The COMPUTHERM Q20RF type switch mode room thermostat is suitable for regulating a large majority of boilers, air conditioners, humidifiers and dehumidifiers in circulation. It can easily be connected to any gas boiler, air conditioner, humidifier and dehumidifier with a two-wire room thermostat connection point and to other electrical devices, regardless of whether the device has a 24 V or 230 V control circuit.
The device can be programmed as needed so that the heating/cooling or humidifier/dehumidifier system heats/cools and humidifies/dehumidifies your apartment or office to the desired temperature or humidity at the times you want, and it contributes to the reduction of energy costs in addition to providing comfort. Separate independent daily programs can be created for each day of the week. For each day, besides 1 fixed switching time.
(PROG 0) 10 freely adjustable (in 10 minutes increments) switching times (PROG 1– PROG 10) can be set, and a different temperature (in 0.5 °C increments) and humidity (in 1 percent increments) can be assigned to every switching times. The device is composed of two units: a portable control unit (thermostat) and a receiver unit that controls the device to be regulated. There is a wireless (radio frequency) connection between the two units therefore there is no need to lay a cable between the thermostat and the device to be regulated. The two units are practically in a synchronized state set at the factory. The thermostat and its receiver have their own safety code which guarantees secure operation of the device. For installation and connection of the receiver unit and its synchronisation with the thermostat please refer to Chapter 5. To extend the lifetime of batteries, the thermostat will not transmit signals continuously. Instead, it will repeat its relevant switch command every 5 minutes. Therefore, control is ensured even after a blackout.
The portability of the thermostat offers the following advantages:
The effective range of the transmitter incorporated in the thermostat is approximately 50 m in open terrain. This distance may become considerably shorter within a building, especially when a metal structure, reinforced concrete or adobe wall stands in the way of radio waves.
This wireless (radio-frequency) thermostat can also be easily extended with the COMPUTHERM Q1RX socket if needed, with which the thermostat is able to control any electrical device (e.g. fan heaters, pumps, zone valves, etc.) operating on 230 V (50 Hz; max. 16 A) according to the room temperature. (Detailed description of the COMPUTHERM Q1RX socket and usage suggestions can be found on our website www.computherm.info.)
The COMPUTHERM Q20RF thermostat can be used as an extension to the COMPUTHERM Q5RF or Q8RF multi-zone devices. The simultaneous use of several COMPUTHERM room thermostats and one COMPUTHERM Q4Z or Q10Z zone controller provides the possibility for the thermostats to also control a pump or a zone valve in addition to starting the heater or cooler. This way it is easy to divide a heating / cooling system into zones, thanks to which the heating/cooling of each room can be controlled separately, thus greatly increasing comfort. Furthermore, the zoning of the heating / cooling system will greatly contribute to the reduction of energy costs, as due to this only those rooms will be heated / cooled at any time where it is required.
It is reasonable to locate it in a room used regularly or for many hours per day so that it is in the direction of natural ventilation in the room but protected from drought or extreme heat (e.g. direct sunlight, refrigerator, chimney, etc). Its optimal location is 0.75 – 1.5 m above floor level. It is advisable to install the receiver of the COMPUTHERM Q20RF in wet, chemically aggressive or dusty environment. thermostat near the boiler, in a place protected from moisture, dust, chemicals and heat. When choosing the location of the receiver, also consider that a propagation of radio waves is prevented by heavy metal objects (e.g. boiler, buffer tank, etc.) or can be adversely affected by metal building structures. If you have it possibility, in order to ensure an interference-free radio frequency connection, we recommend that the receiver be away from the boiler and another large install it at a distance of at least 1 – 2 m from metal structures, at a height of 1.5 – 2 m. We recommend that you check the reliability of the radio frequency connection in the selected location before installing the receiver.
ATTENTION: Do not install the receiver under the boiler cover or in the immediate vicinity of hot pipes, as this may damage the device’s components and endanger the wireless (radio frequency) connection. To avoid electric shock, entrust the connection of the receiver to the boiler to a specialist.
IMPORTANT WARNING: If the radiator valves in your flat are equipped with a thermostatic head, adjust it to maximum temperature or replace the thermostatic head of the radiator valve with a manual control knob in the room where the room thermostat is to be located, otherwise the thermostatic head may disturb the temperature control of the flat.
