Heatit Z-Temp2 is a battery-operated thermostat designed for use with water-based heating systems. Used in combination with the Heatit Z-Water regulator, you can control your heating system with a Z-Wave primary controller/gateway using Heatit Z-Water in combination with one or several Heatit Z-Temp2.
Please read this before the installation
This device may be used with all devices certified with the Z-Wave Plus™ certificate and should be compatible with such devices produced by any manufacturer. Every primary controller is different depending on the manufacturer, their target audience, and their intended use/application. Please review the functionalities implemented by the primary controller, you intend to use with our Z-Wave Plus certified device to ensure that it provides the necessary controls to take full advantage of our product’s capabilities.
This device may be operated within any Z-Wave network with Z-Wave-certified devices from other manufacturers. All non-battery-operated nodes within the network will act as repeaters regardless of the manufacturer to increase the reliability of the network. On delivery, the device does not belong to any Z-Wave network.
The device needs to be added to an existing network to communicate with the other devices within it. Devices may also be removed from a network. The add/remove processes are initiated by the primary controller of the Z-Wave network.
Use a large flathead screwdriver to remove the back cover.
Fix the unit to the wall with double-sided tape, and screws or installed it on top of a Euro wall box.
Make sure the mounting surface is clean and dry.
Then install 3x AA batteries (alkaline) in the device’s battery holder.
NB! Be careful when installing batteries, ensuring the polarity of the batteries is in accordance with the printing in plastic.
There are two ways to add your devices in a Z-Wave network.
Please refer to your primary controller/gateway manual on how to enter add/remove mode. The device can only be added or removed from the network if the primary controller is in add/remove mode.
When the primary controller/gateway is set to add/remove mode, press the link button on the thermostat three times in a rapid sequence.
Please refer to your primary controller/gateway to see if the controller supports SmartStart. SmartStart-enabled products can be added to a Z-Wave network by scanning the Z-Wave QR-Code present on the product with a controller providing SmartStart inclusion. No further action is required, and the SmartStart product will be added automatically within 10 minutes of being switched on in the network vicinity.
Enter SmartStart modus from your primary controller.
With the batteries for the devices removed from the device, scan the QR code on the back of the device, then follow the gateway instructions.
If the device already belongs to a network, follow the removal process before adding it to your network. Otherwise, adding this device will fail. When the device is removed from the network,
the device will revert to factory settings.
By pressing and holding the link button for 20 seconds, the thermostat will perform a complete factory reset. rES will be displayed.
NB! Please use this procedure only when the primary controller/
gateway is missing or otherwise inoperable.
The thermostat uses temperature readings retrieved from the internal sensor. Heat it Z-Temp2 is designed to work in combination with water-based heating solutions. Heatit recommends using Heatit Z-Temp2 in combination with Heatit Z-Water. These two products allow for an advanced water-based heating solution by using a Z-Wave-enabled controller. This is a “wire-free” solution that saves both time and money. All the communication between Heatit Z-Temp2 and the controlled device is wireless. The range can be extended using Heatit Z-Repeater or any other device that supports routing. This makes our water-based solutions an excellent addition to your existing or new home automation system.
Electrical heating
Heatit Z-Temp2 could also be used in situations where a traditional electrical thermostat is not suited. The battery-operated thermostat can be used in combination with Heatit Z-Relay or any other relay device installed in a remote location. Rehabilitation could be done using this solution to avoid unnecessary wiring.
The thermostat benefits from two screens.
You can make changes to the hysteresis in the thermostat via the parameter. This means that you can change the hysteresis from 0.3°C up to max of 3.0°C. The default is 0.5°C.
By pressing the Left and Right (down and up buttons for 10 seconds, the thermostat will display LOC. The child lock is now activated, and the lock icon will be lit up when the display is active. Trying to make changes to the display is not possible within this modus. Changes to the Z-Wave controller are still possible. Refer to your primary controller/gateways user manual on how to change the setpoint.
Child lock is deactivated by pressing the Left and Right (down and up) buttons for 10 seconds, the thermostat will display oPn. The lock symbol is no longer lit when the display is active, and now you can make changes using buttons.
The thermostat can invert its signal sent to external relays. This allows users to use the Heatit Z-TEMP2 in combination with other systems. You can change this behavior using a quick feature in the thermostat or, using Parameter 15 “Inverted Output”.
Changing the behavior,
When the thermostat remains untouched for a while, it will
automatically go to the standby screen. Due to power saving settings, while in standby, the display will be turned off. The proximity sensor will activate the thermostat when proximity is sensed. You can also activate the thermostat manually by pressing any button.
The QR Code is needed when using S2-Security or SmartStart. The Z-Wave DSK can be found in the QR-Code and is located;
The S2 security enhances Z-Wave Plus with an additional layer of AES 128-bit encryption of the wireless Z-Wave communication to prevent hacking and man-in-middle attacks on the home network. The Heatit Z-Temp2 supports S2 and has a Z-Wave DSK QR-Code label that may be used when the module is added to the Z-Wave home network. The primary controller will ask for a 5-digit Code, which can be found underneath the QR-Code. The primary controller will then ask you to confirm the rest of the code that is contained in the QR-Code.
