Fantini logo

Fantini cosmi CH130ARR2 Fan-coil Room Thermostat 

Fantini cosmi- CH130ARR2- Fan-coil -Room -Thermostat - pro

Introduction

Thank you for purchasing a FANTINI COSMI S.p.A. product Please read this instruction manual carefully and always keep it at hand should you need to consult it for any reason. The documentation reflects the characteristics of the product. However, for regulatory or commercial developments, customers should verify the availability of updates relating to this documentation on the FANTINI COSMI S.p.A. website: pdf.fantinicosmi.it

OPERATION

The unit CH130ARR2 is a kit consisting of a thermostat CH130AR2 and an actuator CH176D that connected with a bipolar cable, allows the remote control of two valves, the three-speed motor, or a 0 ..10V motor, of a fan coil. The thermostat reads the room temperature and controls it from the fan coil’s motor valves and speed in order to obtain the best climate comfort. Fan adjustment can be automatic or manual, depending on the settings made by the user from the function keys, which, together with the LCD screen facilitates daily operation of the system. The non-polarised bipolar cable connecting the thermostat to the module has dual function:

It is possible to connect a single thermostat to several actuators in order to control more fan coils simultaneously with only two cables. For this application, follow the detailed instructions in the unit installation manual CH176D

CONTENTS OF PACKAGE

DESCRIPTION OF DISPLAY KEYS

CONTROLS

Fantini -cosmi- CH130ARR2- Fan-coil -Room -Thermostat -FIG (1)

ADVANCED CONTROLS

Simultaneously pressing the two keys enables the following settings:

WARNINGS KEY

  1. Measured or set temperature
  2. Comfort mode
  3. Economy mode
  4. Summer mode
  5. Winter mode
  6. Fan speed indicator (MIN-MED-MAX)
  7. Automatic fan mode
  8. Fan-coil cooling enabled
  9.  Fan-coil heating enabledFantini -cosmi- CH130ARR2- Fan-coil -Room -Thermostat -FIG (3)

Note: in 4-pipe plants, when both symbols 4 and 5 light up it indicates AUTOMATIC mode. With the active minimum sensor function, the symbol 8 or the flashing symbol 9 indicates that the supply water temperature is outside the set limits. In this case, ventilation is interrupted.

TECHNICAL FEATURES

INSTALLATION

ATTENTION!

The thermostat CH130AR2 is supplied with a base suitable for assembly both wall-mounted and recessed in rectangular 3-place box (503) or round.

Fantini -cosmi- CH130ARR2- Fan-coil -Room -Thermostat -FIG (4)

ELECTRICAL CONNECTION

For further information regarding connection of the thermostat-actuator-fan coil system, refer to the connection diagrams in the CH176D unit installation manual. Electrical connections must be carried out as shown in the connection diagram. Please note that connection of the external probe (EXP1) and input for remote control (SEL1), are subject to certain configuration parameter settings.

Connection of the actuator
Connect the power wires coming from the actuator CH172D to terminals A and B, as shown in the figure. Flexible conductors with a max cross-section of 2.5 mm2 can fit in the terminalsFantini -cosmi- CH130ARR2- Fan-coil -Room -Thermostat -FIG (5)

Connection of auxiliary input
Connect the two auxiliary input wires to the screw terminals 1 and 2, as shown in the figure.

Fantini -cosmi- CH130ARR2- Fan-coil -Room -Thermostat -FIG (6)

Connection of the external probe
Connect the two wires of the external probe to the screw terminals 3 and 4, as shown in the figure.

Fantini -cosmi- CH130ARR2- Fan-coil -Room -Thermostat -FIG (7)

DIRECTIONS

START-UP
To start the thermostat after installation, follow the procedure below:

SUMMER/WINTER MODE SELECTION
The current operating mode is indicated by the relative symbol. To change current operating mode settings, simultaneously press keys 1 and 2 (pressing > 3 sec).Fantini -cosmi- CH130ARR2- Fan-coil -Room -Thermostat -FIG (8)

Note: the operating mode cannot be changed if the thermostat is enabled to manage change-over (locally or remotely) or if the 4-pipe system is enabled in AUTOMATIC mode.