Warning: Alkaline batteries may only be used for this appliance. Carbon-zinc batteries known as durable or long life batteries and chargeable accumulators are not suitable for the operation of this appliance. Icon
After the batteries have been inserted, the display flashes the day, time, program number, adjusted and measured temperatures, measured humidity level and icons showing the operating mode and battery power level. After inserting the batteries, snap the front panel of the device into the rear panel and touch the
WARNING: The device must be installed and connected by a qualified professional. Before installing, make sure that neither the thermostat or the device to be controlled is connected to the 230 V mains voltage. Modifying the thermostat can cause electric shock or product failure.
Unscrew the two screws at the bottom of the receiver unit without removing them. Following this, remove the front panel of the receiver unit then fix the back panel to the wall in the vicinity of the boiler with the screws provided. The marks of the connections are pressed into the plastic above the connection points: N, L, 1, 2, and 3.
Connecting the controlled device to the receiver unit
The receiver unit controls the boiler or air conditioner through a potential-free alternating relay whose connection points are: 1 (NO), 2 (COM) and 3 (NC). Connect the two connection points of the heating or cooling equipment to be controlled to the normally open 1 (NO) and 2 (COM) terminals of the relay, as shown on the below figure.
If you would like to operate an old boiler or any other device that has no connection points for thermostats, then the 1 (NO) and 2 (COM) connection points of the thermostat should be connected to the mains cable of the device, similarly as a switch would be connected, as shown in the figure below.
ATTENTION: Always consider the load ability of the receiver unit and follow the manufacturer’s instructions of the heating or cooling equipment. The device must be installed and connected by a qualified professional!
The voltage appearing at terminals 1 (NO) and 2 (COM) depends only on the system being controlled, therefore the dimensions of the wire are determined by the type of the device to be controlled. The length of the wire is of no significance, the receiver unit may be installed either near the boiler or far away from it, but do not install it under the housing of the boiler.
Connecting the receiver unit to the mains
230 V supply voltage should be applied to the receiver unit. This ensures power supply to the receiver unit but this voltage does not appear on the output connection points (1, 2 and 3). The neutral conductor and the phase line of the network should be connected to points N and L (Figure 3; no need to check correct phase sequence). There is no need for earth connection because the product is equipped with double insulation.
Turn the power on for the receiver unit. After a few seconds the wireless (radiofrequency) system (thermostat and receiver unit) are tuned into the operating frequency. As a test, in heating mode touch the
OPERATION OF THE THERMOSTAT THAT HAS BEEN PUT INTO OPERATION
The thermostat controls (manually or via programming) the devices (e.g. gas boiler, pump or dehumidifier) connected thereto on the basis of the humidity/temperature measured by it and being set, considering the switching sensitivity of the thermostat (±0.2 °C/±1.0% according to factory default) This means that when the thermostat is set to heating mode and 22 °C then at switching sensitivity of ±0.2 °C the connection points of the output relay of the receiver unit 1 (NO) and 2 (COM) close at a temperature below 21.8 °C (the heating system switches on), and open at a temperature above 22.2 °C (the heating system switches off). In cooling mode the relay switches conversely.