The node information frame is the business card of a Z-Wave device.
It contains information about the device type and its technical features. The add and remove procedure of the device is confirmed by sending out a node information frame. Besides this, it may be necessary for certain network operations to send out a node information frame.
Z-Wave devices interact with other Z-Wave devices. The relationship between one device controlling another device is called an association. In order to control a subordinate device, the controlling device needs to maintain a list of devices that will receive controlling commands. These lists are called ”Association Groups”. They are always related to the specific event triggered (e.g., sensor reports). In case the event is triggered, all devices stored in the respective association group will receive a joint wireless command.
SETTING AND REMOVING ASSOCIATIONS
Associations may be assigned and removed via Z-Wave commands.
Please refer to your primary controller/Z-Wave gateway for more information.
ROOT DEVICE | THE MAINTHERMOSTAT DEVICE |
Group 1 Lifeline | Lifeline. (Normally used by the Z-Wave Controller) Sends: – Battery Report (sent when the battery runs low). – Notification Report (sent first-time power on). – Device Reset Locally Notification (sent if the device is reset). – Indicator Report – Thermostat Mode Report (sent when mode changed from panel). – Thermostat Setpoint Report (sent when setpoint changed from panel). – Thermostat Operating State Report (sent when heating should be active). – Heating – when the external relay is turned ON, in Standard Output – Cooling – when the external relay is turned ON, in Inverted Output. |
Group 2 Temperature Report | Sensor Multilevel Report (periodical reports). Protection Report (child lock activated/deactivated from panel). Max. nodes in the group: 5 |
Group 3 ON/OFF Control | Multilevel Sensor Report (internal measured temperate and measured relative humidity). Max. nodes in the group: 5 Binary Switch Set (normally used to control external relays). Sends: 0x00 = OFF 0xFF = ON Max. nodes in the group: 5 |
Z-Wave products are supposed to work out of the box after inclusion.
Some configurations of a device can alter the functionality to better serve the user’s needs or unlock further enhanced features. All the parameters below do not feature altering capabilities or advanced or read-only flags.
NO # | PARA SIZE (BYTE) |
NAME | SHORT DESCRIPTION / COMMENT |
MIN |
MAX |
DEFAULT | DESCRIPTION OF VALUE |
1 | 2 | Temperature/ Humidity report interval | Used to adjust the time be- tween report interval for Temperature and humidity reports. | 30 | 32767 | 900 | 30 to 32 767 seconds. |
2 | 2 | Temperature delta value | Temperature reports based on change. Change must be within 1 minute. | 0 | 10, (1.0°C) | Reporting temperature based on change is disabled. | |
5 | 50 | 0.5 to 5°C Only if the change occurs within 1 minute. | |||||
3 | 2 | Humidity delta value | Humidity reports based on change. Change must be within 1 minute. | 0 | 10, (1.0°C) | Reporting humidity based on change is disabled. | |
5 | 50 | 5 to 50%. Only if a change occurs within 1 minute. | |||||
4 | 2 | Temperature offset settings | Calibrates the internal sensor. NB! To set negative values; 65 535 – desired value + 1. | -100 | 100 | 0.0°C | -100 to 100°C |
5 | 2 | Humidity offset settings | Offsets the measured relative humidity. NB! To set negative values; 65 535 – desired value + 1. | -100 | 100 | 0.0% | -10-10% |
6 | 2 | Proximity sensor retrigger interval | 2 | 270 | 10 (10 sec) | 2 to 270 seconds | |
7 | 2 | Proximity sensor Enabled / Disabled | Choose if a proximity sensor is used or not. | 0 | Enable | Disable | |
1 | Enable | ||||||
8 | 2 | LED maximum brightness | Adjust the backlight of LCD display. | 0 | 99 | 50 (50%) | 0-99% |
9 | 2 | LED turned on before the timeout | Adjust the time from the proximity sensor/display touched until the display goes to sleep. | 3 | 300 | 3 | 3 to 300 seconds |
10 | 2 | Temperature Control Hysteresis | Adjust the delta values for the thermostat to turn off the heating. | 3 | 30 | 5 (0.5°C) | 0.3 to 3°C |
11 | 2 | Minimum Temperature Limit | Set the minimum temperature limit | 50 | 400 | 50 (5°C) | 5 to 40°C |
12 | 2 | Maximum Temperature Limit | Set the maximum temperature limit | 50 | 400 | 400 (40°C) | 5 to 40°C |
13 | 2 | External Relay & Operating State update interval | Set the time of how often the devices send Binary Switch Set and their- most mode to the gateway. | 0 | Sends only when changed | Sends only when changed | |
1 | 240 | 1 to 240 minutes + When changed |
NO # | PARA SIZE (BYTE) |
NAME | SHORT DESCRIPTION / COMMENT |
MIN |
MAX |
DEFAULT | DESCRIPTION OF VALUE | |
14 | 2 | Report | Decides if the | 0 | Do not | Do not report to | ||
when | thermostat | report to | gateway when | |||||
presence is | sends temperature when | gateway | presence is | |||||
detected | when | detected, only at | ||||||
presence is | presence | interval. | ||||||
detected. | is detect- ed, only at | |||||||
1 | ||||||||
interval. | ||||||||
15 | 2 | Inverted | Decides if the | 0 | Disabled | Enabled | ||
output | relay output should be | |||||||
1 | Disabled | |||||||
inverted. |
USE CASE | SENSOR TYPE | SIZE | SCALE | PRECISION |
Sends temperature report from internal sensor | Temperature(version 1) = 0x01 | 2Byte = 0x02 | Celsius (°C) = 0x00 | 1 decimal= 0x01 |
Sends relative humidity report from internal sensor | Relative humidity (version 2) = 0x05 | 2Byte = 0x02 | Percentage value (%) =0x00 | 1 decimal= 0x01 |
Notification Command Class
When the device is turned back on after a power outage (insert fresh batteries), the device sends a notification command to indicate that the device is back in an idle state. The Device will also send a humidity report and temperature report when powered back on.
