Thermostats
This manual covers the following models
System Types
Must be installed by a trained, experienced technician
Read these instructions carefully. Failure to follow these instructions can damage the product or cause a hazardous condition.
Need Help?
For assistance with this product please visit http://customer.honeywell.com or call Honeywell Customer Care toll-free at 1-800-468-1502
Remove the wallplate from the thermostat as shown on the left, then follow the directions below for mounting.
CAUTION: ELECTRICAL HAZARD
Can cause electrical shock or equipment damage. Disconnect power before beginning the installation
MERCURY NOTICE
If this product is replacing a control that contains mercury in a sealed tube, do not place the old control in the trash. Contact the Thermostat Recycling Corporation at www.thermostat-recycle.org or 800-238-8192 for information on how and where to properly and safely dispose of your old thermostat
Terminal designations
Wiring guide — conventional and heat pump systems
NOTES
Wire specifications:
Use 18- to 22-gauge thermostat wire. A shielded cable is not required.
TH2110DV/TH1110DV only:
Thermostat mounting
Align the thermostat with the tabs on the wallplate, then push gently until the thermostat snaps in place
Follow the procedure below to configure the thermostat to match the installed heating/cooling system, and customize feature operation as desired.
To begin, press and hold the
NOTE: If you do not press any button for 60 seconds while you are in the setup menu, the thermostat automatically saves any changes made and exits the menu.
NOTE: The options below may not be available in all models.
Setup function Settings & options (factory default in bold) | |||
5 | Heating cycle rate | 5 | For gas or oil furnaces of less than 90% efficiency |
(CPH: cycles/hour) | 1 | For steam or gravity systems | |
TH2110DV, TH1110DV and | 3 | For hot water systems & furnaces of over 90% efficiency | |
TH1100DV | 6 | For electric furnaces | |
[Other cycle rate options: 2 or 4 CPH] | |||
6 | Auxiliary heat | 3 | For hot water systems & furnaces of over 90% |
cycle rate (CPH) | efficiency | ||
TH2210DV and TH1210DV | 1 | For steam or gravity systems | |
5 | For gas or oil furnaces of less than 90% efficiency | ||
6 | For electric furnaces | ||
[Other cycle rate options: 2 or 4 CPH] | |||
9 | Compressor | 3 | Recommended for most compressors |
cycle rate (CPH) | [Other cycle rate options: 1, 2, 4, 5, or 6 CPH] | ||
13 | Early Start (TH2110DV | 1 | On **See page 8 |
and TH2210DV) | 0 | Off | |
14 | Temperature | 0 | Fahrenheit |
display | 1 | Celsius | |
15 | Compressor | 1 | Five-minute compressor off time (See page 8) |
protection | 0 | No compressor off time | |
20 | Clock display (TH2110DV | 0 | 12-hour display |
and TH2210DV) | 1 | 24-hour display | |
25 | Lower temperature | 0 | Standard range 40°F to 90°F (4.5°C to 32°C) |
range (TH1100DV only) | 1 | Lower range (for garage mode) 35°F to 90°F | |
(1.5°C to 32°C) | |||
40 | Restore program | 0 | Off |
schedule to default | 1 | On – program schedule default settings are listed in the | |
(TH2110DV and | operating manual | ||
TH2210DV) |
CAUTION: EQUIPMENT DAMAGE HAZARD
Compressor protection is bypassed during testing. To prevent equipment damage, avoid cycling the compressor quickly.
Special functions
Early Start (Setup Function 13): Early start allows the heating or cooling to turn on before the program start time, so the temperature is reached at the time you set. Compressor Protection (Setup Function 15): Forces the compressor to wait a few minutes before restarting, to prevent damage. During the wait time, the message Cool On or Heat On (heat pumps only) will flash on the display
Accessories & replacement parts
Please contact your distributor to order replacement parts.
Cover plate assembly*………………………………….. Part Number 50002883-001
Use to cover marks left by old thermostats.
Temperature Ranges
Heat: 40° to 90°F (4.5° to 32°C)
Cool: 50° to 99°F (10° to 37°C)
Operating Ambient Temperature
32° to 120°F (0° to 48.9°C)
Shipping Temperature
-20° to 120°F (-28.9° to 48.9°C)
Operating Relative Humidity
5% to 90% (non-condensing)
Physical Dimensions
3-7/16”H x 4-10/16”W x 1-3/16”D
87mm H x 119mm W x 30mm D
Heat (1st stage) | 20-30 Vac | 0.02-1.0 A |
(Powerpile) | 750 mV DC | 100 mA DC |
Auxiliary heat | 20-30 Vac | 0.02-1.0 A |
Cooling | 20-30 Vac | 0.02-1.0 A |
Automation and Control Solutions
Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
http://customer.honeywell.com
® U.S. Registered Trademark
© 2013 Honeywell International Inc.
69-2800EFS—01 M.S. 05-13
Printed in the U.S.A.
Download Manual:
Honeywell TH2000DV Series Programmable Thermostat Installation Guide
Honeywell TH2000DV Series Programmable Thermostat Installation Guide
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…