When the thermostat is set to humidifying mode and to 60%, then at switching sensitivity of ±1.0% the output relay of the receiver unit 1 (NO) and 2 (COM) close at a relative humidity below 49% (the humidifier switches on) and open at a relative humidity above 51% (the humidifier switches off). In dehumidifying mode the relay switches conversely. The closed state of the connection points 1 (NO) and 2 (COM) of the output relay is indicated by the
ATTENTION: According to factory default setting the key lock of the thermostat automatically switches on after 30 seconds which is indicated by the
The thermostat allows a number of setting options by which the operation of the thermostat can be tailored to your liking. You can enter the setting menu of the thermostat by pressing the button
The currently modifiable setting is flashing on the display. After the current day and exact time have been set, you can perform additional settings as follows:
Displayed abbreviation | Description of the setting | Setting options | Factory default setting | Detailed description |
FUNC |
Operating mode | HEA: heating |
HEA |
Chapter 7.1. |
COO: cooling | ||||
HUM: humidifying | ||||
DEH: dehumidifying | ||||
PROGRAM |
Switching on and off of programmed mode | OFF: Switched off. In this case the thermostat is working in a manually set Economy mode or comfort mode. |
ON |
Chapter 7.2. |
ON: Switched on. In this case the thermostat is working according to a pre-set program or manual mode. | ||||
T UNIT | Temperature unit | °C | °C | — |
°F | ||||
HYSTER | Switching sensitivity | ±0.1 – ±1.0 °C | ±0.2 °C | Chapter 7.3. |
±0.2 – ±2.0 °F | ±0.4 °F | |||
±1 – ±5% RH | ±1% RH | |||
MIN | Minimum adjustable temperature/ humidity | 5 – 45 °C | 5 °C | — |
41 – 97 °F | 41 °F | |||
0 – 98% RH | 30% RH | |||
MAX | Maximum adjustable temperature/ humidity | 5 – 45 °C | 35 °C | — |
41 – 97 °F | 95 °F | |||
1 – 99% RH | 80% RH | |||
T CALIB | Calibration of the temperature sensor | -3.0 – +3.0 °C | 0.0 °C | Chapter 7.4. |
-6.0 – +6.0 °F | 0.0 °F |
Displayed abbreviation | Description of the setting | Setting options | Factory default setting | Detailed description |
H CALIB | Calibration of the humidity sensor | -10 – +10% RH | 0% RH | Chapter 7.5. |
H LIMIT |
Setting humidity limit in case of cooling | OFF: function switched off |
80% RH |
Chapter 7.6. |
30-99: if the measured humidity is higher than the set value then the cooling system switches off | ||||
A LIGHT |
Automatic backlight | OFF: switched off |
ON |
— |
ON: switched on (backlight switches on for 10 seconds after any button has been pressed) | ||||
BRIGHT | Backlight brightness | 0 – 10 | 7 | — |
B LIGHT |
Backlight of the buttons | OFF: switched off |
ON |
— |
ON: switched on (backlight of the keys switches on and off simultaneously with the backlight of the display) | ||||
B SOUND | Acoustic signal when buttons are touched | OFF: switched off | OFF | — |
ON: switched on | ||||
LOCK |
Automatic key lock | OFF: automatic key lock is switched off |
ON |
— |
ON: automatic key lock is switched on (the key lock is activated 30 seconds after touching the last button) | ||||
PUMP | Switching on and off of the pump protection function | OFF: switched off | OFF | Chapter 7.7. |
ON: switched on |
Displayed abbreviation | Description of the setting | Setting options | Factory default setting | Detailed description |
SYNC |
Synchronisation with the receiver unit(s) | –: moving to the next setting after touching the button |
— |
Chapter 7.8. |
SYN: the thermostat is synchronised with the receiver(s) set to synchronisation mode in its environment after touching the button | ||||
TEST |
Testing wireless communications | –: moving to the next setting after touching the button |
— |
Chapter 7.9. |
ON: the thermostat changes to test mode after touching the button | ||||
RESET |
Restoring factory default settings | –: saving the settings and exiting the settings menu after touching the button |
— |
Chapter 7.10. |
ON: restoring factory default setting after touching button |
To exit the setting menu and save the settings:
You can easily switch between heating (HEA; factory default setting), cooling (COO), humidifying (HUM) and dehumidifying (DEH) modes. The connection points of the output relay of the receiver unit 1 (NO) and 2 (COM) close at temperatures below those set in the heating mode, at temperatures above those set in the cooling mode, below the humidity level set in the humidifying mode and above the humidity level set in the dehumidifying mode (taking the switching sensitivities into account).
The thermostat can be used in both programmed and non-programmed modes. When the programmed mode is on, in automatic (programmed) mode the thermostat controls the devices connected thereto according to the pre-set program, but it can be switched to manual mode by touching the
The switching sensitivity can be adjusted. By modifying this value, you can define the difference below/above the set temperature/humidity where the thermostat should switch on/off the device connected thereto. The smaller this value, the more stable is the inner temperature/humidity in the room and the comfort improves. Switching sensitivity does not affect the heat loss of the room (building) and vapour formation.
