Honeywell-TH2000DV-Series-Programmable-Thermostat-FEATURED

Honeywell TH2000DV Series Programmable Thermostat Installation Guide

Honeywell-logo

Honeywell TH2000DV Series Programmable Thermostat 

Honeywell-TH2000DV-Series-Programmable-Thermostat-FIG-11

Thermostats
This manual covers the following models

  • TH1100DV: For Heat only systems
  • TH2110DV/TH1110DV: For 1 Heat/1 Cool systems
  • TH2210DV/TH1210DV: For 2 Heat/1 Cool heat pump systems only (Pull thermostat from wallplate and turn over to find the model number.)

System Types

  • Gas, oil, or electric heat with air conditioning
  • Warm air, hot water, high-efficiency furnaces, 1 Heat/1 Cool heat pumps, steam, gravity
  • Heat only
  • Heat only with a fan
  • Cool only
  • 750 mV heating systems
  • 2 Heat/1 Cool heat pumps
  • Gas, oil, or electric heat
  • Warm air, hot water, steam, gravity
  • Heat only
  • 750 mV heating systems

Must be installed by a trained, experienced technician
Read these instructions carefully. Failure to follow these instructions can damage the product or cause a hazardous condition.

Need Help?
For assistance with this product please visit http://customer.honeywell.com or call Honeywell Customer Care toll-free at 1-800-468-1502

Wallplate installation

Honeywell-TH2000DV-Series-Programmable-Thermostat-FIG-1

Remove the wallplate from the thermostat as shown on the left, then follow the directions below for mounting.

Honeywell-TH2000DV-Series-Programmable-Thermostat-FIG-2

  1. Pull wires through the wire hole.
  2.  Position the wallplate on the wall, level, and mark hole positions with a pencil.
  3.  Drill holes at marked positions as shown below, then tap in supplied wall anchors.
  4.  Place wallplate over anchors, insert and tighten mounting screws

CAUTION: ELECTRICAL HAZARD
Can cause electrical shock or equipment damage. Disconnect power before beginning the installation

MERCURY NOTICE
If this product is replacing a control that contains mercury in a sealed tube, do not place the old control in the trash. Contact the Thermostat Recycling Corporation at www.thermostat-recycle.org or 800-238-8192 for information on how and where to properly and safely dispose of your old thermostat

Power options

Honeywell-TH2000DV-Series-Programmable-Thermostat-FIG-3

Wiring

Terminal designations

Honeywell-TH2000DV-Series-Programmable-Thermostat-FIG-4

Wiring guide — conventional and heat pump systems

Honeywell-TH2000DV-Series-Programmable-Thermostat-FIG-5

NOTES
Wire specifications:
Use 18- to 22-gauge thermostat wire. A shielded cable is not required.

  1. Power supply. Provide disconnect means and overload protection as required.
  2.  Remove jumper for 2-transformer systems.
  3. Optional 24 Vac common connection.
  4. The common connection must come from the cooling transformer.
  5.  Use either O or B terminals for the changeover valve.
  6. Use a small piece of wire (not supplied) to connect W and Y terminals.
  7.  Set the fan operation switch to Heat Pump (see page 5).

Fan operation settings

Honeywell-TH2000DV-Series-Programmable-Thermostat-FIG-6

TH2110DV/TH1110DV only:

  • Gas or Oil: For gas or oil heating systems, leave the fan operation switch in this factory-set position. (This setting is for systems that control the fan in a call for heat.)
  • Electric or Heat Pump: Change the switch to this setting for heat pumps or electric heat systems. (This setting is for systems that allow the thermostat to control the fan in a call for heat if a fan wire is connected to the G terminal.)

