To lock the keypad, press and hold the
To unlock the keypad, press and hold the
The RFRP-OT Room Thermostat has the following programming modes available:
If 7 D mode is selected, you can program each day of the week with 6 individual times and temperatures.
If 24H mode is selected, you can only program each day of the week with the same 6 times and temperatures.
Copy function may only be used if the thermostat is in the 7d mode.
Set the times and temperatures for the day that you wish to copy from in programming mode.
When still on the day press the COPY button.
The day of the week that you have selected will be shown with ‘COPY’ below it.
The next day will begin to flash on the top of the screen.
Press the
Press the
You can copy to multiple days using the button.
Press the OK button when copying has been completed.
Temporary Override
When in AUTO mode, press the
Press OK or after 5 seconds the thermostat will operate at this temperature, until the next switching time.
To cancel a temporary override, press the OFF button and then press the
AUTO button to return to the automatic mode.
Permanent Override
Press the MAN button to enter the manual mode (Permanent Override), ‘MAN’ will appear on the screen.
Press the
Press OK or after 5 seconds the thermostat will operate in this permanent override.
To cancel permanent override, press the OFF button and then press the AUTO button to return to the automatic mode.
The thermostat can be boosted to a specific temperature for 1, 2 or 3 hours while the thermostat is operating in all modes except for holiday mode.
Press the BOOST button 1, 2 or 3 times, and the time that the boost will be activated to will flash on the screen.
If you do not press any other button the boost will activate to the temperature displayed on the screen after 5 seconds.
If you press the OK button the temperature will now flash. You can edit the temperature if you press the or buttons.
Press the OK button or wait for 5 seconds for the boost to activate.
‘BOOST TO’ will now be displayed on the screen with the time that it is activated to be displayed above this text.
Press the BOOST button again to deactivate the boost.
This will switch your heating system off between the start and end times you select.
‘HOLIDAY TO’ will appear on screen.
There are two settings for selection. The factory default setting is AUTO.
OFF The backlight is permanently OFF.
AUTO On pressing any button the backlight stays on for 5 seconds.
To adjust the backlight setting, lower the cover on the front of the unit.
Press the OK button for 5 seconds.
Press either the or buttons to select the OFF or AUTO mode.
Press the OK button.
Battery low warning
When the batteries are almost empty, the symbol
The batteries must now be replaced or the unit will shut down.
Lower the flap at the front of the thermostat.
There is a battery compartment located below the buttons.
Apply downward pressure to remove the cover.
Insert the 2 x AA batteries and the thermostat will turn on.
Close the battery compartment.
To access the installer menu, you must hold Prog and OK for 5 seconds.
When in the installer menu, press , and OK to navigate and select.
Use AUTO , MAN or OFF to go back a step.
To achieve the target temperature when the program starts, the thermostat will read:
Example when Ti = 20
Program 1 on the thermostat is 21°C for 06:30 am and the room temperature is 18°C.
The thermostat will start the heating at 05:30 am to reach 21°C for 06:30 am @ Ti=20.
Example when Ti = 10
Program 1 on the thermostat is 21°C for 06:30 am and the room temperature is 18°C.
The thermostat will start the heating at 06:00 am to reach 21°C for 06:30 am @ Ti=10.
TPI (Time Proportional & Integral Mode)
When the thermostat is in TPI mode and the temperature is rising in the zone and falls into the Proportional Bandwidth section, TPI will start to affect the operation of the thermostat. The thermostat will turn on and off as it gains heat so that it doesn’t overshoot the setpoint by too much. It will also turn on if the temperature is falling so it doesn’t undershoot the setpoint which will leave the user with a more comfortable level of heat.
There are 2 settings that will affect the operation of the thermostat:
Example: Program 1 on the thermostat is 21°C for 06:30 am and the room temperature is 18°C. The thermostat will start the heating at 06:30am and the room temperature will start to increase then but will switch itself off before it reaches temperature and allow the room temperature to increase naturally – this cycle may begin again if the thermostat isn’t reaching temperature.
PO 2 Setting high & low limits
This menu allows the installer to change the min. and max. the temperature range that the thermostat can be set at.
PO 3 Hysteresis HOn and HOFF
This menu allows the installer to change the switching differential of the thermostat when the temperature is rising and falling.
HOn is the fall in temperature – Default – 0.4°C. This will allow a fall of 0.4°C from the setpoint before the thermostat turns on again.
HOFF is the rise in temperature – Default – 0.0°C. This will allow the temperature to rise 0°C above its setpoint.
PO 4 Calibrate the thermostat
This menu allows the installer to re-calibrate the thermostat. The current temperature will be displayed on the screen and can be adjusted by pressing the or buttons .
PO 5 Frost Protection
This menu allows the installer to activate or de-activate frost protection. When frost protection is activated the thermostat will switch on the boiler when the temperature drops below 5°C.
PO 6 Exit
This menu allows the installer to return to the main interface.
It is also possible to exit the installer menu by pressing AUTO , MAN or OFF whilst in the installer menu.
This menu allows the installer to change the DHW temperature of the boiler. The temperature can be set in 0.5°C increments by pressing the or buttons.
Press the OK button to select the desired temperature. This menu is only available when the thermostat is connected to OpenTherm® and DHOP is ON (P08 OT installer menu).