When higher comfort level is needed, it is reasonable to select the switching sensitivity so that it ensures as stable inner temperature/humidity as possible. On the other hand, two frequent starts and stops of the controlled device should be avoided because this may reduce the efficiency and lifetime of the device. The switching sensitivity can be set in the temperature range of ±0.1 °C to ±1.0 °C / ±0.2 to ±2.0 °F and in the humidity range of ±1 to ±5% RH. Apart from some special cases, we propose to use ±0.1 °C or ±0.2 °C (factory default) when a heating/cooling system should be controlled. For humidification/ dehumidification, we recommend you use a switching sensitivity of ±1% (factory default) or ±2%. For more information about switching sensitivity please refer to Chapter 6.
Calibration of the temperature sensor (T CALIB)
The accuracy of the thermometer of the thermostat is ±0,5 °C. The temperature displayed by the thermostat can be modified by maximum ±3.0 °C / ±6,0 °F compared to the temperature measured by the temperature sensor, in increments of ±3.0 °C / ±6.0 °F or 0.1 °C / 0.1 °F.
Calibration of the humidity sensor (H CALIB)
Setting the humidity limit for cooling (H LIMIT)
When a cooling system including surface cooling is controlled, it is important that the air in the room must not reach dew point because in this case condensation occurs which can cause serious damages. Using this function, you can set the humidity level above which the thermostat will stop cooling to prevent condensation.
Switching on and off of the pump protecting function (PUMP)
In order to prevent the pump from jamming, the activated pump protection function will start the devices connected thereto for 1 minute every day at 12:00 p.m. (noon), if switching was not done either on the respective day or on the previous day (e.g. during non-heating period). The pump protectionfunction only works when the controlled device is in operable condition.
Synchronisation with the receiver unit(s) (SYNC)
The thermostat and its receiver unit have been synchronized at the factory. When communication is not working between the two units they should be synchronized again. To do so, press and hold (for approx. 10 seconds) the “ON/OFF” button of the receiver unit until the green LED start to flash. Now the receiver unit is in synchronization mode. Then in the setting menu at function SYNC choose option “SYN” and move on with the
Attention: If you wish to synchronize several wireless COMPUTHERM Q series products with one thermostat at the same time or to synchronize a single wireless COMPUTHERM Q series product with several thermostats simultaneously, for detailed information please read Chapter 12.2.
Testing wireless communications (TEST)
With the “TEST” function you can check whether the wireless (radio frequency) connection between the thermostat and its receiver unit functions properly. To this end choose the “ON” option at the “TEST” function in the setting menu and move on with the
In the meantime,
Restoring factory default setting (RESET)
This function resets all settings of the thermostat to factory default. To restore factory default setting choose option “RES” at “RESET” function in the setting menu and move on with the
The thermostat has the following four operating modes:
Touching the
The thermostat can be used for control on the basis of temperature and humidity alike. In every mode the temperature/humidity to be maintained by the thermostat can be defined in 0.5 °C / 0.5 °F / 1% increments within the intervals specified in the settings.
Economy mode (
In economy mode the thermostat provides the economical (e.g. nighttime) temperature/humidity corresponding to the set temperature/humidity in the vicinity of the place of installation. Using the
Comfort mode (
In comfort mode the thermostat provides the comfort (e.g. daytime) temperature/humidity corresponding to the set temperature/humidity in the vicinity of the place of installation. Using the
Manual mode (
In manual mode the thermostat provides the temperature/humidity corresponding to the set temperature/humidity in the vicinity of the place of installation until the next intervention. Using
A description of programming
Steps of programming the device
If you would like to copy the program written for the day selected in section “b” to another day/other days you can easily do it by means of the “COPY” function as described in Chapter 8.4.3.
The use of “COPY” function (copying the program of a day to another day or other days)
Attention: The “COPY” function may only be used for programming the days of the week separately!
