Since the temperature measurement sensor is inside the unit, you must install the thermostat flush-mounting box:
IMPORTANT: Do not install the thermostat on a wall in contact with the outdoors or with an unheated room (e.g. garage, etc.)
The sleeve output in the flush-mounting box must be blanked off (with mastic) in order to avoid unwanted air movements that would cause the sensor reading to be inaccurate.
CF05: the Master thermostat enables the centralised use of ON/OFF and HEAT/COOL (at least one Master thermostat is required in an installation without a programmer).
Temperature management | On/Off management | HEAT/ COOL mode management | |
Master thermostat | On the controlled zone | On all zones | On all zones |
Zone thermostat | On the controlled zone | On the controlled zone | – |
Correction of the measured temperature | +/- 5°C in 0.1°C increments (0°C by default) | ||
Temperature displayed in normal mode | 0 | Setting display (default selection) | |
1 | Display of the measured temperature. | ||
| Ban on the Cool regulation on the thermal zones of the Room Temperature (if SW2 = ON) | 0 | No ban (default selection) |
1 | Ban | ||
Display the status (ON) of the associated output | 0 | No (default selection) | |
1 | Yes | ||
| Thermostat type | 0 | Zone thermostat (default selection) |
1 | Master thermostat |
Activation of the window/door magnetic contact function (the room thermostat switches to Frost Protection mode if the window/door magnetic contact is activated). | 0 | Not activated | |
1 | Activated (default selection) | ||
‘Presence detection’ function (the thermostat lowers its setting in the event that no presence is detected). | 0 | Not activated | |
1 | Activated (default selection) | ||
Standby mode | 0 | Display off after a 10 seconds time-out period | |
1 | Display illuminated continuously (default selection) | ||
Backlighting | 0 | Deactivated | |
1 | When activated, it goes out after a 5-second time-out period (default) | ||
Output number | 1 to 16 depending on the system. ‘–‘ is displayed if none are allocated. | ||
Transmitter type | 0 | Underfloor heating (by default) | |
1 | Heater | ||
2 | Ceiling or ductable | ||
Heating percentage limitation | From 10 to 100% in increments of 10 (100%= No limitation, by default). |
DELETING ALL THE ASSOCIATION BUS WITH THE TECHNICAL UNIT
DELETING THE ASSOCIATION OF THE THERMOSTAT WITH THE TECHNICAL UNIT
Press OK to open the setting, then press + and – to select «= –». Confirm with OK.
INITIALISING THE ROOM THERMOSTAT SETTINGS
This menu restores the system to factory settings.
The system automatically returns to OFF mode.
Download Manual:
Delta Dore 8000-TA-BUS Zone Thermostat Installation Instructions
Delta Dore 8000-TA-BUS Zone Thermostat Installation Instructions
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…