The Danfoss ECtemp Next Plus is an electronic programmable timer thermostat used for controlling electrical floor heating elements. The thermostat is designed for fixed installation only and can be used for both direct heatings of the entire room and for comfort heating of the floor.
| Operation voltage | 85-250V~, 50/60 Hz |
| Standby power consumption | 0,4 W |
| Relay: Resistive load Inductive load | Max. 16 A / 3680 W @ 230 V cos φ= 0.3 Max. 1 A |
| Floor sensor | Floor Sensor NTC 10 kΩ at 25°C Room Sensor NTC 10 kΩ at 25°C |
| Sensing values: (Default NTC 15 K) 0°C 20°C 50°C |
42 kΩ 18 kΩ 6 kΩ |
| Control | Hysteresis ± 1.0° C |
| Ambient temperature | -10°C to +60°C |
| Frost protection temperature | 5°C to +9°C (default 5°C) |
| Temperature range | Room temperature: 5-35°C. Floor temperature: Max. 35°C is default. |
| Sensor failure monitoring | The thermostat has a built-in monitoring circuit, which will switch off the heating if the sensor is disconnected or short-circuited |
| Cable specification max. | 1×4 mm2 or 2×2,5 mm2 |
| Ball pressure test temperature | 75°C |
| Pollution degree | 2 (domestic use) |
| Controller type | 1C |
| Software class | A |
| Storage temperature | -20°C to +65°C |
| IP class | 30 |
| Protection class | Class II – |
| Dimensions | 86 x 86 x 16/40.5 mm (in-wall depth: 24.5 mm) |
| Weight | 103 g |
Safety Instructions
Please also note the following:
Connect the thermostat according to the connection diagram.
Power ON/OFF
Switch thermostat ON/OFF by pressing button on top of thermostat.
Initial Settings
The digits indicate the set value as follows:
| No� | Parameter settings | Settings range | Default |
| P01 | Working mode | 01: Manual 02: Advanced Program- mable Timer | 02 |
| P02 | Temperature control mode | 01: Room and floor temp; 02: Only floor temp.; 03: Only room temp.* | 01 |
| P03 | Maximum floor temperature | 20-30˚C (only for 01 in P02)** | 35˚C |
| P04 | Frost protection | 01: Enable; 02: Disable | 01 |
| P05 | Frost protection setpoint | 5-9˚C | 5˚C |
| P06 | Timer display option | 01: 24h; 02 12h | 01 |
| P07 | Room temp. display option at shutdown | 01: No display surrent temp.; 02: Display current temp. | 01 |
The Advanced Programmable Timer mode enables the setting of a timer-controlled program for automatic comfort temperature, and an energy-saving lower setback temperature if standard room comfort temperature is not required. The function consists of 2 programs:
P1 with 4 events in 5 days (Mon. Tue. Wed. Thu. Fri
P1, Event 1:
P1, Event 2-4:
P2 with 4 events in 2 days (Sat. Sun.).
P2, Event 1:
P2, Event 2-4:
The thermostat will continue the 4-event program based on the present time and day. To set and change the room temperature temporarily:
| Days | Event 1 | Event 2 | Event 3 | Event 4 | ||||
| Start time | Temp� | Start time | Temp� | Start time | Temp� | Start time | Temp� | |
| Mon – Fri. | 6:30 | 20˚C (27˚C)* | 8:30 | 15˚C (25˚C)* | 16:30 | 20˚C (27˚C)* | 22:30 | 25˚C (25˚C)* |
| Sat – Sun. | 7:30 | 20˚C (27˚C)* | 9:30 | 20˚C (27˚C)* | 16:30 | 21˚C (28˚C)* | 22:30 | 25˚C (25˚C)* |
Temperature Setting
IMPORTANT: When the thermostat is used to control a floor heating element in connection with a wooden floor or similar material, always use a floor sensor and never set the maximum floor temperature to more than 35 ° C.
| Thermal resistance [m2K/W] | Examples of Flooring | Details | The approximate setting for 25˚C floor temperature |
| 0.05 | 8 mm HDF based laminate | >800 kg/m3 | 28˚C |
| 0.10 | 14 mm beech parquet | 650 – 800 kg/m3 | 31˚C |
| 0.13 | 22 mm solid oak plank | >800 kg/m3 | 32˚C |
| < 0.17 | Max. carpet thickness suitable for floor heating | acc. to EN 1307 | 34˚C |
| 0.18 | 22 mm solid for planks | 450 – 650 kg/m3 | 35˚C |
Timer Setting
Safety Lock
Away Mode
Present Floor Temperature
Switch Power OFF
Switch Power ON
Extending Maximum floor temperature limitation to 45°C
Power OFF
Power ON
Press M button for 6 seconds Select P03 (Table in 4.2): raise floor temperature limitation higher than 35°C by using the >
Table for 4.9 Change to Room control only and 4.10 Extending Maximum Floor temperature limitations to 45°C
| No. | Function | Setting | Factory default |
| Danfoss ECtemp™ Next Plus | |||
| P01 | Room Sensor Calibration | Offset:-10˚C to +10˚C | 0˚C |
| P02 | Floor Sensor Calibration | Offset:-10˚C to +10˚C | 0˚C |
| P03 | Maximum Room Temp. Limitation | 5-35˚C(Active in Temperature Control Mode 01) | 35˚C |
| P04 | Minimum Room Temp. Limitation | 5-35˚C(Active in Temperature Control Mode 01) | 5˚C |
| P05 | Maximum Room Temp. Limitation | 5-35˚C(Active in Temperature Control Mode 02) | 35˚C |
| P06 | Minimum Room Temp. Limitation | 5-35˚C(Active in Temperature Control Mode 02) | 5˚C |
| P07 | Setting range extension for P06, P07, P08 | 01: Max. 35˚C, 02: Max. 45˚C | 01 |
| P08 | Only room temperature control | 01: Enable, 02: Disable | 02 |
Error Codes
| E1 | Room sensor failure |
| E2 | Floor sensor failure |
| EE | EEPROM failure |
| Lo | Temperature lower than 0˚C |
| Hi | Temperature higher than 5˚C |
5 year warranty
Download Manual:
Danfoss ECtemp Next Plus Electronic Thermostat Installational Guide
OTHER MANUALS:
Danfoss ECtemp Next Plus Electronic Thermostat Product Specifications Guide
Danfoss ECtemp Next Plus Electronic Thermostat Installational Guide
Bad Ragaz Casino No Deposit Bonus Codes For Free Spins 2026 Details pertaining to the…
Online Slot Games For Money Playing online casinos UK on a mobile device Spin the…
Prime Fortune Casino No Deposit Bonus Codes For Free Spins 2026 Fantasy sports became a…
Online Casino Real Money Uk No Deposit Get ready to play the most realistic card…
Sin88 Casino No Deposit Bonus Codes For Free Spins 2026 This can be part of…
How To Always Win Blackjack Casino offer terms and conditions in UK Here is how…