Thermostat mounting

Honeywell-TH2000DV-Series-Programmable-Thermostat-FIG-7
Align the thermostat with the tabs on the wallplate, then push gently until the thermostat snaps in place

Installer setup

Honeywell-TH2000DV-Series-Programmable-Thermostat-FIG-8

Follow the procedure below to configure the thermostat to match the installed heating/cooling system, and customize feature operation as desired.
To begin, press and hold the Honeywell-TH2000DV-Series-Programmable-Thermostat-FIG-9 andHoneywell-TH2000DV-Series-Programmable-Thermostat-FIG-9buttons until the display changes

  • Press the Honeywell-TH2000DV-Series-Programmable-Thermostat-FIG-9or Honeywell-TH2000DV-Series-Programmable-Thermostat-FIG-9 button to change the setting.
  • Press the Honeywell-TH2000DV-Series-Programmable-Thermostat-FIG-9 andHoneywell-TH2000DV-Series-Programmable-Thermostat-FIG-9buttons simultaneously for one second to advance to the next function.
  • Press and hold the Honeywell-TH2000DV-Series-Programmable-Thermostat-FIG-9 and Honeywell-TH2000DV-Series-Programmable-Thermostat-FIG-9 buttons to exit and save settings

NOTE: If you do not press any button for 60 seconds while you are in the setup menu, the thermostat automatically saves any changes made and exits the menu.

NOTE: The options below may not be available in all models.

Setup function                 Settings & options (factory default in bold)
5 Heating cycle rate 5 For gas or oil furnaces of less than 90% efficiency
(CPH: cycles/hour) 1 For steam or gravity systems
TH2110DV, TH1110DV and 3 For hot water systems & furnaces of over 90% efficiency
TH1100DV 6 For electric furnaces
[Other cycle rate options: 2 or 4 CPH]
6 Auxiliary heat 3 For hot water systems & furnaces of over 90%
cycle rate (CPH) efficiency
TH2210DV and TH1210DV 1 For steam or gravity systems
5 For gas or oil furnaces of less than 90% efficiency
6 For electric furnaces
[Other cycle rate options: 2 or 4 CPH]
9 Compressor 3 Recommended for most compressors
cycle rate (CPH) [Other cycle rate options: 1, 2, 4, 5, or 6 CPH]
13 Early Start (TH2110DV 1 On **See page 8
and TH2210DV) 0 Off
14 Temperature 0 Fahrenheit
display 1 Celsius
15 Compressor 1 Five-minute compressor off time (See page 8)
protection 0 No compressor off time
20 Clock display (TH2110DV 0 12-hour display
and TH2210DV) 1 24-hour display
25 Lower temperature 0 Standard range 40°F to 90°F (4.5°C to 32°C)
range (TH1100DV only) 1 Lower range (for garage mode) 35°F to 90°F
(1.5°C to 32°C)
40 Restore program 0 Off
schedule to default 1 On – program schedule default settings are listed in the
(TH2110DV and operating manual
TH2210DV)

CAUTION: EQUIPMENT DAMAGE HAZARD
Compressor protection is bypassed during testing. To prevent equipment damage, avoid cycling the compressor quickly.

Special functions
Early Start (Setup Function 13): Early start allows the heating or cooling to turn on before the program start time, so the temperature is reached at the time you set. Compressor Protection (Setup Function 15): Forces the compressor to wait a few minutes before restarting, to prevent damage. During the wait time, the message Cool On or Heat On (heat pumps only) will flash on the display

Accessories & replacement parts
Please contact your distributor to order replacement parts.
Cover plate assembly*………………………………….. Part Number 50002883-001
Use to cover marks left by old thermostats.

Specifications

Temperature Ranges
Heat: 40° to 90°F (4.5° to 32°C)
Cool: 50° to 99°F (10° to 37°C)

Operating Ambient Temperature
32° to 120°F (0° to 48.9°C)

Shipping Temperature
-20° to 120°F (-28.9° to 48.9°C)

Operating Relative Humidity
5% to 90% (non-condensing)

Physical Dimensions
3-7/16”H x 4-10/16”W x 1-3/16”D
87mm H x 119mm W x 30mm D

Electrical Ratings

Heat (1st stage) 20-30 Vac 0.02-1.0 A
(Powerpile) 750 mV DC 100 mA DC
Auxiliary heat 20-30 Vac 0.02-1.0 A
Cooling 20-30 Vac 0.02-1.0 A

Automation and Control Solutions
Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
http://customer.honeywell.com
® U.S. Registered Trademark
© 2013 Honeywell International Inc.
69-2800EFS—01 M.S. 05-13