Honeywell TH2000DV Series Programmable Thermostat
Thermostats
This manual covers the following models
- TH1100DV: For Heat only systems
- TH2110DV/TH1110DV: For 1 Heat/1 Cool systems
- TH2210DV/TH1210DV: For 2 Heat/1 Cool heat pump systems only (Pull thermostat from wallplate and turn over to find the model number.)
System Types
- Gas, oil, or electric heat with air conditioning
- Warm air, hot water, high-efficiency furnaces, 1 Heat/1 Cool heat pumps, steam, gravity
- Heat only
- Heat only with a fan
- Cool only
- 750 mV heating systems
- 2 Heat/1 Cool heat pumps
- Gas, oil, or electric heat
- Warm air, hot water, steam, gravity
- Heat only
- 750 mV heating systems
Must be installed by a trained, experienced technician
Read these instructions carefully. Failure to follow these instructions can damage the product or cause a hazardous condition.
Need Help?
For assistance with this product please visit http://customer.honeywell.com or call Honeywell Customer Care toll-free at 1-800-468-1502
Wallplate installation
Remove the wallplate from the thermostat as shown on the left, then follow the directions below for mounting.
- Pull wires through the wire hole.
- Position the wallplate on the wall, level, and mark hole positions with a pencil.
- Drill holes at marked positions as shown below, then tap in supplied wall anchors.
- Place wallplate over anchors, insert and tighten mounting screws
CAUTION: ELECTRICAL HAZARD
Can cause electrical shock or equipment damage. Disconnect power before beginning the installation
MERCURY NOTICE
If this product is replacing a control that contains mercury in a sealed tube, do not place the old control in the trash. Contact the Thermostat Recycling Corporation at www.thermostat-recycle.org or 800-238-8192 for information on how and where to properly and safely dispose of your old thermostat
Power options
Wiring
Terminal designations
Wiring guide — conventional and heat pump systems
NOTES
Wire specifications:
Use 18- to 22-gauge thermostat wire. A shielded cable is not required.
- Power supply. Provide disconnect means and overload protection as required.
- Remove jumper for 2-transformer systems.
- Optional 24 Vac common connection.
- The common connection must come from the cooling transformer.
- Use either O or B terminals for the changeover valve.
- Use a small piece of wire (not supplied) to connect W and Y terminals.
- Set the fan operation switch to Heat Pump (see page 5).
Fan operation settings
TH2110DV/TH1110DV only:
- Gas or Oil: For gas or oil heating systems, leave the fan operation switch in this factory-set position. (This setting is for systems that control the fan in a call for heat.)
- Electric or Heat Pump: Change the switch to this setting for heat pumps or electric heat systems. (This setting is for systems that allow the thermostat to control the fan in a call for heat if a fan wire is connected to the G terminal.)
Thermostat mounting
Align the thermostat with the tabs on the wallplate, then push gently until the thermostat snaps in place
Installer setup
Follow the procedure below to configure the thermostat to match the installed heating/cooling system, and customize feature operation as desired.
To begin, press and hold the andbuttons until the display changes
- Press the or button to change the setting.
- Press the andbuttons simultaneously for one second to advance to the next function.
- Press and hold the and buttons to exit and save settings
NOTE: If you do not press any button for 60 seconds while you are in the setup menu, the thermostat automatically saves any changes made and exits the menu.
NOTE: The options below may not be available in all models.
Setup function Settings & options (factory default in bold) | |||
5 | Heating cycle rate | 5 | For gas or oil furnaces of less than 90% efficiency |
(CPH: cycles/hour) | 1 | For steam or gravity systems | |
TH2110DV, TH1110DV and | 3 | For hot water systems & furnaces of over 90% efficiency | |
TH1100DV | 6 | For electric furnaces | |
[Other cycle rate options: 2 or 4 CPH] | |||
6 | Auxiliary heat | 3 | For hot water systems & furnaces of over 90% |
cycle rate (CPH) | efficiency | ||
TH2210DV and TH1210DV | 1 | For steam or gravity systems | |
5 | For gas or oil furnaces of less than 90% efficiency | ||
6 | For electric furnaces | ||
[Other cycle rate options: 2 or 4 CPH] | |||
9 | Compressor | 3 | Recommended for most compressors |
cycle rate (CPH) | [Other cycle rate options: 1, 2, 4, 5, or 6 CPH] | ||
13 | Early Start (TH2110DV | 1 | On **See page 8 |
and TH2210DV) | 0 | Off | |
14 | Temperature | 0 | Fahrenheit |
display | 1 | Celsius | |
15 | Compressor | 1 | Five-minute compressor off time (See page 8) |
protection | 0 | No compressor off time | |
20 | Clock display (TH2110DV | 0 | 12-hour display |
and TH2210DV) | 1 | 24-hour display | |
25 | Lower temperature | 0 | Standard range 40°F to 90°F (4.5°C to 32°C) |
range (TH1100DV only) | 1 | Lower range (for garage mode) 35°F to 90°F | |
(1.5°C to 32°C) | |||
40 | Restore program | 0 | Off |
schedule to default | 1 | On – program schedule default settings are listed in the | |
(TH2110DV and | operating manual | ||
TH2210DV) |
CAUTION: EQUIPMENT DAMAGE HAZARD
Compressor protection is bypassed during testing. To prevent equipment damage, avoid cycling the compressor quickly.
Special functions
Early Start (Setup Function 13): Early start allows the heating or cooling to turn on before the program start time, so the temperature is reached at the time you set. Compressor Protection (Setup Function 15): Forces the compressor to wait a few minutes before restarting, to prevent damage. During the wait time, the message Cool On or Heat On (heat pumps only) will flash on the display
Accessories & replacement parts
Please contact your distributor to order replacement parts.
Cover plate assembly*………………………………….. Part Number 50002883-001
Use to cover marks left by old thermostats.
Specifications
Temperature Ranges
Heat: 40° to 90°F (4.5° to 32°C)
Cool: 50° to 99°F (10° to 37°C)
Operating Ambient Temperature
32° to 120°F (0° to 48.9°C)
Shipping Temperature
-20° to 120°F (-28.9° to 48.9°C)
Operating Relative Humidity
5% to 90% (non-condensing)
Physical Dimensions
3-7/16”H x 4-10/16”W x 1-3/16”D
87mm H x 119mm W x 30mm D
Electrical Ratings
Heat (1st stage) | 20-30 Vac | 0.02-1.0 A |
(Powerpile) | 750 mV DC | 100 mA DC |
Auxiliary heat | 20-30 Vac | 0.02-1.0 A |
Cooling | 20-30 Vac | 0.02-1.0 A |
Automation and Control Solutions
Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
http://customer.honeywell.com