EVENT | TYPE | EVENT | LENGTH |
Power On (OxFF) | Power manegment (0x08) | Power has been applied (0x01) | 0x00 |
SUPPORTED COMMAND CLASSES
The following table lists all Command Classes supported by the Z-Wave Device. The device supports both S0 and S2 Authenticated security and S2 Unauthenticated security.
INSECURE INCLUSION | INSECURE ON SECURE INCLUSION | SECURE ON SECURE INCLUSION | |
COMMAND_CLASS_ZWAVEPLUS_INFO_V2 | Yes | Yes | Yes |
COMMAND_CLASS_ASSOCIATION_V2 | Yes | Yes | |
COMMAND_CLASS_MULTI_CHANNEL_ ASSOCIATION_V2 | Yes | Yes | |
COMMAND_CLASS_ASSOCIATION_GRP_INFO_V3 | Yes | Yes | |
COMMAND_CLASS_TRANSPORT_ SERVICE_V2 | Yes | Yes | |
COMMAND_CLASS_VERSION_V3 | Yes | Yes | |
COMMAND_CLASS_MANUFACTURER_SPECIF- IC_V2 | Yes | Yes | |
COMMAND_CLASS_DEVICE_RESET_ LOCALLY_V1 | Yes | Yes | |
COMMAND_CLASS_INDICATOR_V3 | Yes | Yes | |
COMMAND_CLASS_POWERLEVEL_V1 | Yes | Yes | |
COMMAND_CLASS_BATTERY_V1 | Yes | Yes | |
COMMAND_CLASS_SECURITY_V1 | Yes | Yes | |
COMMAND_CLASS_SECURITY_2_V1 | Yes | Yes | |
COMMAND_CLASS_NOTIFICATION_V8 | Yes | Yes | |
COMMAND_CLASS_SUPERVISION_V1 | Yes | Yes | |
COMMAND_CLASS_FIRMWARE_ UPDATE_MD_V5 | Yes | Yes | |
COMMAND_CLASS_THERMOSTAT_MODE_V3 | Yes | Yes | |
COMMAND_CLASS_THERMOSTAT_SETPOINT_V3 | Yes | Yes | |
COMMAND_CLASS_THERMOSTAT_ OPERATING_STATE_V1 | Yes | Yes | |
COMMAND_CLASS_PROTECTION_V1 | Yes | Yes | |
COMMAND_CLASS_CONFIGURATION_V4 | Yes | Yes | |
COMMAND_CLASS_SENSOR_ MULTILEVEL_V5 | Yes | Yes | |
COMMAND_CLASS_APPLICATION_ STATUS_V1 | Yes | Yes | Yes |
ART. NO. | PRODUCT | COLOR | FREQUENCY |
45 126 66 | Heatit Z-Temp2 thermostat Battery | White RAL 9003 | EU 868.4MHz |
45 126 67 | Heatit Z-Temp2 thermostat Battery | Black RAL 9011 | EU 868.4MHz |
99 306 10 | Heatit Z-Temp2 thermostat Battery | White RAL 9003 | RU 869.0MHz |
99 306 68 | Heatit Z-Temp2 thermostat Battery | White RAL 9003 | AUS 921.4MHz |
Heatit Controls AB can not be held liable for typographical errors, other errors, or omittances in our information. Product specifications may change without further notice.
All electrical installations must be carried out by a licensed electrician. The product must be installed in accordance with national building codes and our installers manual.
Heatit Controls AB l Läkarvägen 4, 454 31 BRASTAD, SWEDEN
Phone: +47 61 18 77 77
post@heatit.com
www.heatit.com
Download Manual:
Heatit 4512667 HEATIT Z-TEMP2 Thermostat Installational Manual
OTHER MANUALS:
Heatit 4512667 HEATIT Z-TEMP2 Thermostat Product Specifications Guide
Heatit 4512667 HEATIT Z-TEMP2 Thermostat Quick Start Guide
Heatit 4512667 HEATIT Z-TEMP2 Thermostat Installational Manual
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…