Thank you for purchasing a FANTINI COSMI S.p.A. product Please read this instruction manual carefully and always keep it at hand should you need to consult it for any reason. The documentation reflects the characteristics of the product. However, for regulatory or commercial developments, customers should verify the availability of updates relating to this documentation on the FANTINI COSMI S.p.A. website: pdf.fantinicosmi.it
The unit CH130ARR2 is a kit consisting of a thermostat CH130AR2 and an actuator CH176D that connected with a bipolar cable, allows the remote control of two valves, the three-speed motor, or a 0 ..10V motor, of a fan coil. The thermostat reads the room temperature and controls it from the fan coil’s motor valves and speed in order to obtain the best climate comfort. Fan adjustment can be automatic or manual, depending on the settings made by the user from the function keys, which, together with the LCD screen facilitates daily operation of the system. The non-polarised bipolar cable connecting the thermostat to the module has dual function:
It is possible to connect a single thermostat to several actuators in order to control more fan coils simultaneously with only two cables. For this application, follow the detailed instructions in the unit installation manual CH176D
CONTENTS OF PACKAGE
CONTROLS
ADVANCED CONTROLS
Simultaneously pressing the two keys enables the following settings:
WARNINGS KEY
Note: in 4-pipe plants, when both symbols 4 and 5 light up it indicates AUTOMATIC mode. With the active minimum sensor function, the symbol 8 or the flashing symbol 9 indicates that the supply water temperature is outside the set limits. In this case, ventilation is interrupted.
ATTENTION!
The thermostat CH130AR2 is supplied with a base suitable for assembly both wall-mounted and recessed in rectangular 3-place box (503) or round.
For further information regarding connection of the thermostat-actuator-fan coil system, refer to the connection diagrams in the CH176D unit installation manual. Electrical connections must be carried out as shown in the connection diagram. Please note that connection of the external probe (EXP1) and input for remote control (SEL1), are subject to certain configuration parameter settings.
Connection of the actuator
Connect the power wires coming from the actuator CH172D to terminals A and B, as shown in the figure. Flexible conductors with a max cross-section of 2.5 mm2 can fit in the terminals
Connection of auxiliary input
Connect the two auxiliary input wires to the screw terminals 1 and 2, as shown in the figure.
Connection of the external probe
Connect the two wires of the external probe to the screw terminals 3 and 4, as shown in the figure.
START-UP
To start the thermostat after installation, follow the procedure below:
SUMMER/WINTER MODE SELECTION
The current operating mode is indicated by the relative symbol. To change current operating mode settings, simultaneously press keys 1 and 2 (pressing > 3 sec).
Note: the operating mode cannot be changed if the thermostat is enabled to manage change-over (locally or remotely) or if the 4-pipe system is enabled in AUTOMATIC mode.
OPERATING MODES
COMFORT MODE
ECONOMY MODE
OFF
In this mode, the thermostat stops any adjustment. If the thermostat is in winter mode, only antifreeze protection is active. To check the currently set antifreeze temperature, press key 3 or 4. To change the set Antifreeze temperature value, repeatedly press key 3 (to increase it) or key 4 (to decrease it). The temperature is changed in steps of 0.1°C. To switch to OFF mode, repeatedly press key 2 to decrease the fan speed until the wording OFF appear on the screen
FAN SPEED SETTING
There are three different fan speeds: minimum, medium, and maximum. The speed can be set manually by selecting one of the three speeds, or automatic. In AUTO, the thermostat will use the most suitable fan speed to reach and maintain the requested room temperature.
KEY LOCK
To enable the key lock function, useful in preventing the thermostat from being used by unauthorised persons, follow the steps below:
TEMPORARY KEY UNLOCK
FAULTS
The presence of one or more faults is indicated on the display by the following error codes:
It is recommended to use a soft cotton cloth without any detergent to clean the thermostat.
THERMOSTAT CONFIGURATION
ATTENTION!
