NOTE: These communicating thermostats communicate via a 4-wire Modbus protocol and will only operate with the Aurora Control System. TPCM32U03* is not applicable to variable-speed compressor equipment.
Adjusting Temperature (Temporary Override in Programmable models)
Setting Date And Time
Hold Setting
Vacation and Permanent (Programmable models only) This section describes the HOLD functions. You can program the thermostat to hold the temperature for a period of time.
If you want to hold the temperature for a few hours or a few weeks, your thermostat can accommodate your schedule.
Vacation Hold
(Programmable models only)
The thermostat can operate the fan in four ways: AUTO (on only during heating and cooling calls) ON (always on) INTERMITTENT (cycles fan) Pg. 3 PROGRAMMED FAN (fan follows the program set in the program menu screen) (programmable models only) Pg. 3
Changing Modes
NOTE: If selecting EMERGENCY HEAT, the backlight color will change from blue to red indicating that auxiliary heat is operating instead of the heat pump compressor. Auxiliary/emergency heat is significantly more expensive to operate than the heat pump compressor, and should not be selected unless the heat pump compressor is not operational.
Fahrenheit or Celsius
Contrast Adjustment
You can change the contrast level of your thermostat screen to be displayed to your preference.
Backlight ON Time
This thermostat has a two-color backlight feature. Anytime
a button is pressed, the blue backlight stays on for a certain amount of time. A red backlight is visible if you are selecting Emergency Heat mode. You can adjust the amount of time the backlight stays on in the menu options.
(programmable models only) Preset Programming Preset options will step you through the programming. Simply select the temperatures and then view the completed program. Programming a Day or a Series of Days
Copying A Program From One Day To Another
In the PROGRAM menu, there is an option to COPY. The option can be used to copy the program from one day to another day. After COPY is selected, the thermostat will prompt you for which day to copy from. Next, it will prompt you for which day to copy the program to. After these selections, it will then confirm what is being copied to where. At this point, you have the option of canceling the copy process, by pressing ◄ to return to the copy menu, or saving what you have by pressing the center button ■. The SAVED screen will appear returning you to the copy menu. Pressing ◄ will return you to the PROGRAM menu. Pressing ◄ again will return you to the MAIN MENU.
Security Lockout
This thermostat has the option to set security features to lock out everything but the adjustment of the temperature or a total keypad lockout.
Humidity Offset
This option allows the calibration of the humidity sensor. Adjustments can range between -10% and +10%. The default is 0% offset.
Auto Changeover
With the auto changeover, the thermostat automatically switches itself from heating to cooling, or vice versa, based on the setpoints. When setting up the thermostat you have to enter both a cooling setpoint and a heating setpoint. The thermostat will also prevent the user from setting the cooling setpoint lower than the heating setpoint. The mode is set to AUTO for this operation to work.MENU → SETTINGS → AUTO CHANGEOVER Time – This setting sets the minimum off time before the thermostat can change from one mode to another. The default is 5 minutes. The range is from 0-120 minutes in 15-minute increments. Auto or Manual Change – Default is AUTO. If MANUAL is chosen, you will need to change from heating to cooling or vise versa. When MANUAL is set, AUTO is removed from the MODE screen as a choice.
Instantaneous Energy Monitoring can be found under the main menu if the energy monitoring option has been enabled on the Aurora Control System. The screen displays energy usage in real-time, the current mode of the heat pump, and the outdoor air temperature (if installed).
Superboost (Variable Speed Heat Pumps ONLY)
Superboost can be found under the main menu. The Superboost option temporarily enables a larger cooling capacity range. The screen will allow the homeowner to turn on or off the Superboost option. The option will enable by default for a 24-hour period of time and then will automatically be disabled.
WARNING: OVERUSE OF THIS OPTION MAY CAUSE OVERHEATING OF LOOPS.
Intermittent Fan
Temperature conditions can vary widely between the thermostat location and extremities of the space the thermostat serves. This air stratification problem can be especially pronounced during mild outdoor conditions when long periods elapse between space conditioning demands from the thermostat. This intermittent fan operation can also improve the performance of air cleaning or special filtration systems that locate the cleaning or filtration media at the return air side of the fan.
Service Information
MENU → SETTINGS → SERVICE INFO These screens help an installer or contractor to have a good understanding of what problems might be occurring before arriving for service.