Touch the
Modifying the programs of the device
Program inspection
The temporary manual mode can only be used in programmed mode until the next program switching. For activation, with buttons
During the temporary manual mode the segments indicating the time on the display alternately show the exact time (TIME), and the time remaining in manual control (TIME LEFT) (e.g.4:o2, that is 4 hours and 2 minutes). After this time, the
The party program can be used in any default mode of the thermostat. For activation touch the
During the holiday program the segments indicating the hour on the display alternately show the exact time (TIME) and the number of days remaining in temporary manual control (TIME LEFT) (e.g. “ 3D ” that is 3 days). When the remaining time decreases below 24 hours then from then on the remaining time is displayed in the same as at the party program (e.g. 22: 18, that is 10:18 p.m.). After this time, the icon
By factory default the backlight of the thermostat automatically switches on for 15 seconds after touching any button. Regardless of the automatic backlight, touching the
You can switch off the control buttons of the thermostat to prevent the settings from accidental or unauthorized modifications. Touching the
The average life span of the batteries is 1 year, but frequent use of backlight can shorten this period considerably. When the
Attention: Only high-quality alkaline batteries may be used in the device. So called durable or long-life zinc-carbon batteries are unsuitable for the operation of the devices. The
The receiver unit switches its potential-free output in accordance with the switching signals of the wireless Q series COMPUTHERM room thermostat(s) which is/are synchronized with the unit.
A green and a red LEDs indicates the operating condition of the receiver unit as detailed below:
Chapter 4. outlines optimal location of the receiver unit, its connection and commissioning are discussed in Chapters 5.2. and 5.3., testing of the wireless communication are found in Chapter 7.9., while the synchronization process and manual operating mode are described in the following sub-chapters.
The receiver unit and its thermostat were harmonized at the factory. If you find that the thermostat fails to control the receiver unit or you intend to control it with another COMPUTHERM Q series room thermostat (too), then they should be synchronized. Synchronize the thermostat as described in Chapter 7.8. If you intend to synchronize several wireless COMPUTHERM Q series receiver units/sockets with one thermostat then first set all receiver units to synchronization mode than perform the steps of synchronization.
If you wish to synchronize more than one thermostat with the receiver unit then repeat the previous steps with the other thermostats, too. When you reach the maximum permissible number of synchronizable products (12) then, after pressing the “ON/OFF” button for 10 seconds, the red and green LEDs on the product flash alternately three times. In this case, pressing the “ON/OFF” and “MANUAL” buttons for 10 seconds, the receiver unit should be set to the default position for the synchronization of the new thermostat. Then both LEDs light up for 2 seconds, indicating that the receiver unit is reset and the synchronization of the new thermostat can commence.
Attention: If you want a given thermostat not to control the receiver unit then synchronize the thermostat with another wireless COMPUTHERM Q series device, perform the steps of synchronization on the thermostat alone (without receiver unit), or reset the receiver unit to factory default as described above.
Manual control of the receiver unit
Pressing the “MANUAL” button disconnects the thermostat(s) from the receiver unit synchronized with it/them. Then the device connected to the thermostat can only be switched on and off manually, without any temperature/humidity control. The continuous light of the green LED indicates the manual mode. Pressing the “ON/OFF” button switches on or off the device connected to the receiver unit. (The red LED lights when the output is on). Pressing the “MANUAL” button again ceases manual control and resets automatic operation (controlled by thermostat) (the green LED goes out).
When you think that your appliance is operating incorrectly or encounter any problem while the appliance is being used then we recommend that you read Frequently Asked Questions (FAQ) available on our website, where we collected the problems and questions that most frequently occur while our appliances are being used, along with the solutions thereto: https://www.computherm.info/en/faq
The vast majority of the problems encountered can be solved easily by using the hints available on our website, without seeking professional help. If you have not found a solution to you problem, please pay a visit to our qualified service.
Remark
In addition to using modern temperature regulators, the following up-to-date regulation methods also contribute significantly to the improvement of the comfort provided by the heating network, the energy efficiency of the heating network and the coefficient of performance:
Total weight of the device: approx. 351 g (thermostat + receiver + holder)
The COMPUTHERM Q20RF type thermostat complies with the requirements of directives RED 2014/53/EU and RoHS 2011/65/EU.
Copyright © 2022 Quantrax Ltd. All rights reserved.
DOWNLOAD MANUALS:
COMPUTHERM Q20RF Programmable Wireless Thermostat Operating Instructions
COMPUTHERM Q20RF Programmable Wireless Thermostat Operating Instructions
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…