Thermostat parameters configuration must only be carried out by qualified technical personnel. Thermostat operation in relation to a specific design is subject to correct setting of certain operation configuration parameters, which can be consulted and/or edited by accessing a technical menu, as described below:
P01 is displayed on the screen, which refers to the first alphanumeric identification index of the parameters list.
Note: the thermostat forwards the various controls (valves control, fan speed control) to the CH176D actuation unit every minute.
USER-EDITABLE PARAMETERS
PARAMETER | DESCRIPTION | DEFAULT | FIELD |
P01 | Password | 000 | 000: password disabled 386: universal password |
P02 | Unit of measure | CEL | CEL: Celsius FAH: Fahrenheit |
P03 | Auxiliary input status display (AUX IN) | cL: closed oP: open | |
P04 | Temperature display on remote actuator input | -50°C … 50°C cL: closed oP: open | |
P05 | Temperature display on external sensor input | -50°C … 50°C cL: closed oP: open | |
End | Exit the user parameters menu + save parameters. If keys 1-2-4 are pressed simultaneously for three seconds, you access the hidden menu for changing the system installation parameters (P06…P51). These parameters should only be configured by qualified technical personnel. | End |
SYSTEM INSTALLATION PARAMETERS (HIDDEN MENU)
PARAMETER | DESCRIPTION | DEFAULT | FIELD |
P06 | Plant type (PLANT) | 2P | 2P: 2 pipes 4P: 4 pipes |
P07 | Hot water/electrical resistance valve selection | 1 | 1: hot water valve 2: electrical resistance |
P08 | Ventilation modes | 1 | 1: continuous 2: continuous-stop winter mode 3: continuous-stop summer mode 4: subordinated to valve status 5: subordinated-stop in winter mode 6: subordinated-stop in summer mode |
P9 | Adjustment modes | 1 | 1: Manual Winter/Summer mode 2: Automatic Winter/Summer mode |
P10 | Anti-stratification | 1 | 1: not active 2: summer only 3: winter only |
P11* | Temperature sensor on remote actuator sensor input
Reading frequency : Once a minute | 1 | 1: not connected 2: winter only minimum sensor 3: winter/summer minimum sensor 4: automatic change-over 5: return ( only if P13 is other than 6 ) |
P12 | Temperature sensor on external sensor input Reading frequency : Once a minute Options 7-8-9 are only visible if CH172D was selected as remote actuator ( P51 ) | 1 | 1: not connected 2: ON/OFF 3: manual change-over 4: comfort/economy 5: reduction (-3.0°C winter +3.0°C summer) 6: return ( only if P12 is other than 5 ) 7: winter only minimum sensor 8: winter/summer minimum sensor 9: automatic change-over |
P13 | Auxiliary input
Reading frequency : Once every 10 seconds | 1 | 1: not connected 2: ON/OFF 3: manual change-over 4: comfort/economy 5: reduction (-3.0°C winter +3.0°C summer) |
P14 | P13 – P14 input polarity | 1 | n.o. normally open n.c. normally closed 1: P12 (n.o.) P13 (n.o.) 2: P12 (n.o.) P13 (n.c.) 3: P12 (n.c.) P13 (n.o.) 4: P12 (n.c.) P13 (n.c.) |
P15 | Room temperature correction | 0.0 °C | -4.0°C … 4.0°C (0.1°C step) |
P16 | Temperature correction on external sensor | 0.0 °C | -4.0°C … 4.0°C (0.1°C step) |
P17 | Temperature correction on remote sensor | 0.0 °C | -4.0°C … 4.0°C (0.1°C step) |
