ♦ Wait five minutes for the heating system to respond. |
Cooling system does not turn on. | ♦ Set the mode to Cool by pressing the Mode button. ♦ Check that the cool temperature setting is set below the room temperature and “Cool On” shows solidly in the display. ♦ Wait five minutes for the cooling system to respond. |
The fan doesn’t work. | ♦ Check whether the Fan mode is set to Auto ♦ Check whether the heating or cooling system works. |
The Mode button doesn’t work. | ♦ Check whether the keypad is locked or not. ♦ Check whether the system is working in Energy saving mode. ♦ Check whether the thermostat is off. |
The Fan button doesn’t work. | ♦ Check whether the keypad is locked or not. ♦ Check whether the system is working in Energy saving mode. ♦ Check whether the thermostat is off. |
The Up or Down button doesn’t work. | ♦ Check whether the keypad is locked or not. ♦ Check whether the system is working in Energy saving mode. ♦ Check whether the thermostat is off. |
DOWNLOAD MANUALS:
hotowell HTW-51-T6861 DIGITAL Thermostat Product Specification Guide
hotowell HTW-51-T6861 DIGITAL Thermostat Product Specification Guide
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…