The TF85L Thermostat provides 24VAC single stage temperature control of 2 pipe and 4 pipe fan-coil applications with automatic control of a 3 speed fan along with manual heat/cool changeover. The TF85L Thermostat is mercury free and requires no batteries. All set points are retained permanently in non-volatile memory in case of a power interruption.
WARNING
POWER SUPPLY | |
24 VAC system | 18 – 30 VAC, 50/60 Hz |
TEMPERATURE : | |
Temperature accuracy | ± 1.8 °F |
Storage temperature | 32 – 158 °F |
Ambient temperature | 50 – 122 °F |
Setting temperature range | 64 – 85 °F |
Deadband (Auto changeover model) | ± 1 °F of Setpoint |
HEAT and COOL RELAY : ( P1, P2) | |
Rating (resistive load) | |
· Maximum switching capacity | 3 A 277 VAC |
· Delay Time | 1 minute or 3 minutes (default) |
FAN RELAY: (P3, P4, P5) | |
Rating (resistive load) | |
Maximum switching capacity | 2 A 277 VAC 3 A 125 VAC |
Read these instructions thoroughly before installing product. Failure to follow these instructions could damage the product or cause a hazardous condition. Check the voltage and current ratings on the product to ensure that it is suitable for your application. Installer must be a trained, experienced service technician. Check product for proper operation after installation
Mounting Location
Mount the thermostat approximately 5 ft. (1.5m) above the floor in a location that is free from direct sunlight, heat from appliances, hot or cold air from ducts, concealed pipes and chimneys, and drafts or dead spots behind doors or in corners. Do not mount on exterior wall, if possible. Failure to locate thermostat mounting as indicated will result in poor temperature control.
Note: Level thermostat mounting is for appearance only and is not required for proper thermostat operation
Press and hold TEMP
Note
Example 1 : The Display shows P2 steady means the thermostat is set up for Continuous Fan operation.
Change the Set Up Parameters
Note: If POWER button is pressed before exiting from the set up mode (Section d above), the thermostat will exit without changing the setup parameters. P4 setting applies only when P2 is set to Cycled Fan
Power
Press POWER to turn on/off the equipment. The thermostat will operate to the set point stored in non volatile memory.
Heat/Cool (For Manual changeover only)
Note: This button shows the status for the Auto changeover model. Heat/Cool can not be changed.
Fan
Auto mode
Note: Fan speed defaults to Automatic after 1 hour if it is changed by the user to a particular speed.
Continuous Fan
FAN is always on in High, Medium or Low speeds as long as the thermostat is powered.
Cycled Fan Standard
Fan is on when the heat or cool outputs are on (on cycle). Automatic fan operation is active in the on cycle. When the heat or cool outputs are off (off cycle), the Fan output is off. The Fan LEDs (Auto, High, Med and Low) are all turned off. The Fan button is deactivated in the off cycle. During the on cycle the fan speed can be manually changed. The fan will turn off in the off cycle and revert back to the selected fan speed during the on cycle.
Cycled Fan Override
The fan is on when the heat or cool outputs are on (on cycle). Automatic fan operation is active in the on cycle. When the heat or cool outputs are off (off cycle), the Fan output is off. The Fan LEDs (Auto, High, Med, and Low) are all turned off. The Fan button can be activated in the off cycle. The appropriate Fan LED (High, Med and Low) is turned on and the appropriate output is energized. It stays at this speed during the on-cycle as well as the off-cycle. This is subject to the automatic fan speed default timer.
Warning: This mode should not be selected for hydronic applications with no control valves. Excessive heating can result if the Fan is turned on manually.
Auto Fan Speed Timer
Fan speed defaults back to Automatic after 1 hour (or 3 hours based on P1 flashing setting) if it is changed to a particular speed.
Press TEMP
T200 Manual changeover
T201 Auto changeover
System status
LED at turns on when there is a demand for heating or cooling. LED will flash when the delay time is activated. The default system delay time is 3 minutes.
Sensor Error Alarm
If the thermostat temperature sensor is defective, the thermostat will turn off the equipment and start flashing “SE” on the display.
Auto Restart
All the setup parameters are stored in non-volatile memory. When there is a power failure and returns to normal, the thermostat will resume operation with the previous setup parameters
DOWNLOAD MANUALS:
Vtronix TF85L –10011 Digital Room Thermostat INSTALLATION MANUAL
Vtronix TF85L –10011 Digital Room Thermostat INSTALLATION MANUAL
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…