The TF85L Thermostat provides 24VAC single-stage temperature control of 2 pipe and 4 pipe fan-coil applications with automatic control of a 3 speed fan along with manual heat/cool changeover. The TF85L Thermostat is mercury free and requires no batteries. All set points are retained permanently in non-volatile memory in case of a power interruption.
WARNING
Read these instructions thoroughly before installing product. Failure to follow these instructions could damage the product or cause a hazardous condition. Check the voltage and current ratings on the product to ensure that it is suitable for your application. Installer must be a trained, experienced service technician. Check product for proper operation after installation.
CAUTION
Damage to heating and cooling system may occur. Disconnect power from the equipment at the main breaker/fuse block while installing the thermostat.
Mounting Location
Mount the thermostat approximately 5 ft. (1.5m) above the floor in a location that is free from direct sunlight, heat from appliances, hot or cold air from ducts, concealed pipes and chimneys, and drafts or dead spots behind doors or in corners. Do not mount on exterior wall, if possible. Failure to locate thermostat mounting as indicated will result in poor temperature control.
Note: Level thermostat mounting is for appearance only and is not required for proper thermostat operation.
Mount and Wire the Thermostat
Set up mode
Press and hold
Note
Example 1 : The Display shows P2 steady means the thermostat is set up for Continuous Fan operation
Change the Set Up Parameters
Note: If
Power
Press
Heat/Cool (For Manual changeover only)
Note: – This button is deactivated for Auto changeover model. Heat/Cool mode can not be changed.
Fan
Auto mode icon
The speed will be adjusted according to the difference between the room and the setpoint temperature.
Note : Fan speed defaults to Automatic after 1 hour if it is changed by the user to a particular speed.
Continuous Fan
FAN is always on in High, Medium or Low speeds as long as the thermostat is powered.
Cycled Fan Standard
Fan is on when the heat or cool outputs are on (on cycle). Automatic fan operation is active in the on cycle. When the heat or cool outputs are off (off cycle), the Fan output is off. The Fan icons (Auto, High, Med and Low) are all turned off. The
Cycled Fan Override
Fan is on when the heat or cool outputs are on (on cycle). Automatic fan operation is active in the on cycle. When the heat or cool outputs are off (off cycle), the Fan output is off. The Fan icons (Auto, High, Med and Low) are all turned off. The button
Warning: This mode should not be selected for hydronic applications with no control valves.
Excessive heating can result if the Fan is turned on manually
Auto Fan Speed Timer
Fan speed defaults back to Automatic after 1 hour (or 3 hours based on P1 flashing setting) if it is changed to a particular speed.
Temperature setting
T200 Manual changeover
T201 Auto changeover
Note: – icon on LCD display 6 indicates the auto changeover model.
System status
Display at 7 shows ON when there is a demand for heating or cooling. The LCD ON icon will flash when the delay time is activated. Default system delay time is 3 minutes.
Sensor Error Alarm
If the thermostat temperature sensor is defective, the thermostat will turn off the equipment and start flashing “SE” on the display.
Auto Restart
All the setup parameters are stored in non volatile memory. When there is a power failure and return to normal, the thermostat will resume operation with the previous setup parameters.
External Sensor
VTRONIX, LLC Po Box 267096, Weston, FL 33326
Copyright © 2017 Vtronix Document no. 170064-110E (Rev.00)
DOWNLOAD MANUAL:
Vtronix TF85L-200 Digital Room Thermostat INSTALLATION MANUAL
Vtronix TF85L-200 Digital Room Thermostat INSTALLATION MANUAL
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…