WARNING: Before installing the thermostat, turn off all power to the unit. There may be more than one power disconnect. Electrical shock can cause personal injury or death.
Installer Information/Advanced Features
Safety Considerations
Improper wiring or installation may damage a thermostat. Wiring must conform to local and national electrical codes
Introduction
The thermostat is a wall-mounted, low-voltage thermostat that maintains room temperature by controlling the operation of a heating and air conditioning system. Batteries are not required; temperature and mode settings are preserved with the power off.
Installation Considerations
The thermostat requires no batteries. The thermostat is not a power-stealing device and MUST have both R and C connected.
Thermostat Location
The thermostat should be mounted:
The thermostat should NOT be mounted:
All excess wire should be pushed back into the wall as far as possible. Excess wire inside the thermostat plastic case may interfere with the air flow across the temperature sensor. Thermostat Connections
The dashed line represents an optional, but highly suggested, “W” terminal connection for Loss of Communication Backup Heat.
Installer Settings
NOTE: These options are intended to be used by the installer. End users are not advised to change or modify any of these settings. Doing so may make your equipment stop working properly and/or may void the warranty of the thermostat as well as the equipment hooked up to the thermostat. To access the installer setting menu, the mode must be set to OFF. Then, press both the up and down arrow keys at the same time for at least 5 seconds to enter the installer screen.
Model Configuration
Options to select from
PROGRAMMABLE / NONPROGRAMMABLE, SINGLE-STAGE/MULTI STAGE
NORMAL/DUAL FUEL/INTELLIGENCE STANDARD/ INTELLIGENCE NO DOWN STAGING Normal – used for normal operation
Dual Fuel – used on dual fuel systems. Needs an outdoor sensor to lockout dual fuel. IntelliZone Standard – used with IntelliZone. The ‘W’ acts like a Y3 and requires less droop. It activates 3rd stage with the same time/temperature weighting as Y1 and Y2. IntelliZone No Down Staging – used with IntelliZone and if used, SHOULD BE ONLY ON MAIN ZONE. The thermostat will hold the deepest call encountered and should minimize compressor speed changes.
Each of these options has settings for Cumulative Run Time and Calendar Time. Messages will flash at the top of the Main screen when these events are met to alert the owner that it is time to service these options.
Air Filter – Cumulative Run Time default is 1000 hours and Calendar Time is 6 months. Values can range from 400-3600 hours for Cumulative Run Time (in 100-hour increments), or Calendar Time can be set to OFF, or 3-48 months (in 3-month increments).
To cancel the message, select the CANCEL ALARM, and press the center button ■.
Input Dealer Info
Contractors are able to input Contractor Name and Contractor Phone number into these screens. The model and serial number are communicated from the unit. This way, the owner could give this information to the contractor so that he would know what system the owner has prior to the service visit.
Fan with Heat Option
Options are ON or OFF. This selection determines whether G (fan) output is to be ON or OFF when W (auxiliary heat) output is ON.
Humidity Option (TPCM32U04 Only)
If your system is set up with a humidifier, or you desire a dehumidification option, select the appropriate setting.
To adjust the Set Point for Humidification or Dehumidification, Select the RH from the Main menu. The values can be selected and adjusted from that screen.
NOTE: If you have an outdoor sensor attached to the thermostat, the Humidification setting is adjusted automatically based on the outdoor temperature.
Humidify – Turns on the H output when the room humidity is below the set point and MODE is set to HEAT, EHEAT, or AUTO when Heating was the last mode run.
Dehumidify – Turns on the DH output when the room humidity is above the set point and the MODE is set to COOL or AUTO when Cool was the last mode run.
Both – HUMIDIFY operates in the HEAT mode and
DEHUMIDIFY operates in COOL mode.
None – Neither is active.
Reversing Valve Option
Option of the reversing valve (O output) being on when in cooling or heating. The default is COOLING.
Restore Defaults
This will allow you to revert to the factory default settings.
Anticipator
This adjustment controls the sensitivity and cycle rate of the thermostat. Higher numbers decrease the cycle rate. Lower numbers increase the cycle rate. The default value is 0, and the range is 0-4.
Differential
This adjustment will vary the number of degrees, from the set point, before a call for heating or cooling is made. Adjustments can range between 0.5˚ and 4˚ differential. The default is 0.5˚ offset. (If your set point is 70˚F in heating, your thermostat will not call for heat until the temperature is 69.5˚F, with a 0.5 differential).