OPERATING MODES

COMFORT MODE

ECONOMY MODE

OFF
In this mode, the thermostat stops any adjustment. If the thermostat is in winter mode, only antifreeze protection is active. To check the currently set antifreeze temperature, press key 3 or 4. To change the set Antifreeze temperature value, repeatedly press key 3 (to increase it) or key 4 (to decrease it). The temperature is changed in steps of 0.1°C. To switch to OFF mode, repeatedly press key 2 to decrease the fan speed until the wording OFF appear on the screen

Fantini -cosmi- CH130ARR2- Fan-coil -Room -Thermostat -FIG (12)

FAN SPEED SETTING
There are three different fan speeds: minimum, medium, and maximum. The speed can be set manually by selecting one of the three speeds, or automatic. In AUTO, the thermostat will use the most suitable fan speed to reach and maintain the requested room temperature.Fantini -cosmi- CH130ARR2- Fan-coil -Room -Thermostat -FIG (13)

KEY LOCK
To enable the key lock function, useful in preventing the thermostat from being used by unauthorised persons, follow the steps below:

TEMPORARY KEY UNLOCK

FAULTS

The presence of one or more faults is indicated on the display by the following error codes:

MAINTENANCE

It is recommended to use a soft cotton cloth without any detergent to clean the thermostat.

THERMOSTAT CONFIGURATION

ATTENTION!
Thermostat parameters configuration must only be carried out by qualified technical personnel. Thermostat operation in relation to a specific design is subject to correct setting of certain operation configuration parameters, which can be consulted and/or edited by accessing a technical menu, as described below:

P01 is displayed on the screen, which refers to the first alphanumeric identification index of the parameters list.

Note: the thermostat forwards the various controls (valves control, fan speed control) to the CH176D actuation unit every minute.

USER-EDITABLE PARAMETERS

PARAMETER DESCRIPTION DEFAULT FIELD
P01 Password 000 000: password disabled

386: universal password

P02 Unit of measure CEL CEL: Celsius

FAH: Fahrenheit

P03 Auxiliary input status display (AUX IN) cL: closed

oP: open

P04 Temperature display on remote actuator input -50°C … 50°C

cL: closed

oP: open

P05 Temperature display on external sensor input -50°C … 50°C

cL: closed

oP: open

End Exit the user parameters menu + save parameters.

If keys 1-2-4 are pressed simultaneously for three seconds, you access the hidden menu for changing the system installation parameters (P06…P51).

These parameters should only be configured by qualified

technical personnel.

End

SYSTEM INSTALLATION PARAMETERS (HIDDEN MENU)

PARAMETER DESCRIPTION DEFAULT FIELD
P06 Plant type (PLANT) 2P 2P: 2 pipes

4P: 4 pipes

P07 Hot water/electrical resistance valve selection 1 1: hot water valve

2: electrical resistance

P08 Ventilation modes 1 1: continuous

2: continuous-stop winter mode 3: continuous-stop summer mode 4: subordinated to valve status

5: subordinated-stop in winter mode

6: subordinated-stop in summer mode

P9 Adjustment modes 1 1: Manual Winter/Summer mode

2: Automatic Winter/Summer mode

P10 Anti-stratification 1 1: not active

2: summer only

3: winter only

P11* Temperature sensor on remote actuator sensor input

 

Reading frequency : Once a minute

1 1: not connected

2: winter only minimum sensor

3: winter/summer minimum sensor 4: automatic change-over

5: return ( only if P13 is other than 6 )

P12 Temperature sensor on external sensor input Reading frequency : Once a minute

Options 7-8-9 are only visible if CH172D was selected as remote actuator ( P51 )

1 1: not connected

2: ON/OFF

3: manual change-over

4: comfort/economy

5: reduction (-3.0°C winter +3.0°C summer)

6: return ( only if P12 is other than 5 ) 7: winter only minimum sensor

8: winter/summer minimum sensor

9: automatic change-over

P13 Auxiliary input

 

Reading frequency : Once every 10 seconds

1 1: not connected

2: ON/OFF

3: manual change-over

4: comfort/economy

5: reduction (-3.0°C winter +3.0°C summer)

P14 P13 – P14 input polarity 1 n.o. normally open

n.c. normally closed

1: P12 (n.o.) P13 (n.o.)

2: P12 (n.o.) P13 (n.c.)

3: P12 (n.c.) P13 (n.o.)

4: P12 (n.c.) P13 (n.c.)

