This kind of digital thermostat, applying the most advanced and international standardized microcomputer control chip, measures the indoor temperature by the in-built NTC high-precision sensor. It can always compare with the setting temperature, and automatically regulate the heating/cooling air input or switch on/off the motorized valve, so as to keep the room at a certain temperature
A: Control the fan coil and motorized valve synchronously (The fan stops as the motorized stops when the temperature reaches the set value.)
B: Control the fan coil and motorized valve. Asynchronously (the fan goes on working as the motorized valve stops when the temperature reaches the set value.)
T: Have clock or timing power ON/OFF function.
Y: Have a remote control function, if it is blank, it means thermostats do not have this function.
L: Have a backlight function, if it is blank, it means thermostats do not have this function.
K: Key-Card occupied/unoccupied detecting input.
N: RS485 ModBus communication.
M: Modulating signal output(0-10V/2-10v/4-20mA optional)
Button
Lock/Unlock keyboard: Long press+, – simultaneously 10s to lock/unlock buttons.
If you press the button [wind speed], it is respectively automatic wind, automatic wind, high-speed wind, medium-speed wind, and low-speed wind, medium-speed wind, and low-speed wind in turn.
Parameter Setupadjust the wind speed
During the Turn-Off status, simultaneously press the “M” and “+” buttons for 10 seconds to access ISU(Installer Set-Up) setting, until the screen showing appears “01”, which is menu No.1. Each presses the M button to switch to next menu.
Installation Dimension Figure
Wiring Diagram (more customized solutions are available)
Please follow the instructions to make the correct installation.
Step 1: Open the control board, Use a 3.5mm wide screwdriver along the bevel into the slot for 4mm.
Step 2: Slightly upwardly prize it to open the hook.
Malfunction | Disposal |
Boot-strap error | Check L.N power and the wiring connection Check the power ON/OFF button Change the control board, or change the power supply board Check the connection of wiring between the control board and the power supply board |
LCD garbled | The back shell may be deformed during the installation loose the two fixation board |
No output with right display | Power control panels and connecting cable may be damaged Change the control board and then change the power plate |
Remote failure | Check whether there is a remote battery power Change the remote |
Temperature display abnormal | The temperature hasn’t been calibrated. |
Cautions
The warranty service is 18 months from the date of purchase. The products of our company may enjoy life-long in accordance with the regulation. Our company will make a certain change to the service out of the warranty period or product quality. Hotowell International Co., Limited |info@hotowell.com| +86-592-3327332 | Building 7, Guanyinshan International Business Center, Xiamen 361000, China
DOWNLOAD MANUALS:
hotowell HTW-31-F17 Digital Thermostat Product Specification Guide
hotowell HTW-31-F17 Digital Thermostat Product Specification Guide
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…