PARAMETER | DESCRIPTION | DEFAULT | FIELD |
P18 | Display mode | 1 | 1: Troom view 2 = set point view |
P19 | OFF display mode | 1 | 1: ‘OFF’ view 2: view from P18 |
P20 | Key lock mode | 1 | 1 All keys locked 2: Setpoint + W/S + E/C key lock 3: W/S + E/C key lock |
P21 | Regulation differential in winter mode | Std | Std / 0.3°C … 5.0°C (step 0.1°C) |
P22 | Regulation differential in summer mode | Std | Std / 0.3°C … 5.0°C (step 0.1°C) |
P23 | Summer set point upper limit comfort | 30.0 °C | 2.0°C … 30.0°C (0.1°C step) |
P24 | Summer set point lower limit comfort | 2.0 °C | 2.0°C … 30.0°C (0.1°C step) |
P25 | Summer set point upper limit economy | 30.0 °C | 2.0°C … 30.0°C (0.1°C step) |
P26 | Summer set point lower limit economy | 2.0 °C | 2.0°C … 30.0°C (0.1°C step) |
P27 | Winter set point upper limit comfort | 30.0 °C | 2.0°C … 30.0°C (0.1°C step) |
P28 | Winter set point lower limit comfort | 2.0 °C | 2.0°C … 30.0°C (0.1°C step) |
P29 | Winter set point upper limit economy | 30.0 °C | 2.0°C … 30.0°C (0.1°C step) |
P30 | Winter set point lower limit economy | 2.0 °C | 2.0°C … 30.0°C (0.1°C step) |
P31 | Upper limit set-point automatic regulation | 30.0 °C | 2.0°C … 30.0°C (0.1°C step) |
P32 | Lower limit set-point automatic regulation | 2.0 °C | 2.0°C … 30.0°C (0.1°C step) |
P33 | Minimum sensor threshold in winter mode | 34.0 °C | 28.0°C … 42.0°C (step 0.1°C) |
P34 | Minimum sensor threshold in summer mode | 22.0 °C | 10.0°C … 25.0°C (step 0.1°C) |
P35 | Minimum sensor tripping differential | 4.0 °C | 2.0°C … 6.0°C (0.1°C step) |
P36 | Lower change-over temp. threshold | 22.0 °C | 15.0°C … 24.0°C (step 1.0°C) |
P37 | Upper change-over temp. threshold | 32.0 °C | 26.0°C … 35.0°C (step 1.0°C) |
P38 | Dead zone range (automatic regulation) | 2.0 °C | -1.0°C … 6.0°C (1.0°C step) |
P39* | Minimum manual fan speed (0..10V) | 1.0V | 1.0V … 6.0V (step 0.1V) |
P40* | Medium manual fan speed (0..10V) | 5.0V | 3.0V … 8.0V (step 0.1V) |
P41* | Maximum manual fan speed (0..10V) | 10.0V | 6.0V … 10.0V (step 0.1V) |
P42 | Ventilation speed change-over hysteresis (IrL) | 0.5 °C | 0.5°C … 2.0°C (0.1°C step) |
P43* | Minimum winter automatic fan speed (0..10V) | 1.0V | 1.0V … 6.0V (step 0.1V) |
P44* | Maximum winter automatic fan speed (0..10V) | 10.0V | 5.0V … 10.0V (step 0.1V) |
P45* | Minimum summer automatic fan speed (0..10V) | 1.0V | 1.0V … 6.0V (step 0.1V) |
P46* | Maximum summer automatic fan speed (0..10V) | 10.0V | 5.0V … 10.0V (step 0.1V) |
P47 | Proportional band in winter automatic mode | 3.5 °C | 2.0°C … 6.0°C (0.1°C step) |
P48 | Proportional band in summer automatic mode | 3.5 °C | 2.0°C … 6.0°C (0.1°C step) |
P49* | Enable ventilation relay | YES | YES: relays enabled + 0..10V output no: relays disabled (only 0..10V output) |
P50 | Remote actuator selection | 176 | 176: CH176D 172: CH172D |
P51 | Restoring factory settings (default) | no | no YES |
P06 Plant type (plant)
P07 Hot water valve
P08 Ventilation modes
P09 Adjustment modes
Note: when selecting option 2, the adjustment involves parameter P38; By selecting option 2 SUMMER/WINTER mode cannot be changed manually.