Cycles Per Hour
This feature will not allow more than the specified number of equipment cycles per hour. Values can range from 4 or 6 (or 1 cycle every 15 minutes (default) or 1 cycle every 10 minutes, if 6 is set). The factory default setting is 4. This default selection will provide optimum performance in nearly all installations.
MENU → SETTINGS → CYCLES PER HOUR
Program Settings
MENU → SETTINGS → PROGRAM SETTINGS
Smart recovery is a feature of your thermostat designed to improve comfort by adjusting temperatures to achieve a room temperature by the programmed time. When it’s time for a programmed temperature change, smart recovery begins working in advance, turning the system on and off as needed to adjust the indoor temperature. During these transition periods, you may notice that the actual temperature and your temperature setting don’t match. That’s a smart recovery in action, adjusting temperatures in small increments for greater energy efficiency. This is more energy efficient than simply allowing the system to operate at full capacity until the desired temperature has been met. Smart Recovery helps avoid excessive use of auxiliary heat when recovering from night setbacks in the heating mode.
Events Per Day
This is where you can set the number of events per day. (An event is a period of time scheduled with a certain heating and cooling setpoint.) For instance, if you are away from your home from 8am to 5pm, make this period of time an event and set the thermostat at an energy-saving setting. You have the option of setting the events per day to 4-RESIDENTIAL (4 events), 2-RESIDENTIAL (2 events) or 2-BUSINESS (2 events).
Smart Heat Staging (Heat Pump Only)
This delays 3rd stage heating for a set time. Options are ON or OFF. The default is OFF. The range for this are 0-120 minutes in 5-minute increments. If set to ON, 30 minutes is the default time.( If ‘ON’ is selected and the demand has not been satisfied the thermostat will energize electric heat after the selected time has expired regardless of demand.)
Cooling Lockout
When an outdoor temperature sensor is installed, it can be set up so the cooling option doesn’t energize if the outdoor temperature is below a certain temperature. Ranges for this are NONE
(default), 45˚F, 50˚F, or 55˚F.
Electric Heat Or Dual Fuel Lockout
When an outdoor temperature sensor is installed, you can set it up so the electric heat or Dual Fuel option doesn’t energize if the outdoor temperature is above a certain temperature. Ranges for this are NONE (default), 5˚F to 60˚F in 5˚ increments.
Compressor Satisfy
Normal – Allows compressor downstaging from Y2 to Y1. Recommended setting for most products. Y2 Finish – Once the heat pump has engaged Y2 the thermostat will not allow downstaging to Y1. The call is satisfied in Y2.
Remote Sensor
Allows selection of the remote sensor to determine indoor temperature. Options are REMOTE SENSOR, AVERAGE, and STAND ALONE. The REMOTE SENSOR is connected to the ID and GND on the thermostat terminals.
Non-Critical Faults
Non-critical faults are displayed below the temperature on the main screen. These faults will clear themselves if the fault condition corrects itself. Your dealer should be informed when either a critical or non-critical fault occurs.
Lockout/Critical Faults
Critical faults will change the screen to the service needed screen and turn the backlight color to red. The system can be reset by pressing the left arrow key on the thermostat. Some of the faults will clear themselves if the fault condition corrects itself. Your dealer should be informed when either a critical or non-critical fault occurs.
Fault Reference
Fault Code | Fault Description |
1 | Inputs Error (O and W) |
2 | High Pressure |
3 | Low Pressure |
4 | Freeze Detection (FP2) |
5 | Freeze Detection (FP1) |
7 | Condensate Overflow |
8 | Over/Under Voltage |
9 | Air Flow/RPM |
10 | Compressor Monitor |
11 | FP1 or FP2 Sensor Error |
15 | Hot Water Limit |
18 | Non Critical Communication Error |
19 | Critical Communication Error |
NOTE: For a complete list of fault codes, please reference the unit’s manual. The Manufacturer has a policy of continual product research and development and reserves the right to change design and specifications without notice.
Download Manual:
Waterfurnace TPCM32U03 Elite Communicating Thermostats Instruction Guide
Waterfurnace TPCM32U03 Elite Communicating Thermostats Instruction Guide
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…