P15 Room temperature correction 0.0 °C -4.0°C … 4.0°C (0.1°C step)
P16 Temperature correction on external sensor 0.0 °C -4.0°C … 4.0°C (0.1°C step)
P17 Temperature correction on remote sensor 0.0 °C -4.0°C … 4.0°C (0.1°C step)
PARAMETER DESCRIPTION DEFAULT FIELD
P18 Display mode 1 1: Troom view

2 = set point view

P19 OFF display mode 1 1: ‘OFF’ view

2: view from P18

P20 Key lock mode 1 1 All keys locked

2: Setpoint + W/S + E/C key lock

3: W/S + E/C key lock

P21 Regulation differential in winter mode Std Std / 0.3°C … 5.0°C (step 0.1°C)
P22 Regulation differential in summer mode Std Std / 0.3°C … 5.0°C (step 0.1°C)
P23 Summer set point upper limit              comfort 30.0 °C 2.0°C … 30.0°C (0.1°C step)
P24 Summer set point lower limit               comfort 2.0 °C 2.0°C … 30.0°C (0.1°C step)
P25 Summer set point upper limit            economy 30.0 °C 2.0°C … 30.0°C (0.1°C step)
P26 Summer set point lower limit             economy 2.0 °C 2.0°C … 30.0°C (0.1°C step)
P27 Winter set point upper limit                 comfort 30.0 °C 2.0°C … 30.0°C (0.1°C step)
P28 Winter set point lower limit                  comfort 2.0 °C 2.0°C … 30.0°C (0.1°C step)
P29 Winter set point upper limit                economy 30.0 °C 2.0°C … 30.0°C (0.1°C step)
P30 Winter set point lower limit                economy 2.0 °C 2.0°C … 30.0°C (0.1°C step)
P31 Upper limit set-point automatic regulation 30.0 °C 2.0°C … 30.0°C (0.1°C step)
P32 Lower limit set-point automatic regulation 2.0 °C 2.0°C … 30.0°C (0.1°C step)
P33 Minimum sensor threshold in winter mode 34.0 °C 28.0°C … 42.0°C (step 0.1°C)
P34 Minimum sensor threshold in summer mode 22.0 °C 10.0°C … 25.0°C (step 0.1°C)
P35 Minimum sensor tripping differential 4.0 °C 2.0°C … 6.0°C (0.1°C step)
P36 Lower change-over temp. threshold 22.0 °C 15.0°C … 24.0°C (step 1.0°C)
P37 Upper change-over temp. threshold 32.0 °C 26.0°C … 35.0°C (step 1.0°C)
P38 Dead zone range (automatic regulation) 2.0 °C -1.0°C … 6.0°C (1.0°C step)
P39* Minimum manual fan speed (0..10V) 1.0V 1.0V … 6.0V       (step 0.1V)
P40* Medium manual fan speed (0..10V) 5.0V 3.0V … 8.0V        (step 0.1V)
P41* Maximum manual fan speed (0..10V) 10.0V 6.0V … 10.0V      (step 0.1V)
P42 Ventilation speed change-over hysteresis (IrL) 0.5 °C 0.5°C … 2.0°C (0.1°C step)
P43* Minimum winter automatic fan speed (0..10V) 1.0V 1.0V … 6.0V       (step 0.1V)
P44* Maximum winter automatic fan speed (0..10V) 10.0V 5.0V … 10.0V      (step 0.1V)
P45* Minimum summer automatic fan speed (0..10V) 1.0V 1.0V … 6.0V       (step 0.1V)
P46* Maximum  summer  automatic    fan   speed

(0..10V)

10.0V 5.0V … 10.0V      (step 0.1V)
P47 Proportional band in winter automatic mode 3.5 °C 2.0°C … 6.0°C (0.1°C step)
P48 Proportional band in summer automatic mode 3.5 °C 2.0°C … 6.0°C (0.1°C step)
P49* Enable ventilation relay YES YES: relays enabled + 0..10V output

no: relays disabled (only 0..10V output)

P50 Remote actuator selection 176 176: CH176D

172: CH172D

P51 Restoring factory settings (default) no no

YES

P06 Plant type (plant)

P07 Hot water valve

P08 Ventilation modes

P09 Adjustment modes

Note: when selecting option 2, the adjustment involves parameter P38; By selecting option 2 SUMMER/WINTER mode cannot be changed manually.

P10 Anti-stratification operation
This setting is only effective if P11=5 or P12 = 6 (adjustment with return sensor)

Note: if ventilation is not active for 15 straight minutes, the anti-stratification function switches on for two minutes ventilation at MEDIUM speed regardless of minimum sensor consent.