This menu allows the installer to view information received from the OpenTherm® boiler. It may take a few seconds to load information relating to each parameter. The information that can be shown from the boiler is outlined in the table below.
Displayed on screen | Description | Remark |
tSEt | Target water temp | |
tFLO | Outlet water temp | |
trEt | Return water temp | |
tdH | DHW temperature | This is only visible if DHOP is On (P08 OT Installer menu) |
tFLU | Flue gas temperature | Dependent on boiler |
tESt | Outdoor temperature | Dependent on boiler |
nOdU | Modulation percentage | |
FLOr | Water flow | This is only visible if DHOP is On (P08 OT Installer menu) |
PrES | Water pressure | Dependent on boiler |
This menu allows the installer to activate or deactivate DHW target temperature control from the thermostat. This menu is only available when the thermostat is connected to OpenTherm®
This menu allows the installer to configure the OpenTherm® parameters.
To access the menu please enter the password “08” with the or buttons.
Press OK to confirm.
The parameters that can be set are outlined in the table below.
Param | Description | Range | Default |
HHCH t-1 | Maximum set point heating | 45 – 85˚C | 85˚C |
LLCH t-2 | Minimum set point heating | 10 – HHCH˚C | 45˚C |
CLI t-3 | This allows user to select different climatic curves for weather compensation. This only applies to Boilers with an outside sensor connected. | 0.2 – 3.0 | 1.2 |
InFL t-4 | Influence of room sensor on modulation of the boiler. Recommended value is 10. | 0 – 20 | 10 |
HHbO t-5 | This is the target setpoint for your CH flow temperature. Note: this value must be within the range of HHCH and LLCH. | HHCH Max >=ID57 >=LLCH Min | 85˚C |
Exit | Press OK button to turn back to main interface. |
Climatic Curve
This menu allows the installer to return to the main interface. It is also possible to exit the installer menu by pressing AUTO, MAN or OFF whilst in the installer menu.
It is possible to have 6 CombiPack4-OT controlling 1 OpenTherm® boiler. To do this it is necessary to make one of the RF1A-OT receivers into a Hub Receiver. This Hub Receiver will receive data from all of the RFRP-OT thermostats and relay this information to the boiler via OpenTherm®. Note: The Hub Receiver should have a wired OpenTherm® connection to the boiler.
Identifying if a receiver is a Hub Receiver
Pairing the RF1A-OT receivers together
Once all units have been paired, allow time for the receivers to begin to communicate and receive OpenTherm® information from the boiler. This may take approximately 2 – 5 minutes.
You will see the red light FLash on the Hub receiver and see corresponding FLash on the other receivers paired to the Hub Receiver when they are sharing information. You may need to pair the receivers to the thermostats again. If so, please refer to page 51.
You can tell if your thermostat is receiving OpenTherm® information from the boiler by entering the installer menu of the thermostat (Hold Prog and OK buttons for 10 Sec) and go to P07 – Info.
If the installer menu is only showing P01 – P05, the thermostat and/or receiver has not been successfully paired.
Example A 1 no. The thermostat controlling OT Boiler
Example B 3 no. Thermostats controlling OT Boiler >>
Note: A maximum of 6 thermostats can be used in the system.
OT Connection Normal Operation | Green LED | Red LED |
RF1A-OT On | ON | OFF – will flash when communicating via RF |
RF1A-OT Off | OFF | ON – will flash when communicating via RF |
OT Communication Error | Green LED | Red LED |
RF1A-OT On | Constant Flash | OFF |
RF1A-OT Off | Constant Flash | ON |
RF Communication Error | Green LED | Red LED |
RF1A-OT On | ON | Constant Flash |
RF1A-OT Off | OFF | Constant Flash |
Summary | Green LED | Red LED |
RF Communication Error | OFF or ON | Constant Flash |
OT Communication Error | Constant Flash | OFF or ON |
Normal Operation RF1A On | ON | OFF or Flashing |
Normal Operation RF1A Off | OFF | ON or Flashing |
Please note, If you are installing a CombiPack4 the RFRP-OT thermostat and the RF1A-OT receiver will have a pre-established RF connection so it is not necessary to carry out the RF connection process below.
On the RF1A-OT receiver:
On the RFRP-OT thermostat:
To disconnect the RFRP-OT thermostat from an RF1A-OT receiver
On the RFRP-OT thermostat:
Press the button. The thermostat will begin to search through the RF channels.
Press and hold the COPY button for 10 seconds. ‘Adr’ will appear on the screen of the thermostat.
Press the OK button twice to complete the unpairing process. The thermostat RFRP-OT is now disconnected from the receiver RF1A-OT.
On the RF1A receiver:
Press the Connect button, the red light will FLash.
Red & green lights if using as a hub receiver.
Press and hold connect for about 10 seconds, the receiver will then stop FLashing.
The RF connection is now cleared.
EPH Controls IE
technical@ephcontrols.co.uk
www.ephcontrols.co.uk/contact-us
T +44 1933 322 072
EPH Controls UK
technical@ephcontrols.com
www.ephcontrols.com/contact-us
T +353 21 471 8440
EPH Controls CP4 room thermostat RF programmable Installation Instructions
EPH Controls CP4 room thermostat RF programmable Operating Instructions
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…