P10 Anti-stratification operation
This setting is only effective if P11=5 or P12 = 6 (adjustment with return sensor)
Note: if ventilation is not active for 15 straight minutes, the anti-stratification function switches on for two minutes ventilation at MEDIUM speed regardless of minimum sensor consent.
P11 Temperature sensor on remote actuator sensor input
Note: by selecting option 4 SUMMER/WINTER mode cannot be changed manually.
P12 Temperature sensor on external temperature sensor input
P13 Auxiliary input
P15 Room temperature correction
P16 Temperature correction on external sensor
P17 Temperature correction on remote sensor
These parameters are used to correct the room temperature value read, since in certain installations, the room temperature read may be unsatisfactory due to the position of the probe (internal or return).
P18 Display mode
P19 OFF display mode
P20 Key lock mode
With active password, select the number and type of locked keys.
P21-P22 Adjustment differential
P33 Minimum sensor threshold triggered (winter mode)
P34 Minimum sensor threshold triggered (summer mode)
P36 Lower change-over threshold
P37 Upper change-over threshold
P38 Dead zone interval
P50 Remote actuator selection
OPERATION
The CH130AR2 unit is an actuation model which, connected to a thermostat for fan coil CH133AR2 – CH133RR – CH130AR2 – CH130ARR – CH130RR via a bipolar cable, allows to remotely control the two valves, the three-speed motor or a 0 .. 10V, motor, and accept a temperature sensor connected to the appropriate input.
The bipolar cable connecting the module to the thermostat, has a dual function:
The CH130AR2C unit is compatible with the CH172D actuator via external set-up. It is possible to connect a single thermostat to several actuators, so as to control more than one fan coil simultaneously with only two cables; for this application, carefully follow the detailed instructions in the document.
The device is designed for installation on DIN rail, but its small size facilitate the installation inside the fan coil also.
ATTENTION!
The end parts (live) of the CH176D must be installed in a container or fan coil inaccessible by the user. Installation must be carried out by qualified personnel, in compliance with the requirements concerning installation of electrical devices. Make sure that the power network is disconnected before making any connections or working on the device.
CONNECTING SEVERAL MODULES TO ONE THERMOSTAT
A CH133AR2 – CH133RR – CH130AR2 – CH130ARR – CH130RR thermostat can control up to five fan-coils simultaneously, using only two wires to connect to the various actuation modules. In this case, only one of the two CH176D modules must have the “BUS selector” in “MASTER” position, while all others must be left in “SLAVE” mode (default setting). The temperature probe connected to the actuation module set up as “MASTER” is the one read by the thermostat. The connection between the various devices must be made as per the diagram in the following figure
If thermostats CH133RR – CH130RR – CH130ARR are connected to the actuation module, it must be configured in CH172D mode. The selection is made by switching on the actuation module by means of the configuration of the probe input according to the following diagram:
LUMINOUS STATUS INDICATOR
COMMISSIONING AND OPERATIONAL CHECK
Commissioning and testing procedure:
The symbol of the crossed-out wheeled bin indicates that the products must be collected and disposed of separately from household waste. The batteries and integrated accumulators may be disposed of together with the product. They will be separated at the recycling facilities. A black bar indicates that the product was placed on the market after 13 August 2005. Participating in the separate collection of products and batteries contributes to the correct disposal of these materials and therefore avoids possible negative consequences for the environment and human health. For more detailed information on the collection and recycling programmes available in your country, contact the local authorities or the sales point where you purchased the product.
GENERAL WARRANTY CONDITIONS
The conventional warranty lasts 24 months, starting from the date the equipment is installed. The warranty covers all parts of the equipment, with the exception of those subjected to normal wear through use.
FANTINI COSMI S.p.A.
DOWNLOAD MANUALS:
Fantini cosmi CH130ARR2 Fan-coil Room Thermostat Instruction Manual
OTHER MANUALS:
Fantini cosmi CH130ARR2 Fan-coil Room Thermostat Product Data Sheet
Fantini cosmi CH130ARR2 Fan-coil Room Thermostat Instruction Manual
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…