P11 Temperature sensor on remote actuator sensor input

Note: by selecting option 4 SUMMER/WINTER mode cannot be changed manually.

P12 Temperature sensor on external temperature sensor input

P13 Auxiliary input

P15 Room temperature correction
P16 Temperature correction on external sensor

P17 Temperature correction on remote sensor
These parameters are used to correct the room temperature value read, since in certain installations, the room temperature read may be unsatisfactory due to the position of the probe (internal or return).

P18 Display mode

P19 OFF display mode

P20 Key lock mode
With active password, select the number and type of locked keys.

P21-P22 Adjustment differential

P33 Minimum sensor threshold triggered (winter mode)

P34 Minimum sensor threshold triggered (summer mode)

P36 Lower change-over threshold

P37 Upper change-over threshold

P38 Dead zone interval

P50 Remote actuator selection

DIN RAIL CH176D ACTUATOR

OPERATION

The CH130AR2 unit is an actuation model which, connected to a thermostat for fan coil CH133AR2 – CH133RR – CH130AR2 – CH130ARR – CH130RR via a bipolar cable, allows to remotely control the two valves, the three-speed motor or a 0 .. 10V, motor, and accept a temperature sensor connected to the appropriate input.

The bipolar cable connecting the module to the thermostat, has a dual function:

The CH130AR2C unit is compatible with the CH172D actuator via external set-up. It is possible to connect a single thermostat to several actuators, so as to control more than one fan coil simultaneously with only two cables; for this application, carefully follow the detailed instructions in the document.

TECHNICAL FEATURES

The device is designed for installation on DIN rail, but its small size facilitate the installation inside the fan coil also.

ATTENTION!
The end parts (live) of the CH176D must be installed in a container or fan coil inaccessible by the user. Installation must be carried out by qualified personnel, in compliance with the requirements concerning installation of electrical devices. Make sure that the power network is disconnected before making any connections or working on the device.

Fantini -cosmi- CH130ARR2- Fan-coil -Room -Thermostat -FIG (15)

CONNECTING SEVERAL MODULES TO ONE THERMOSTAT
A CH133AR2 – CH133RR – CH130AR2 – CH130ARR – CH130RR thermostat can control up to five fan-coils simultaneously, using only two wires to connect to the various actuation modules. In this case, only one of the two CH176D modules must have the “BUS selector” in “MASTER” position, while all others must be left in “SLAVE” mode (default setting). The temperature probe connected to the actuation module set up as “MASTER” is the one read by the thermostat. The connection between the various devices must be made as per the diagram in the following figure

Fantini -cosmi- CH130ARR2- Fan-coil -Room -Thermostat -FIG (16)

OPERATING MODE SELECTION

If thermostats CH133RR – CH130RR – CH130ARR are connected to the actuation module, it must be configured in CH172D mode. The selection is made by switching on the actuation module by means of the configuration of the probe input according to the following diagram:

LUMINOUS STATUS INDICATOR

COMMISSIONING AND OPERATIONAL CHECK

Commissioning and testing procedure:

DISPOSAL

The symbol of the crossed-out wheeled bin indicates that the products must be collected and disposed of separately from household waste. The batteries and integrated accumulators may be disposed of together with the product. They will be separated at the recycling facilities. A black bar indicates that the product was placed on the market after 13 August 2005. Participating in the separate collection of products and batteries contributes to the correct disposal of these materials and therefore avoids possible negative consequences for the environment and human health. For more detailed information on the collection and recycling programmes available in your country, contact the local authorities or the sales point where you purchased the product.

GENERAL WARRANTY CONDITIONS
The conventional warranty lasts 24 months, starting from the date the equipment is installed. The warranty covers all parts of the equipment, with the exception of those subjected to normal wear through use.

FANTINI COSMI S.p.A.

REFERENCE:

DOWNLOAD MANUALS:

Fantini cosmi CH130ARR2 Fan-coil Room Thermostat Instruction Manual

OTHER  MANUALS:

Fantini cosmi CH130ARR2 Fan-coil Room Thermostat Product Data Sheet

Fantini logo

Fantini cosmi CH130ARR2 Fan-coil Room Thermostat Instruction Manual

Leave a Reply

Your email address will not be published. Required fields are marked *

To respond on your own website, enter the URL of your response which should contain a link to this post's permalink URL. Your response will then appear (possibly after moderation) on this page. Want to update or remove your response? Update or delete your post and re-enter your post's URL again. (Find out more about Webmentions.)