Thermostat Buttons and Switches
The Display
ATTACH THERMOSTAT BASE TO WALL
WARNING: ELECTRICAL SHOCK HAZARD
Turn off power at the main service panel by removing the fuse or switching the appropriate circuit breaker to the OFF position before removing the existing thermostat.
485 Communication Function Instruction
When the 485 communication distance is more than 300m, need to increase terminal resistance in 485 the beginning of the communication terminal and end Especially, if the communication equipment quantity is less in the trunk(less than 22pcs). When increasing terminal resistance, only short circuit the terminal resistance jumper J5 of the thermostat.
Remote Control Optional
The configuration menu allows you to set certain thermostat operating characteristics to your system or personal requirements. S witch off the thermostat, long press button ② over 4 seconds till power on again means you have entered the first configuration menu item There are 6 menu items. Press button ② to change to the next item and press button ④ or ⑤ to select.
In implicit parameter menu mode, long press button ⑥ for 3 seconds, all parameters will back to the initial value.
Step | Press buttons | Displayed(factory default) | Press▲、▼to select | Descriptions |
1 | ② 4 seconds | (0) | -4—+4 | Adjust temperature coefficient |
2 | ② | (35℃) | 20℃—50℃ | Select the maximum setting temperature for heating |
3 | ② | (5℃) | 5℃—20℃ | Select the minimum setting temperature for cooling |
4 | ② | (℃) | ℃/℉ | Temperature unit option |
5 | ② | (2) | 1、2、3 | Display backlight option |
6 | ② | (rd) | rd, rE | Memorize option before power loss |
7 | ② | (On) | OFF/On | Fan stop option |
8 | ② | (4) | 4/2 | Control system option |
9 | ② | (1) | 1–255 | Communication address |
10 | ② | (18℃) | 10—18℃ | Heating mode without a room card temperature |
11 | ② | (25℃) | 25—30°C | Cooling mode without a room card temperature |
12 | ② | (SC) | SC/OC/00 | Activate Room Card function mode option |
Timer switch on/off function and rela y delay protection function
In switch off state, long press button f or 3 seconds, will enter into set the automatically switch on time, press button ④ or ⑤ to set the time, the time value will raise or low er 0.5 ; In switch on state, long press button for 3 seconds, will enter into set t he automatically switches off time, similarly press the raise button or lower button to set the time value.
In timer switch on/off mode, the setting value is the countdown value. For example: when you set the time val ue is 3.5 in switch on state, your thermostat will switch off automatically after three and a half hours. If the time value is 0, means you have closed the timer switch on/off function. In switch on state, if you have open the timer switch off function, th e LCD will display the timer mark and the remaining time. The thermostat also have relay delay protection, remote control, and 485 communication function.
Response frame: Command returns when all is done correctly; No response when the operation is wrong, PC will handle it; subsequent sets follow this answer/respond rule
DOWNLOAD MANUALS:
Hexa CONTROL RT226-F4 FAN COIL THERMOSTAT Installation and operation instructions
Hexa CONTROL RT226-F4 FAN COIL THERMOSTAT Installation and operation instructions
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…