Danfoss ECtemp Next Plus Electronic Thermostat  

Danfoss -ECtemp -Next- Plus -Electronic -Thermostat - PRO

Introduction

The Danfoss ECtemp Next Plus is an electronic programmable timer thermostat used for controlling electrical floor heating elements. The thermostat is designed for fixed installation only and can be used for both direct heatings of the entire room and for comfort heating of the floor.

Technical Specifications

Operation voltage 85-250V~, 50/60 Hz
Standby power consumption 0,4 W
Relay: Resistive load Inductive load  

Max. 16 A / 3680 W @ 230 V

cos φ= 0.3 Max. 1 A

Floor sensor Floor Sensor NTC 10 kΩ at 25°C

Room Sensor NTC 10 kΩ at 25°C

Sensing values: (Default NTC 15 K) 0°C

20°C

50°C

 

 

42 kΩ

18 kΩ

6 kΩ

Control Hysteresis ± 1.0° C
Ambient temperature -10°C to +60°C
Frost protection temperature 5°C to +9°C (default 5°C)
Temperature range Room temperature: 5-35°C. Floor temperature: Max. 35°C is default.
Sensor failure monitoring The thermostat has a built-in monitoring circuit, which will switch off the heating if the sensor is disconnected or short-circuited
Cable specification max. 1×4 mm2 or 2×2,5 mm2
Ball pressure test temperature 75°C
Pollution degree 2 (domestic use)
Controller type 1C
Software class A
Storage temperature -20°C to +65°C
IP class 30
Protection class Class II –
Dimensions 86 x 86 x 16/40.5 mm (in-wall depth: 24.5 mm)
Weight 103 g

Safety Instructions

Please also note the following:

Mounting Instructions

Connect the thermostat according to the connection diagram.Danfoss -ECtemp -Next- Plus -Electronic -Thermostat - 2

Symbols

Danfoss -ECtemp -Next- Plus -Electronic -Thermostat - 3 Danfoss -ECtemp -Next- Plus -Electronic -Thermostat - 4

Settings

Power ON/OFF
Switch thermostat ON/OFF by pressing button on top of thermostat.

Initial Settings

The digits indicate the set value as follows:

No Parameter settings Settings range Default
P01 Working mode 01: Manual

02: Advanced Program- mable Timer

02
P02 Temperature control mode 01: Room and floor temp; 02: Only floor temp.;

03: Only room temp.*

01
P03 Maximum floor temperature 20-30˚C (only for 01 in P02)** 35˚C
P04 Frost protection 01: Enable; 02: Disable 01
P05 Frost protection setpoint 5-9˚C 5˚C
P06 Timer display option 01: 24h; 02 12h 01
P07 Room temp. display option at shutdown 01: No display surrent temp.;

02: Display current temp.

01

Advanced Programmable Timer

The Advanced Programmable Timer mode enables the setting of a timer-controlled program for automatic comfort temperature, and an energy-saving lower setback temperature if standard room comfort temperature is not required. The function consists of 2 programs:

P1 with 4 events in 5 days (Mon. Tue. Wed. Thu. Fri

P1, Event 1:

P1, Event 2-4:

P2 with 4 events in 2 days (Sat. Sun.).

P2, Event 1:

P2, Event 2-4:

The thermostat will continue the 4-event program based on the present time and day. To set and change the room temperature temporarily:

 

Days

Event 1 Event 2 Event 3 Event 4
Start time Temp Start time Temp Start time Temp Start time Temp
Mon – Fri. 6:30 20˚C

(27˚C)*

8:30 15˚C

(25˚C)*

16:30 20˚C

(27˚C)*

22:30 25˚C

(25˚C)*

Sat – Sun. 7:30 20˚C

(27˚C)*

9:30 20˚C

(27˚C)*

16:30 21˚C

(28˚C)*

22:30 25˚C

(25˚C)*

Temperature Setting

IMPORTANT: When the thermostat is used to control a floor heating element in connection with a wooden floor or similar material, always use a floor sensor and never set the maximum floor temperature to more than 35 ° C.

Thermal resistance [m2K/W] Examples of Flooring Details The approximate setting for 25˚C floor temperature
0.05 8 mm HDF based laminate >800 kg/m3 28˚C
0.10 14 mm beech parquet 650 – 800

kg/m3

31˚C
0.13 22 mm solid oak plank >800 kg/m3 32˚C
< 0.17 Max. carpet thickness suitable for floor heating acc. to EN 1307 34˚C
0.18 22 mm solid for planks 450 – 650

kg/m3

35˚C

Timer Setting

Safety Lock

Away Mode

Present Floor Temperature

Change to Room control only

Switch Power OFF

Switch Power ON

Extending Maximum floor temperature limitation to 45°C

Power OFF

Power ON
Press M button for 6 seconds Select P03 (Table in 4.2): raise floor temperature limitation higher than 35°C by using the >

Table for 4.9 Change to Room control only and 4.10 Extending Maximum Floor temperature limitations to 45°C

No. Function Setting Factory default
Danfoss ECtemp™ Next Plus
P01 Room Sensor Calibration Offset:-10˚C to

+10˚C

0˚C
P02 Floor Sensor Calibration Offset:-10˚C to

+10˚C

0˚C
P03 Maximum Room Temp. Limitation 5-35˚C(Active in Temperature Control Mode 01)  

35˚C

P04 Minimum Room Temp. Limitation 5-35˚C(Active in Temperature Control Mode 01)  

5˚C

P05 Maximum Room Temp. Limitation 5-35˚C(Active in Temperature Control Mode 02)  

35˚C

P06 Minimum Room Temp. Limitation 5-35˚C(Active in Temperature Control Mode 02)  

5˚C

P07 Setting range extension for P06, P07, P08 01: Max. 35˚C, 02:

Max. 45˚C

 

01

P08 Only room temperature control 01: Enable, 02: Disable  

02

Error Codes

E1 Room sensor failure
E2 Floor sensor failure
EE EEPROM failure
Lo Temperature lower than 0˚C
Hi Temperature higher than 5˚C

Warranty

5 year warranty

Disposal InstructionDanfoss- 088L0122- ECtemp -Touch- Thermostat- 30

Reference

Download Manual:

Danfoss ECtemp Next Plus Electronic Thermostat Installational Guide

OTHER MANUALS:

Danfoss ECtemp Next Plus Electronic Thermostat Product Specifications Guide

Danfoss-logo

Danfoss ECtemp Next Plus Electronic Thermostat Installational Guide

Leave a Reply

Your email address will not be published. Required fields are marked *

To respond on your own website, enter the URL of your response which should contain a link to this post's permalink URL. Your response will then appear (possibly after moderation) on this page. Want to update or remove your response? Update or delete your post and re-enter your post's URL again. (Find out more about Webmentions.)